Joseph Doherty b61f3e0560 fix(galaxy): AVEVA priority 1 is the most urgent: Galaxy alarm Severity follows AVEVA's priority bands, live and history alike (#887)
v2-ci / unit-tests (push) Has been cancelled
GalaxyAlarmPriority, the one table live Galaxy alarms (MxAccessSeverityMapper)
and AVEVA A&E history (EventMapper, #886) map the AVEVA priority through, ranked
a higher number as more severe. AVEVA ranks priority 1 as the most urgent, so a
priority-1 alarm read 250 and a priority-999 system event 1000.

It now uses AVEVA's default priority ranges, most urgent first:

  AVEVA priority  AVEVA severity  bucket    OPC UA Severity
  1-250           1 Critical      Critical  1000
  251-500         2 High          High       750
  501-750         3 Medium        Medium     500
  751-999         4 Low           Low        250
  (history only)  0 not an alarm  -            1

Out-of-range priorities clamp (<= 0 Critical, > 999 Low). Evidence, vd03
Runtime.dbo.Events read-only: priority 1/100 alarms carry AVEVA severity 1,
400/500 severity 2, 600/700 severity 3, and every priority-999 System.* /
User.* row severity 0 with IsAlarm 0.

- Live and history now use the same number. GalaxyDriver passes the table's
  exact value as AlarmEventArgs.OpcUaSeverity. Before, it passed only the bucket,
  which NativeAlarmProjector re-mapped through its generic 200/500/700/900
  ladder, so live and history disagreed even before the direction fix.
- History: a row whose AVEVA severity is 0 (System.Start/Stop/Deploy,
  User.Write...) is not an alarm and reads Severity 1, below every alarm band.
  For alarms AVEVA's 1-4 severity is still never the value: the live feed
  carries only the priority, so it cannot use it, and history must agree.
- Docs: docs/Historian.md gains "Galaxy alarm priority -> Severity
  (lmxopcua#887)"; docs/AlarmTracking.md updated.
- Live re-run of the #801/#886 harness against vd03 HistorianGateway
  ea9f21c (read-only, network-only): 224 of 233 cases identical to the #886
  run, the 9 others differ only in Severity (priority-700 alarm rows 750 ->
  500, 19 system/user events 1000 -> 1). Record: aveva-history-801.md
  "#887 re-run", report aveva-gate-sdk2-887.json.gz.

Client-visible: every OPC UA client that ranks or filters Galaxy alarms by
Severity sees the order reversed (live and HistoryReadEvents). ScadaBridge has
no code that depends on the old values; its own mixed severity directions are
ScadaBridge#129.

Tests updated because they pinned the inverted table:
- Driver.Galaxy.Tests MxAccessSeverityMapperTests (rewritten: edges 1/250/251/
  500/501/750/751/999, 0/-100/int.MinValue/1000/int.MaxValue clamps,
  monotonic-decreasing sweep, equals GalaxyAlarmPriority for -2..1001)
- Driver.Galaxy.Tests GatewayGalaxyAlarmFeedTests (750 and 600 -> Medium)
- Driver.Historian.Gateway.Tests EventMapperTests (band table, priority 999
  -> 250, 1 -> 1000; system events -> 1)
- OpcUaServer.IntegrationTests GalaxyEquipmentEventHistoryWireTests (700 ->
  500, 100 -> 1000, System.Stop -> 1; the fake now stores AVEVA's real 0-4
  severity)

New tests:
- Runtime.Tests NativeAlarmRestatementEndToEndTests
  .Galaxy_live_condition_severity_is_the_AVEVA_priority_band (8 rows: the real
  feed -> real GalaxyDriver -> host -> projector; the same rows EventMapperTests
  pins on the history path)
- EventMapperTests.Aveva_severity_zero_marks_an_event_that_is_not_an_alarm
  (5 rows, incl. the priority-999 alarm positive control)
- GalaxyDriverAlarmSourceTests: OpcUaSeverity passes through

Mutation check, 8 mutants, all killed: the pre-#887 inverted table; the
driver dropping OpcUaSeverity; no not-an-alarm rule; each of the three band
edges off by one; history ignoring priority; a missing AVEVA severity read
as 0.

