Part 9 ConditionType.Quality was never assigned; default(StatusCode)==Good
so every native + scripted condition reported Good unconditionally — a
comms-lost device still showed a healthy, inactive, Good condition (a
wrong-VALUE bug, distinct from the null-value #473/#475). Clients (and HMIs
bucketing on IsGood) could not tell "genuinely inactive" from "lost contact".
Layer 1 — make Quality a real, plumbed field:
- AlarmConditionSnapshot gains OpcUaQuality Quality (default Good).
- MaterialiseAlarmCondition sets it (native BadWaitingForInitialData, scripted Good).
- WriteAlarmCondition projects snapshot.Quality; the delta-gate gains a Quality
member so a quality-bucket change fires a Part 9 event.
Layer 2 — drive native quality from driver connectivity (a comms-lost driver
emits no alarm transitions, and an alarm-bearing raw tag has no value variable,
so quality can't come from either existing channel):
- DriverInstanceActor Tells parent ConnectivityChanged on Connected/Reconnecting.
- DriverHostActor fans it to every native condition the driver owns as
OpcUaPublishActor.AlarmQualityUpdate (Good on connect, Bad on disconnect).
- New dedicated IOpcUaAddressSpaceSink.WriteAlarmQuality sets ONLY Quality and
fires only on a bucket change — never touches Active/Acked/Retain (an active
alarm that loses comms stays active). Not a full-snapshot re-projection, so it
can't clobber severity/message and works for a never-fired condition.
Forwarded through DeferredAddressSpaceSink (F10b trap; auto-verified by the
reflection forwarding guard). Ungated by redundancy role; no /alerts row.
Scripted conditions stay Good; worst-of-input quality deferred to #478 (Layer 3).
Tests: node-level (materialise/project/no-clobber/unknown-node no-op),
NativeAlarmProjector, DriverInstanceActor connectivity emission, DriverHostActor
fan-out, OpcUaPublishActor routing, and the wire-level guard
(Condition_event_Quality_tracks_source_connectivity_on_the_wire) — RED-verified
against a simulated pre-fix always-Good server. Existing DriverInstanceActor
parent probes ignore the new ConnectivityChanged.
Docs: docs/AlarmTracking.md §"Condition source-data Quality (#477)";
design doc docs/plans/2026-07-17-alarm-condition-quality-477-design.md.
H1 (HIGH): write-routing key now (AddressSpaceRealm, bareId), not bare-only.
A raw s=<RawPath> and a UNS s=<Area/Line/Equip/Eff> can collide as bare
strings; the bare-only key let a colliding raw+UNS pair route to the WRONG
driver ref (last-writer-wins). The realm the node manager resolves (RealmOf)
is now threaded through IOpcUaNodeWriteGateway.WriteAsync -> RouteNodeWrite ->
_driverRefByNodeId keyed by (realm, bareId). New regression test:
Colliding_raw_and_uns_bare_ids_route_to_their_own_driver_by_realm.
M1 (MEDIUM): discovered-node injection made coherently DORMANT. HandleDiscoveredNodes
hard-short-circuits (single enforcement point; _discoveredByDriver never
populates so the re-inject tail is inert too), with a clear log pointing at the
/raw browse-commit flow. New pin: Discovered_nodes_are_ignored_dormant_in_v3;
the 16+2 v2 injection scenarios re-pointed to an accurate skip reason
(DiscoveryInjectionDormantV3).
M2 (MEDIUM): realm-qualified dual-node self-correction tests —
Failed_uns_write_reverts_uns_node_and_leaves_raw_node_untouched +
Raw_realm_revert_reverts_raw_node_only (the second fails if the realm is dropped).
L1: removed the = AddressSpaceRealm.Uns defaults from the consequential
node-manager mutation methods (WriteValue/WriteAlarmCondition/MaterialiseAlarmCondition/
EnsureFolder/EnsureVariable/UpdateFolderDisplayName/UpdateTagAttributes/
RaiseNodesAddedModelChange/Remove*/RevertOptimisticWriteIfNeeded) + the
AttributeValueUpdate/AlarmStateUpdate records, so the compiler forces explicit
realm; read-only accessors + internal builders retain their defaults.
