Servo (0x0056) and spindle (0x0040) meter records are 8 bytes:
[i32 value][u16 base][u16 exponent], the same self-describing envelope as the
position blocks.
Servo: offset 4 was read as a decimal count. It is the BASE (a steady 10), so
every load was divided by 10^10 and published ~0 -- the sister ignitionoee panel
read servo 0% on every axis of a Makino cutting at 20,000 rpm. Loads are now
value / base^exponent, a direct percentage.
Spindle: the raw meter is a 1/16384 fraction of full scale. Settled on the real
Z-34184 by regressing the type-1 meter against cnc_rddynamic2 spindle speed over
596..20,000 rpm (rpm = 1.220749 x meter; 16384 x 1.220749 = 20000.75). So:
- Spindle/{name}/Load publishes % of rated load (Float64; was the raw Int32
count -- a reading of 9155 meant 55.9%).
- Spindle/{name}/MaxRpm is RENAMED Spindle/{name}/MotorSpeedPct (Float64, % of
maximum speed) and is polled with Load. The old node was actively wrong: the
type-1 meter is the live motor speed, and it was read once at bootstrap and
served forever as if it were a max-RPM constant. Client-visible: FIXED: tags
on .../MaxRpm must be re-pointed.
- The spindle read no longer stops at the first zero after slot 1 (which dropped
an idle second spindle and kept non-zero residue); every slot is returned.
A record whose envelope is undescribable (base not 2/10, exponent > 18 -- e.g.
residue past the configured axis/spindle count) publishes BadNoData, never a Good 0.
Ported from the sister ignitionoee FOCAS driver v0.17.2/v0.17.3 (Focas.Wire-019);
live captures live-spmeter-{load,maxrpm}-0x0040.bin added as fixtures.
Every 0x0026 position block is self-describing: [i32 raw][u16 base][u16 exponent],
value = raw / base^exponent. The live 31i-B capture (ref-dynamic2-axis1.bin)
reports base 10 / exponent 4 on every block, so axis 1 is 280.1574 mm, not
2801574. The driver ignored the envelope and instead sent 'cnc_getfigure'
(0x00D3) -- a command that does not exist in the FOCAS wire protocol, served only
by the in-tree mock; the real control refuses it with rc=1, so on hardware every
position fell back to PositionDecimalPlaces (default 0) and published raw counts.
- ParsePositionBlock decodes the envelope into FocasPosition; the driver applies
raw / base^exponent at publish. PositionDecimalPlaces is now only the fallback
for a scale-less (4-byte) block.
- A block describing no position (0xFFFF vacant marker, base not 2/10, exponent
> 18 -- raw / 10^400 would read as a Good 0.0) publishes BadNoData on that node
alone; siblings are untouched.
- ReadPositionFiguresAsync / IFocasClient.GetPositionFiguresAsync and the
per-axis figure cache are deleted.
Ported from the sister ignitionoee FOCAS driver v0.17.0 (+ Focas.Wire-014);
live axis-scoped captures live-dynamic2-axis{1,2}-0x0026.bin (Z-34184 X 0.0374,
Y 370.177) added as fixtures.
Adds <summary>/<param>/<returns>/<inheritdoc> where missing and removes
project bookkeeping IDs (task/tracking refs) from shipped code comments,
so the docs read cleanly and CommentChecker is quiet except for known
false positives (PLC/protocol terms, event/IEqualityComparer inheritdoc).
Doc/comment-only; no logic changed; solution builds clean.
Equipment tags were stuck at Bad_WaitingForInitialData on the deployed driver: the equipment poll, fixed-tree loop, probe and recycle shared one FOCAS/2 socket with no serialization, and the steady-state read had no timeout — concurrent reads collided and a stalled read hung forever, never overwriting the node's initial-data seed.
- SynchronizedFocasClient: per-device SemaphoreSlim gate + per-call timeout around every wire op (Connect/Probe gated, not double-bounded); wired in EnsureConnectedAsync. ReadAsync/WriteAsync map a per-call timeout to BadCommunicationError instead of rethrowing.
- FlexibleStringConverter on FOCAS config Series: the AdminUI persists the enum as a number ("series":6); accept number-or-string instead of throwing -> stub.
- FocasHostAddress.TryParse tolerates a scheme-less {ip}[:{port}] (AdminUI hostAddress form); canonical focas:// unchanged, malformed schemes still rejected.
247 FOCAS tests green; each fix has a regression test. Live-validated on wonder-app-vd03 (tags read Good).