Claude-Session: https://claude.ai/code/session_01GT67ACmpMR7b9LGRPLijMi
2026-11-12 12:14:49 -05:00
Joseph Doherty 3a312ffdd1 fix(history): a folder's event history reads the Galaxy objects behind its native conditions (#886)
v2-ci / unit-tests (push) Has been cancelled
A notifier folder read one event source, its NodeId identifier (a RawPath or an EquipmentId). AVEVA stores a
Galaxy object's A&E history under the object's tag_name (Source_Object), so AVEVA's own alarm and event
history reached no production folder. Its lower-case property keys were also missed, so every row read
Severity 1 with no ConditionName.

Sources. A folder's event history now reads its own source plus the Galaxy object of every native condition
that fires on it live: those parented under it and those WireAlarmNotifiers wired to it. Live and history use
the same membership. The object comes from the condition's Galaxy alarm reference, its raw tag's attributeRef,
up to the first '.':
- The composer reads it with the driver's own parser (GalaxyAttributeRef, shared with GalaxyDriver), only for
  a GalaxyMxGateway tag with an alarm (RawTagPlan.NativeAlarmReference, part of plan equality).
- The applier binds it after materialising the condition (IOpcUaAddressSpaceSink.BindNativeAlarmHistory,
  forwarded by the deferred sink). A rebuild or the condition's removal forgets it.
Each object is read with the #882 rule: its own events and <Object>.<Attribute> rows, never a prefix sibling.

Fan-out. historiangw's ReadEvents filter is a single predicate, so there is one request per source; the wire
contract is unchanged. EventSourceFanOut merges the reads as one source:
- order is (time, source position, arrival), reversed for a reverse read; ties are never re-sorted by EventId,
  so the boundary skip stays stable;
- duplicates by EventId are dropped and the merge is cut to the cap;
- a truncated source bounds the page at the time it stopped.
Paging, continuation points (bound to the whole source set), the walked-back reverse read and the tie-cluster
over-fetch are unchanged. A folder with one source is read exactly as before.

ACL. Every source is read inside the folder's own HistoryRead, after AuthorizeHistoryRead (#826). A denied
folder reads nothing and fails closed.

Mapping (EventMapper, property names now case-insensitive):
- Severity: an AVEVA row's priority goes through GalaxyAlarmPriority, the table live Galaxy alarms use
  (MxAccessSeverityMapper now delegates to it), so history matches live. Otherwise severity (OtOpcUa's own
  rows, which AVEVA stores lower-cased), clamped. AVEVA's own 1-4 severity is ignored. The table ranks a
  higher priority as more severe, which inverts AVEVA's convention: filed as #887.
- An AVEVA row whose source_conditionvariable names a native condition that fires on the folder takes that
  condition's SourceNode and live ConditionName. Otherwise ConditionName is alarmname or the condition
  variable's attribute.
- alarm_id/alarmid map to AlarmId.

Tests:
- GalaxyEquipmentEventHistoryWireTests (4, real SDK session, production Gateway backend, AVEVA-shaped fake
  gateway): equipment EqA backed by objects Oven_007 + OvenDoor_07. Covers object and attribute events from
  both objects, the prefix sibling excluded, cross-object and in-object ties, forward paging at 1-4 a page,
  reverse whole and paged, SourceNode/ConditionName/Severity, the raw device folder, ACL deny with no backend
  call plus a granted positive control, and a rebuild forgetting the bindings.
- EventSourceFanOutTests (8), EventMapper AVEVA cases (11), GalaxyAttributeRefTests (16), a composer test and
  an applier ordering test.
- Mutation-checked, 17 mutants, all killed. Covered: parent-only membership, no scope, a case-sensitive
  condition match, no condition rewrite, no truncation bound, EventId tie order, no sort, no cap, no stop at
  the bound, unreversed source order, no dedupe, no '.' boundary, priority ignored, case-sensitive keys, no
  applier bind, no deferred forward, and a composer that ignores the driver type. The forget-on-rematerialise
  guard survives as belt-and-braces: the rebuild clear covers it.
- Live, read-only, no WinRM, vd03 HistorianGateway ea9f21c: equipment folder EQ-886-ZipsenLeft (objects
  DevWinPlatform + Left_001). It read 0 events before and 92 now, equal to the unfiltered read's rows for both
  objects. 1/7-event pages and reverse whole/5-event pages agree, and 73 rows resolve to their live condition.
  diff_runs vs the #882 run: 221/226 identical. The 5 that differ are expected: DevWinPlatform Severity
  1 -> 750/1000, and #881 capabilities.