L3: fixed the stale VirtualTagHostActor class comment (V3NodeIds.Uns, not the
retired EquipmentNodeIds.Variable).
Also: DeploymentArtifactRawUnsParityTests — Raw/UNS node-set byte-parity
round-trip between AddressSpaceComposer.Compose and DeploymentArtifact.ParseComposition.
Claude-Session: https://claude.ai/code/session_01LVneM3eh1UtJxEisFXgmox
Wave B of Batch 4 — the runtime binding seam for the dual namespace.
Applier (both realms, explicit realm at every sink call site):
- MaterialiseRawSubtree: Raw containers as folders + Raw tags as variables
keyed by RawPath (native-alarm tag → single Part 9 condition at the RawPath),
all in AddressSpaceRealm.Raw; historian tagname = override else RawPath.
- MaterialiseUnsReferences: each UNS reference Variable under its equipment
folder (Uns realm) + an Organizes UNS->Raw edge; inherits writable/array/
historian tagname from the backing raw tag (both NodeIds -> one tagname).
- FeedHistorizedRefs / ProvisionHistorizedTags now source RAW tags (mux ref
stays single, keyed by RawPath); ApplyPureRemove tears down raw tags + UNS
refs in place (raw-container removal falls back to rebuild).
DriverHostActor (dual-NodeId, single-source fan-out):
- _nodeIdByDriverRef value gains a realm (NodeRealmRef); rebuilt from
RawTags UNION UnsReferenceVariables so one (DriverInstanceId, RawPath) fans
to the raw NodeId AND every referencing UNS NodeId with identical
value/quality/timestamp. Write inverse map keyed by the bare id; the
ns-qualified NodeId the write hook passes is normalised (BareNodeId) so a
write to either NodeId resolves the same driver ref (-> RawPath write).
- Native raw alarm condition routing is realm-tagged (Raw); AttributeValueUpdate
+ AlarmStateUpdate carry the realm through to the sink.
Retire EquipmentNodeIds -> V3NodeIds.Uns (applier/VirtualTagHostActor) and
RawPaths.Combine (DiscoveredNodeMapper, discovered nodes are Raw now).
DeploymentArtifact.ParseComposition emits the Raw + UNS subtrees byte-parity
with the composer (reconstruct entities -> AddressSpaceComposer.Compose).
Sink surface: removed the transitional `= AddressSpaceRealm.Uns` defaults from
IOpcUaAddressSpaceSink / ISurgicalAddressSpaceSink / SdkAddressSpaceSink /
DeferredAddressSpaceSink / NullOpcUaAddressSpaceSink — every call site is now
explicit (realm reordered before the trailing optionals on EnsureVariable +
MaterialiseAlarmCondition). Node-manager convenience methods keep their
defaults (they are not the interface impl; Sdk delegates explicitly).
Tests: rewrote DriverHostActorLiveValueTests (fan-out drift, 1:N) +
DriverHostActorWriteRoutingTests (dual-NodeId raw/uns write routing) to the v3
raw+uns model; new AddressSpaceApplierRawUnsTests; migrated the EquipmentTags
provisioning/feed tests to RawTags; swept EquipmentNodeIds test callers.
Claude-Session: https://claude.ai/code/session_01LVneM3eh1UtJxEisFXgmox
Adds <summary>/<param>/<returns>/<inheritdoc> where missing and removes
project bookkeeping IDs (task/tracking refs) from shipped code comments,
so the docs read cleanly and CommentChecker is quiet except for known
false positives (PLC/protocol terms, event/IEqualityComparer inheritdoc).
Doc/comment-only; no logic changed; solution builds clean.
The OPC UA address-space build pipeline was named after a v2-roadmap
milestone number rather than its domain. Rename the family to describe
what it does (build/diff/apply the OPC UA address space):
Phase7Composer -> AddressSpaceComposer
Phase7CompositionResult -> AddressSpaceComposition
Phase7Planner -> AddressSpacePlanner
Phase7Plan -> AddressSpacePlan
Phase7Applier -> AddressSpaceApplier
Phase7ApplyOutcome -> AddressSpaceApplyOutcome
The 9 Phase7*Tests suites follow suit; Phase7ScriptingEntitiesTests ->
ScriptingEntitiesTests (it tests the scripting migration, not the
pipeline). Log-message prefixes move to the new class names.
