Part 9 ConditionType.Quality was never assigned; default(StatusCode)==Good
so every native + scripted condition reported Good unconditionally — a
comms-lost device still showed a healthy, inactive, Good condition (a
wrong-VALUE bug, distinct from the null-value #473/#475). Clients (and HMIs
bucketing on IsGood) could not tell "genuinely inactive" from "lost contact".
Layer 1 — make Quality a real, plumbed field:
- AlarmConditionSnapshot gains OpcUaQuality Quality (default Good).
- MaterialiseAlarmCondition sets it (native BadWaitingForInitialData, scripted Good).
- WriteAlarmCondition projects snapshot.Quality; the delta-gate gains a Quality
member so a quality-bucket change fires a Part 9 event.
Layer 2 — drive native quality from driver connectivity (a comms-lost driver
emits no alarm transitions, and an alarm-bearing raw tag has no value variable,
so quality can't come from either existing channel):
- DriverInstanceActor Tells parent ConnectivityChanged on Connected/Reconnecting.
- DriverHostActor fans it to every native condition the driver owns as
OpcUaPublishActor.AlarmQualityUpdate (Good on connect, Bad on disconnect).
- New dedicated IOpcUaAddressSpaceSink.WriteAlarmQuality sets ONLY Quality and
fires only on a bucket change — never touches Active/Acked/Retain (an active
alarm that loses comms stays active). Not a full-snapshot re-projection, so it
can't clobber severity/message and works for a never-fired condition.
Forwarded through DeferredAddressSpaceSink (F10b trap; auto-verified by the
reflection forwarding guard). Ungated by redundancy role; no /alerts row.
Scripted conditions stay Good; worst-of-input quality deferred to #478 (Layer 3).
Tests: node-level (materialise/project/no-clobber/unknown-node no-op),
NativeAlarmProjector, DriverInstanceActor connectivity emission, DriverHostActor
fan-out, OpcUaPublishActor routing, and the wire-level guard
(Condition_event_Quality_tracks_source_connectivity_on_the_wire) — RED-verified
against a simulated pre-fix always-Good server. Existing DriverInstanceActor
parent probes ignore the new ConnectivityChanged.
Docs: docs/AlarmTracking.md §"Condition source-data Quality (#477)";
design doc docs/plans/2026-07-17-alarm-condition-quality-477-design.md.