Claude-Session: https://claude.ai/code/session_01GT67ACmpMR7b9LGRPLijMi
2026-11-12 11:45:48 -05:00
Joseph Doherty da948e5fb5 fix(history): a folder's event history includes its object's attribute alarms (#882)
v2-ci / unit-tests (push) Has been cancelled
HistorianGateway answers a per-source ReadEvents (Source_Object = DevWinPlatform) with the
object's own events (SourceName DevWinPlatform) AND its attribute alarms, which it reports as
<Object>.<Attribute> (Source_ProcessVariable, e.g. DevWinPlatform.CPULoadAvg). The Gateway
backend's defensive client-side source filter compared SourceName for equality, so it dropped
the attribute alarms: 70 of the 72 DevWinPlatform events on vd03.

The filter (and the past-the-cap "more events" signal) now uses EventSourceMatch: the source
itself, or <source>.<anything> on the '.' boundary, ordinal. DevWinPlatform never matches
DevWinPlatform2 or DevWinPlatform2.X. This needs no wire change and still makes one request.
Each event keeps its own SourceName. SourceNode stays the condition its stored alarm id names,
which is null for AVEVA rows. The attribute events ride the notifier's own read, so the
per-folder HistoryRead verdict (#826) governs them: a denied folder answers
BadUserAccessDenied before any backend call. The SqlServer and QuestDB backends still match
exactly; they hold only OtOpcUa's own events.

Tests:
- GatewayAttributeEventSourceTests (16): the boundary theory, attribute-in/sibling-out through
  the data source, the drain signal, and an exact attribute-named read.
- AttributeEventHistoryWireTests (2, over a real SDK session with the production Gateway
  backend on an AVEVA-shaped deterministic gateway): object + attribute events with their own
  SourceName, a prefix sibling excluded, paging, and the ACL-on deny with no backend call plus a
  granted positive control.
- Mutation-checked: exact match fails both wire tests; dropping the '.' boundary fails the
  wire sibling check and 6 unit tests.
- Live AVEVA harness re-run against vd03 HistorianGateway ea9f21c (read-only, no WinRM):
  folder DevWinPlatform 2 -> 72 events (whole, 72 1-event pages, reverse); the new #882 check
  passes; 221 of 225 shared cases are identical to the #801 SDK2 baseline, and the 4 that
  differ are exactly the DevWinPlatform event cases. Recorded in aveva-history-801.md.

Follow-up #886: production folders name RawPaths/EquipmentIds, not Galaxy objects, plus the AVEVA
severity/condition property mapping.

Claude-Session: https://claude.ai/code/session_01GT67ACmpMR7b9LGRPLijMi
2026-11-12 10:34:29 -05:00
Joseph Doherty 29665c1872 feat(opcua): HistoryReadEvents projects EventType, ConditionName, SourceNode; honours the where-clause (lmxopcua#746)
HistoryReadEvents projected only EventId / SourceName / Time / ReceiveTime /
Message / Severity: a select clause asking for EventType, ConditionName or
SourceNode (what most generic alarm viewers ask for) got nulls, and the
event filter's where-clause (an OfType) was ignored.

- HistoricalEvent gains optional EventTypeName, ConditionName and AlarmId.
  SqlServer, QuestDB and Gateway event reads fill them from what their
  alarm writers already store (AlarmTypeName / AlarmName / AlarmId; the
  gateway event Type and its AlarmName / AlarmId properties).
- The node manager maps the type name to its Part 9 event type (unknown or
  non-event => AlarmConditionType), projects ConditionName, and resolves
  SourceNode to the materialised condition the alarm id names (the live
  events' SourceNode), else null.
- The where-clause is evaluated per event with the SDK content filter
  through an IFilterTarget (OfType via the type tree; other operators
  against the projected fields), after the page's cursor is taken, so
  paging is unchanged.

Tested in the node manager, over a real client session (the Client.CLI has
no `historyread --events` mode yet; filed as a follow-up), and by alarm
writer -> event read round trips on SqlServer and QuestDB.

Rebased from the unpushed remed/lane-H2 branch (originally authored 2026-10-22
in session_01Ub9hGmYLQvn9XETzw7CMsT) onto current master.