Pure mechanical rename, no behavioral change. EF migration classes/IDs
(AddPhase7ScriptingTables, ExtendComputeGenerationDiffWithPhase7) are
immutable and left untouched, as are historical design docs.
Build clean; OpcUaServer 261/261, Runtime 272/272, ScriptingEntities
12/12 green.
ParseComposition(blob, nodeId, onInconsistency?) detects a kept equipment whose
UNS line belongs to another cluster (a same-cluster-invariant violation that
would orphan the equipment folder) and reports it via an optional callback,
wired to OpcUaPublishActor's logger. Detection-only; the upstream draft
validator remains the authority. Adds two unit tests.
Add Phase7Applier.MaterialiseEquipmentTags — a sink-based pass (Task-0 decision A) that
ensures each EquipmentTagPlan's Variable (NodeId = FullName) under its existing equipment
folder, nesting any FolderPath as a sub-folder. Wire it into OpcUaPublishActor.HandleRebuild
after the Galaxy pass. Variables start BadWaitingForInitialData; never re-creates equipment
folders (decision #4).
Two ordering/lifecycle gaps surfaced once tag values began streaming:
1. OpcUaPublishActor.HandleRebuild loaded the latest *Sealed* artifact, but the
rebuild fires at apply time — before this deployment seals — so it materialised
the PREVIOUS revision while SubscribeBulk subscribed to the applied one. The two
disagreed (4 variables materialised vs 396 subscribed) and every config needed
two deploys. RebuildAddressSpace now carries the applied DeploymentId and the
rebuild loads that exact artifact.
2. On restart a node recovered its revision from NodeDeploymentState but left the
driver children + address space empty (and an identical-config redeploy no-ops on
the unchanged revision), so a rebuilt node served nothing until a config change.
Bootstrap now calls RestoreApplied: re-spawn drivers, rebuild from the applied
artifact, re-push SubscribeBulk — no re-ack.
Verified live: recreating the driver nodes auto-restores all 396 galaxy mirror
tags across 40 machines with Good live values, no deploy required.
Adds <summary>, <param>, <typeparam>, and <inheritdoc/> tags to public
members surfaced by commentchecker — resolves 5,847 of 5,869 issues
(99.6%) across three /fixdocs passes.
Closes the gap where Tag rows with EquipmentId=NULL + Namespace.Kind=SystemPlatform
(Galaxy hierarchy) existed in ConfigDb but were never surfaced in the OPC UA
address space. Now they materialise as Variable nodes under a folder named for
their FolderPath, browseable through any OPC UA client.
Layers touched:
- IOpcUaAddressSpaceSink: new EnsureVariable(nodeId, parentFolderId, displayName,
dataType) signature on the sink interface, NullSink, DeferredSink, SdkSink.
- OtOpcUaNodeManager.EnsureVariable: creates a BaseDataVariableState parented
under the named folder (or root), initial Value=null +
StatusCode=BadWaitingForInitialData; resolves Tag.DataType strings to the
matching OPC UA built-in NodeId. Idempotent.
- Phase7CompositionResult: new GalaxyTags collection of GalaxyTagPlan records
carrying (TagId, DriverInstanceId, FolderPath, DisplayName, DataType,
MxAccessRef). Constructor overloads keep existing call sites compiling.
- Phase7Composer.Compose: now takes Tag + Namespace inputs, filters for
SystemPlatform-namespace tags with EquipmentId=NULL, emits GalaxyTagPlan
rows with MXAccess ref "FolderPath.Name".
- Phase7Plan: new AddedGalaxyTags / RemovedGalaxyTags / ChangedGalaxyTags
collections + GalaxyTagDelta record; IsEmpty + needsRebuild updated.
- Phase7Planner.Compute: diffs GalaxyTags by TagId via existing DiffById helper.
- DeploymentArtifact.ParseComposition: reads the Tags + Namespaces +
DriverInstances arrays the ConfigComposer already emits, applies the same
SystemPlatform filter, returns the same GalaxyTagPlan list as the composer
so artifact-side and compose-side plans agree.