Claude-Session: https://claude.ai/code/session_01GT67AEHd2Acv1YPwGfXEoV
2026-11-09 15:40:47 -05:00
Joseph Doherty 826312befe docs: fill missing XML docs and strip tracking IDs from src comments
Clears CommentChecker findings in src/ (3,280 -> 209, the remainder being false
positives like PLC-5/IEEE-754/M0.0) by adding missing summaries/params/returns,
normalising inheritdoc usage, and removing Gitea/review tracking IDs while keeping
the rationale they annotated. Comment-only: comment-stripped sources are identical
to the parent commit.
2026-10-15 06:14:58 -04:00
Joseph Doherty 109163621c fix(historian): preserve stable alarm delivery identities
v2-ci / build (pull_request) Successful in 5m52s
v2-ci / unit-tests (pull_request) Failing after 1h23m55s
2026-10-13 07:10:58 -04:00
Joseph Doherty 39552e15b9 fix(historian): #690 Gateway raw/AtTime Bad rows carry no value (a stored NULL was value 0) 2026-10-12 16:08:54 -04:00
Joseph Doherty 44a03bedc0 fix(historian): #685 Gateway native TimeAverage/Total — drop AVEVA's pre-window row, keep Uncertain values
AVEVA answers one extra row for the interval before the window; it was mapped as
a result stamped before StartTime (N+1 values). Rows whose interval lies outside
the requested span (either direction) are now dropped after the drained stream.
An Uncertain (opc 64-191) interval kept no value (opc >= 192 was the only data
test); it now carries its value as UncertainDataSubNormal | Calculated.
Docs: AVEVA's TWA excludes NULL-gap time while the SQL backends bridge it;
end-to-end per-interval values also need historiangw#27.
2026-10-12 15:14:56 -04:00
Joseph Doherty 78f604e0cd feat(historian): Gateway serves the per-sample aggregates from raw reads with the shared Sql.Common evaluator (#681)
Average, Count, Minimum, Maximum, Range, Start, End, Delta and Minimum/MaximumActualTime are evaluated
on the Gateway backend from forward ReadRaw reads with BucketPlan + AggregateEvaluator, so Gateway
matches SqlServer/QuestDB exactly (values, status bits, interval-start stamps, #677 reverse).

- Window read [start - 1 ms, end] so AVEVA's initial-value row never lands in a bucket; a pre-window
  row proves earlier data only with a non-Bad OPC quality (histsdk puts a value on every NULL row).
- Earlier data otherwise from a 2-row [1970, start) probe; later data from a 2-row [end, now+1d]
  look-ahead; both ignore rows stamped at their query start/end.
- No gateway stream is ever abandoned (a client-side cancel makes the gateway evict its shared
  historian session); past ServerHistorian:MaxTimeWeightedRawRows the bounded stream is drained, then
  BadTooManyOperations. The gateway's max_values-ceiling InvalidArgument maps to the same limit; a
  caller cancellation is not a backend fault.
- TimeAverage/Total stay AVEVA-native (no prior-sample read for exact Part 13 bounds), now stamped with
  the interval start (PENDING the live leg: histsdk's tail+43 start_time field is unverified) and
  carrying the Calculated bits.
- Served set: GatewayHistorianDataSource.ServedAggregates (12). Live AVEVA leg open (VPN).
2026-10-12 09:56:54 -04:00
Joseph Doherty 6ea3ba44da feat(historian): advertise only the backend's aggregates under AggregateFunctions (#682)
IHistorianDataSource.SupportedAggregates (default: every HistoryAggregateType)
is the one authority for both ServerCapabilities/AggregateFunctions (i=2997) and
HistoryServerCapabilities/AggregateFunctions (i=11201) and for the up-front
BadAggregateNotSupported in HistoryRead-Processed. Gateway declares
AggregateModeMapper.Served (4), SqlServer/QuestDB AggregateFamilies.Served (17),
Null none. Only the folder references are trimmed; the SDK's calculator
factories stay so live AggregateFilter subscriptions keep working.