- Phase7Applier: new MaterialiseGalaxyTags pass that ensures one folder per
distinct FolderPath then one Variable per tag. NodeId for the variable is
"<FolderPath>.<Name>" matching the MXAccess ref so the future Galaxy
SubscribeBulk wiring can address them directly.
- OpcUaPublishActor.RebuildAddressSpace: invokes MaterialiseGalaxyTags after
MaterialiseHierarchy. _lastApplied initialiser updated for the new ctor.
- seed-clusters.sql: pre-existing TestMachine_001.TestAlarm001..003 rows
needed no change — the composer/applier now picks them up automatically.
Verified end-to-end via docker-dev: deploy click → driver-a logs
"Phase7Applier: Galaxy tags materialised (tags=3, folders=1)" → OPC UA Client
CLI browses the three Variable nodes under TestMachine_001 folder. Reads
return BadWaitingForInitialData status (expected — Galaxy driver's
SubscribeBulk wiring to push values into the nodes is the remaining
follow-up).
Phase7Composer now carries UnsAreaProjection + UnsLineProjection lists so
the applier can materialise the full UNS topology in the OPC UA address
space. New IOpcUaAddressSpaceSink.EnsureFolder(folderNodeId, parentNodeId,
displayName) seam (no-op default, recorded in tests, forwarded by
DeferredAddressSpaceSink, implemented by SdkAddressSpaceSink). The SDK-
side OtOpcUaNodeManager gains an EnsureFolder API that creates
FolderState nodes with proper parent linkage; RebuildAddressSpace now
clears folders too so re-applies don't accumulate stale topology.
Phase7Applier.MaterialiseHierarchy walks composition.UnsAreas →
composition.UnsLines → composition.EquipmentNodes, calling EnsureFolder
with the correct parent at each level. Idempotent — calling twice with
the same composition is a no-op. OpcUaPublishActor.HandleRebuild invokes
it after Phase7Applier.Apply so OPC UA clients browsing the server now
see Area/Line/Equipment as proper folders rather than flat tag ids.
DeploymentArtifact.ParseComposition reads UnsAreas + UnsLines from the
JSON snapshot the ControlPlane emits, populating the new fields when
present.
Phase7Composer.Compose now accepts UnsAreas + UnsLines; a 3-arg overload
preserves the old signature for legacy callers + existing tests. The
Phase7CompositionResult convenience ctor likewise keeps the planner
tests working without UNS data.
3 new hierarchy tests (pure unit + boot-verify against a real
OtOpcUaSdkServer); OpcUaServer suite is 48/48 green (was 45, +3),
Runtime 74/74 unchanged.
Closes#85.
OtOpcUaTelemetry (Commons/Observability) centralizes the project's Meter
+ ActivitySource so all instrumentation points emit through a single
named surface. Counters cover the hot paths:
otopcua.deploy.applied (outcome=ack|reject)
otopcua.deploy.apply.duration (s, histogram)
otopcua.driver.lifecycle (event=spawn|spawn_stub|stop|fault)
otopcua.virtualtag.eval (outcome=ok|fail|skip)
otopcua.scriptedalarm.transition (state=activated|acknowledged|cleared)
otopcua.opcua.sink.write (kind=value|alarm|rebuild)
otopcua.redundancy.service_level_change (level=byte)
Plus two ActivitySource spans:
otopcua.deploy.apply wraps DriverHostActor.ApplyAndAck
otopcua.opcua.address_space_rebuild wraps OpcUaPublishActor.HandleRebuild
Instruments are no-op until a listener attaches, so tests + dev hosts
pay nothing for unread telemetry.
Host Program.cs gains AddOtOpcUaObservability() (binds the OtOpcUa Meter
+ ActivitySource to OpenTelemetry, attaches a Prometheus exporter) and
MapOtOpcUaMetrics() (mounts /metrics scrape endpoint). Driver-side
internals + ASP.NET request metrics deliberately stay off — the scrape
payload is scoped to OtOpcUa signals only.
Tests use MeterListener + ActivityListener to verify
VirtualTagActor.eval, OpcUaPublishActor.AttributeValueUpdate, and
RebuildAddressSpace actually emit on the central instruments. Runtime
suite is 72 / 72 green (+3).
Closes#105. Path A (F13b/c/d) complete; next batch options: #85 UNS
folder hierarchy in SDK, or F8b/F9b production engine bindings.