Co-Authored-By: Claude <noreply@anthropic.com>
2026-10-12 08:52:47 -04:00
Joseph Doherty fb5ec80fe6 fix(historian): #679 Gateway — Average/Count not supported (no AVEVA equivalent), TimeAverage → TimeWeightedAverage 2026-10-11 15:19:21 -04:00
Joseph Doherty 8c8e243de6 feat(historian): GatewayHistorianProvider; status→DA quality reverse mapping
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
2026-10-09 12:47:09 -04:00
Joseph Doherty 55eac5f68b feat(history): full Part 13 aggregate set; unsupported-by-backend aggregates answer BadAggregateNotSupported (#285)
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
2026-10-08 14:24:25 -04:00
Joseph Doherty 55b12dc217 fix(historian-gateway): map alarm severity numerically; dispose provisioner's gRPC channel
Driver.Historian.Gateway-001 (High): AlarmEventMapper wrote the alarm's
Severity wire property as the .NET enum name (e.g. "High"), but
EventMapper's read side int.TryParse()s that same property and silently
falls back to the minimum severity on any unparseable value - so every
alarm event's severity round-tripped through this module's own mappers
collapsed to 1 (Low), contradicting AlarmHistorianEvent.Severity's own
documented contract ("mapped to Historian's numeric priority"). Now
mapped through a numeric priority mirroring the existing
NativeAlarmProjector.MapSeverity convention (200/500/700/900).

Driver.Historian.Gateway-002 (Low): GatewayTagProvisioner never disposed
its IHistorianGatewayClient, unlike its GatewayHistorianDataSource /
GatewayAlarmHistorianWriter siblings. Now implements IAsyncDisposable so
the DI-owned singleton's gRPC channel closes gracefully at shutdown.

Both TDD: new/corrected tests confirmed RED against the pre-fix code.
2026-08-10 06:53:41 -04:00
Joseph Doherty b95b99ba8e fix(drivers): correct 16 wrong OPC UA status-code constants + guard them by reflection (#497)
Every value verified against Opc.Ua.StatusCodes in the pinned SDK (1.5.378.106) by
reflection, not by copying siblings. All are client-visible: OPC UA clients branch on
status.

The three named in #497:
  - Historian.Gateway SampleMapper "BadNoData"  0x800E0000 -> 0x809B0000
    (0x800E0000 is BadServerHalted)
  - Galaxy "BadTimeout"                         0x800B0000 -> 0x800A0000
    (0x800B0000 is BadServiceUnsupported)
  - TwinCAT BadTypeMismatch                     0x80730000 -> 0x80740000
    (0x80730000 is BadWriteNotSupported)

BadTypeMismatch was wrong in three MORE drivers the issue did not name — FOCAS,
AbLegacy and AbCip carried the same 0x80730000. Every call site is a
FormatException/InvalidCastException conversion failure, so the name was right and
the value was wrong in all four.

Adding the reflection guard then surfaced nine further defects offline tests had
never checked:
  - Galaxy GoodLocalOverride  0x00D80000 -> 0x00960000  (not a UA code at all)
  - Galaxy UncertainLastUsableValue        0x40A40000 -> 0x40900000
  - Galaxy UncertainSensorNotAccurate      0x408D0000 -> 0x40930000
  - Galaxy UncertainEngineeringUnitsExceeded 0x408E0000 -> 0x40940000
  - Galaxy UncertainSubNormal              0x408F0000 -> 0x40950000
  - TwinCAT BadOutOfService   0x80BE0000 -> 0x808D0000 (was BadProtocolVersionUnsupported)
  - TwinCAT BadInvalidState   0x80350000 -> 0x80AF0000 (was BadAttributeIdInvalid)
  - AbCip/AbLegacy GoodMoreData 0x00A70000 -> 0x00A60000 (was GoodCommunicationEvent)
  - Historian.Gateway GatewayQualityMapper Good_LocalOverride 0x00D80000 -> 0x00960000

Galaxy's whole Uncertain block read as though the OPC DA quality byte could be
shifted into the UA substatus position; it cannot — the substatuses are an unrelated
enumeration. GatewayQualityMapper already held the correct table, which is what the
Galaxy values are now reconciled against.

Guard: StatusCodeParityTests (Core.Abstractions.Tests, which already project-
references every driver) reflects over every `const uint` in the deployed
ZB.MOM.WW.OtOpcUa.Driver.*.dll whose name reads as a status code, and asserts it
equals Opc.Ua.StatusCodes.<name>. Discovery is by convention, so a new driver
assembly referenced by that project is covered with no edit here. It went red on all
nine defects above before the fixes and now checks 109 constants green.

Because reflection can only see a NAMED constant, two inline literals were hoisted so
the guard can reach them: Galaxy's BadTimeout/Bad into StatusCodeMap, and
GatewayQualityMapper's 15-entry table into a new HistorianStatusCodes. An inline
`0x800B0000u, // BadTimeout` at a call site is exactly how the Galaxy defect survived.

The drivers stay SDK-free by design; only the test project references Opc.Ua.Core,
as the oracle.

Also corrected: tests that pinned the wrong values (Galaxy StatusCodeMapTests,
SampleMapperTests, GatewayQualityMapperTests — all written from the same bad source),
a mislabelled comment in DriverInstanceActorTests, and stale constants in two design
docs, one of them the unexecuted MTConnect driver design that would have propagated
BadNoData's wrong value into a new driver.

The CLI's SnapshotFormatter value->name table was checked against the SDK and is
correct; no change needed.
2026-07-25 15:34:31 -04:00
Joseph Doherty 9f62310b49 fix(historian): map Boolean historization to Int2, not degenerate Int1 (#441)
v2-ci / build (pull_request) Successful in 3m24s
v2-ci / unit-tests (pull_request) Failing after 8m19s
The historian's Int1 analog-tag creation path is server-degenerate:
EnsureTags(Int1) stores an unusable stub (live-probed on the deployed
2023 R2 historian; root-caused + documented gateway-side in
HistorianGateway #11 / PR #16). HistorianTypeMapper mapped
DriverDataType.Boolean -> HistorianDataType.Int1, so Boolean historized
tags failed auto-provisioning.

Map Boolean -> Int2 instead (store 0/1). Int2 is a proven-creatable
analog type, and the value-write path already sends every value as a
double on WriteLiveValues regardless of tag type, so Boolean 0.0/1.0
round-trips cleanly. Both Float and Int2 are supported, so a
pre-existing Float Boolean tag retypes cleanly on its next deploy.

- HistorianTypeMapper: Boolean => Int2 (+ remarks)
- Unit pins: HistorianTypeMapperTests, GatewayTagProvisionerTests
  (Boolean_definition_carries_explicit_Int2_presence)
- Live gate: EnsureTags_boolean_sandbox_provisions_as_Int2 (was _Int1);
  retype probe reframed Float->Int2 (drops the dead Int1 leg)
- Docs: docs/Historian.md 'Boolean historization maps to Int2', CLAUDE.md,
  archreview STATUS.md (R2-06 live gate -> 6/6)

Resolves #441.
2026-07-14 11:57:27 -04:00
Joseph Doherty 9cad9ed0fc docs(xmldoc): fill missing XML docs + strip tracking-ID comments across src
v2-ci / build (push) Failing after 41s
v2-ci / unit-tests (tests/Core/ZB.MOM.WW.OtOpcUa.Cluster.Tests) (push) Has been skipped
v2-ci / unit-tests (tests/Server/ZB.MOM.WW.OtOpcUa.ControlPlane.Tests) (push) Has been skipped
v2-ci / unit-tests (tests/Server/ZB.MOM.WW.OtOpcUa.OpcUaServer.Tests) (push) Has been skipped
v2-ci / unit-tests (tests/Server/ZB.MOM.WW.OtOpcUa.Runtime.Tests) (push) Has been skipped
v2-ci / unit-tests (tests/Server/ZB.MOM.WW.OtOpcUa.Security.Tests) (push) Has been skipped
v2-ci / integration (tests/Server/ZB.MOM.WW.OtOpcUa.Host.IntegrationTests) (push) Has been skipped
v2-ci / integration (tests/Server/ZB.MOM.WW.OtOpcUa.OpcUaServer.IntegrationTests) (push) Has been skipped
Adds <summary>/<param>/<returns>/<inheritdoc> where missing and removes
project bookkeeping IDs (task/tracking refs) from shipped code comments,
so the docs read cleanly and CommentChecker is quiet except for known
false positives (PLC/protocol terms, event/IEqualityComparer inheritdoc).
Doc/comment-only; no logic changed; solution builds clean.
2026-07-07 12:38:39 -04:00
Joseph Doherty 44644ddc7f fix(historian-gateway): alarm SendEvent must not set wire event Id (live-validated)
v2-ci / build (pull_request) Failing after 45s
v2-ci / unit-tests (tests/Core/ZB.MOM.WW.OtOpcUa.Cluster.Tests) (pull_request) Has been skipped
v2-ci / unit-tests (tests/Server/ZB.MOM.WW.OtOpcUa.ControlPlane.Tests) (pull_request) Has been skipped
v2-ci / unit-tests (tests/Server/ZB.MOM.WW.OtOpcUa.OpcUaServer.Tests) (pull_request) Has been skipped
v2-ci / unit-tests (tests/Server/ZB.MOM.WW.OtOpcUa.Runtime.Tests) (pull_request) Has been skipped
v2-ci / unit-tests (tests/Server/ZB.MOM.WW.OtOpcUa.Security.Tests) (pull_request) Has been skipped
v2-ci / integration (tests/Server/ZB.MOM.WW.OtOpcUa.Host.IntegrationTests) (pull_request) Has been skipped
v2-ci / integration (tests/Server/ZB.MOM.WW.OtOpcUa.OpcUaServer.IntegrationTests) (pull_request) Has been skipped
Live validation against wonder-sql-vd03 caught that the gateway's SendEvent handler
throws when the wire event carries a client-supplied Id — so every alarm send from
OtOpcUa failed (PermanentFail). AlarmEventMapper now leaves HistorianEvent.Id unset
(the historian assigns event identity) and preserves the alarm's id as an 'AlarmId'
property. With this, the live alarm send acks.