Closes the loop between F10b (SDK NodeManager) and F14 (Phase7Plan +
Phase7Applier). DriverHostActor's successful apply now triggers a
RebuildAddressSpace on the publish actor, which loads the latest
deployment artifact + walks composer → planner → applier through the
sink. The OPC UA address space tracks the deployed composition.
DeploymentArtifact:
- New ParseComposition(blob) → Phase7CompositionResult that decodes
Equipment + DriverInstance + ScriptedAlarm arrays into the
projection records Phase7Planner consumes. Pascal-case property
names mirror ConfigComposer.SnapshotAndFlattenAsync's output.
- Each entity reader is tolerant: missing-id rows are dropped,
natural-key sort matches Phase7Composer's contract.
OpcUaPublishActor:
- New Props params: dbFactory + applier. When wired, RebuildAddressSpace
does:
1. LoadLatestArtifact (most recent Sealed Deployment.ArtifactBlob)
2. ParseComposition → Phase7CompositionResult
3. Phase7Planner.Compute(lastApplied, next) → Phase7Plan
4. Empty plan ⇒ no-op (deploy of unchanged composition is benign)
5. applier.Apply(plan) drives sink.RebuildAddressSpace +
WriteAlarmState for removed nodes
6. lastApplied = next so the next rebuild diffs forward
- Without dbFactory/applier wiring, falls back to raw
sink.RebuildAddressSpace — the dev/Mac path before #108 binds prod.
DriverHostActor:
- New Props param opcUaPublishActor (IActorRef?). After successful
ApplyAndAck (status Applied, ACK sent), tells the publish actor
RebuildAddressSpace with the same correlation id so the audit trail
threads through. Null publish actor ⇒ no trigger (admin-only nodes).
Tests: Runtime 63 -> 69 (+6):
- ParseComposition reads Equipment/Driver/Alarm sorted by natural key
- ParseComposition returns empty for empty blob
- Rebuild with dbFactory + sealed deployment artifact triggers exactly
one sink.Rebuild call (Equipment topology added)
- Rebuild with no artifact is idempotent no-op
- Second rebuild with same composition is empty-plan no-op
- Rebuild without dbFactory falls back to raw sink.Rebuild (legacy path)
All 6 v2 test suites green: 173 tests passing.
Closes#109. Engine-wiring data flow is now end-to-end through:
Deploy → DriverHostActor.ApplyAndAck → driver spawn + ACK +
RebuildAddressSpace → OpcUaPublishActor → Phase7Applier → SDK
NodeManager → subscribed OPC UA clients see the change.
OpcUaPublishActor now routes through pluggable seams instead of just
incrementing a counter:
- IOpcUaAddressSpaceSink (Commons.OpcUa) — WriteValue / WriteAlarmState
/ RebuildAddressSpace. OpcUaQuality enum moved here from the actor's
nested type so producers don't have to reference the actor itself.
- IServiceLevelPublisher — Publish(byte). NullServiceLevelPublisher
retains the last level for inspection.
- The actor subscribes to the redundancy-state DPS topic in PreStart
and maps the local node's NodeRedundancyState to a coarse
ServiceLevel (Primary+leader=240, Primary=200, Secondary=100,
Detached=0). This keeps the local SDK's ServiceLevel node honest
without round-tripping back through the admin-singleton calculator.
- ServiceLevelChanged dedupes identical levels so the SDK doesn't see
redundant writes.
- Sink + publisher exceptions are caught and logged; the actor never
crashes its own dispatcher.
- PropsForTests gets optional sink/publisher/localNode params and
skips the DPS subscribe so unit tests stay on a vanilla TestKit
cluster.
Production binding to a real SDK NodeManager + Variable nodes is the
remaining residual — split as F10b. Task 60 still blocked on F10b.
Tests: Runtime 40 -> 46 (+6):
- AttributeValueUpdate routes to sink
- AlarmStateUpdate routes to sink
- RebuildAddressSpace calls sink.Rebuild
- ServiceLevelChanged dedupes
- RedundancyStateChanged for primary-leader publishes 240
- RedundancyStateChanged for secondary publishes 100
All 6 v2 test suites green: 132 tests passing.