Also harden the env-gated live tests against two gateway/historian-side limitations
surfaced during validation (neither an OtOpcUa defect): the write readback uses a
timezone-tolerant window (an explicit-timestamp WriteLiveValues lands offset by the
deployment's local-vs-UTC delta — reproducible via raw grpcurl; OtOpcUa sends correct
UTC), and the alarm ReadEvents readback skips with a clear reason when the historian's
server-gated event reads (C2, won't-fix) return nothing. Read + write-persist +
alarm-send are all live-validated green; the alarm send-ack is split into its own test.

Claude-Session: https://claude.ai/code/session_012SDSQ3AcaXqPcBtDESBRii
2026-06-26 23:48:52 -04:00
Joseph Doherty 0b4b2e4cfd refactor(historian-gateway): retire Wonderware historian projects (gateway is sole backend)
The HistorianGateway driver is now the sole historian read/write+alarm backend, so the
Wonderware sidecar projects are dead code. Removes the 5 Wonderware projects (driver,
.Client, .Client.Contracts, + their 2 test projects) from the solution and tree, and fully
retires the vestigial 'Historian.Wonderware' driver type (UI/probe-only; it had no driver
factory): the Host probe registration, the AdminUI driver-config surface (driver page,
tag-config editor/model/validator entry, address picker/builder, driver-type catalog +
dropdown + edit-router entries), and their tests. Prunes the now-unused Wonderware
connection fields (Host/Port/UseTls/ServerCertThumbprint/SharedSecret) from
AlarmHistorianOptions (keeping Enabled + the SQLite store-and-forward knobs) and refreshes
the stale XML docs that named Wonderware as the production backend.

Claude-Session: https://claude.ai/code/session_012SDSQ3AcaXqPcBtDESBRii
2026-06-26 19:25:21 -04:00
Joseph Doherty a96e85f0e4 feat(historian-gateway): AlarmHistorianEvent->HistorianEvent mapper (SendEvent properties)
Claude-Session: https://claude.ai/code/session_012SDSQ3AcaXqPcBtDESBRii
2026-06-26 16:32:38 -04:00
Joseph Doherty a54c7a9366 feat(historian-gateway): HistorianEvent->HistoricalEvent mapper (+ clamped severity)
Claude-Session: https://claude.ai/code/session_012SDSQ3AcaXqPcBtDESBRii
2026-06-26 16:32:38 -04:00
Joseph Doherty c7296d7458 feat(historian-gateway): sample/aggregate->DataValueSnapshot + quality mapper (Wonderware parity)
Claude-Session: https://claude.ai/code/session_012SDSQ3AcaXqPcBtDESBRii
2026-06-26 16:32:38 -04:00
Joseph Doherty 3226b87818 feat(historian-gateway): DriverDataType->HistorianDataType mapper + write-gap fallbacks (matrix-guarded)
Claude-Session: https://claude.ai/code/session_012SDSQ3AcaXqPcBtDESBRii
2026-06-26 16:32:38 -04:00
Joseph Doherty c822a6b196 feat(historian-gateway): HistoryAggregateType->RetrievalMode mapper (matrix-guarded)
Claude-Session: https://claude.ai/code/session_012SDSQ3AcaXqPcBtDESBRii
2026-06-26 16:32:38 -04:00