A bad keep-alive now degrades health (LastSuccessfulRead preserved) and,
once per outage, publishes BadNoCommunication (value retained) for every
subscribed ref plus a quality-only annotation on subscribed alarm
conditions. Good keep-alives and data/event notifications advance
LastSuccessfulRead, so an idle-but-alive subscription never looks dead
to the #527 watchdog. A keep-alive that recovers on the same session
re-reads the Bad refs and republishes them Good; a session that does not
come back is recovered by the watchdog's ShutdownAsync + InitializeAsync
+ re-subscribe.
Deletes the SessionReconnectHandler wiring (it retried forever in SDK
1.5.378, cloned subscriptions the driver never re-tracked and kept health
Healthy), OnReconnectComplete, TryRearmReconnect and the reconnect_*
counters (new keepalive_recovered). Teardown of a lost session skips
wire deletes and bounds CloseSession. SDK warnings reach the driver log.
Wire test reworked: restart => Bad, then watchdog-style reinit => Good.
Since #516 a DriverConfig change is stop + respawn, so DriverSpawnPlan.ToApplyDelta
was always empty and the in-place path had no producer. #663 and #664 were both
latent bugs in it. This deletes it:
- host: ApplyChildDelta, _pendingDelta, HandleApplyResult and HandleDeltaApplied
- plan: DriverSpawnPlan.ToApplyDelta
- actor: the ApplyDelta, ApplyResult and DeltaApplied messages, the Connected
reinit handler and the mid-connect AdoptConfigDuringInit
- tests: the actor tests that drove the seam
IDriver.ReinitializeAsync and each driver's implementation and unit tests stay.
Comments and docs that cited AdoptConfigDuringInit as the reason a driver must
release prior state at init now cite the IDriver contract and overlapping
retries, which still apply.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
AdoptConfigDuringInit re-runs InitializeAsync(newConfig) and acks success, but
Calculation and Galaxy ignored the JSON there: Calculation kept its old tag
set, and Galaxy connected on its old endpoint. Calculation now rebuilds its tag
table from a config with a body (sharing AdoptConfig with ReinitializeAsync and
stopping any running timer scheduler first). Galaxy, which cannot hot-swap its
options, refuses a non-equivalent one the way ReinitializeAsync does. The actor
now sends DeltaApplied once the adopted init succeeds, so a dependency
consumer's mux interest is re-registered. Unreachable from deploys since #516.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
A Connected ApplyDelta called ReinitializeAsync and kept the actor's data and
native-alarm handles, though every driver's reinit drops the driver-side
subscriptions behind them (#630). The reconcile only re-subscribes a missing
handle, so the driver went silent until a reconnect. Release both at the
driver before the reinit and re-subscribe both in a finally. Unreachable from
deploys since #516; pinned by a two-case test, each case failing against a
different wrong fix.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
- Reconcile retries of a failing alarm subscribe back off (skip 2^(n-1)-1
ticks, cap 7 => >= every 4 min at the 30 s tick) so a hanging subscribe
cannot hold the mailbox every tick; the stack is logged once per streak.
- The unreachable handler re-attach logs at Warning (it only fires on a
regression).
- OpcUaClient: a failed SubscribeAlarmsAsync detaches its notification
handler and bounds the session cleanup to 5 s under _gate;
OnEventNotification drops events from subscriptions not registered in
_alarmSubscriptions, so a stray that survives cleanup cannot deliver.
- The retry test also covers 3 failures (crosses the backoff); its tick
positive control documents its dependence on the stub's changing health.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
A data re-subscribe (every deploy's bulk SetDesiredSubscriptions push to a
kept driver) dropped the prior data subscription through the full
DetachSubscription, which also unhooked OnAlarmEvent and forgot the alarm
handle. On any deploy that did not respawn the driver, the alarm
subscription kept logging "established" while every event reached nobody
until a reconnect or respawn. The data path now uses DetachDataSubscription;
only a lost connection and PostStop detach both.
The #488 health-poll reconcile only looked at data, so an alarm subscribe
that failed on (re)connect gated the feed for the life of the connection.
ReconcileAlarmSubscription now re-attaches a missing handler and
re-subscribes a stale/missing alarm handle every tick.
OpcUaClient removes a half-built alarm subscription from its session when
SubscribeAlarmsAsync throws, so the new retries cannot accumulate.
Tests: actor-level data-resubscribe + reconcile-retry tests and an
end-to-end NativeAlarmFeedSurvivesDeployTests through DriverHostActor; all
three fail against the unfixed actor.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
The alarm subscribe gated on 'a handle exists', which is correct for an idempotent
re-push and wrong for a deploy that widens/narrows the set. Combined with the
spawn-time desired set, a respawning deploy could latch the PREVIOUS revision's
alarm refs for the life of the connection; sourceNodeIds-filtering drivers
(OpcUaClient/AbCip/Focas) would never deliver the new alarm.
Seen RED: LastSubscribedAlarmRefs stayed [alarmX] after a deploy widening to
[alarmX, alarmY].
The connect path was the one capability call the resilience pipeline never
saw, so a driver that could not connect contributed zero breaker input and
the /hosts resilience panel read 'All targets healthy' against a dead
endpoint. InitializeAsync now routes through the invoker as
DriverCapability.Initialize, keyed on the driver-instance id.
- No pipeline retry: the actor's RetryConnect timer is the retry loop
(parser forces retryCount overrides to 0, same funnel as write-shaped).
- Breaker threshold 2, not the Read-sized 5: the breaker samples 30 s and
the reconnect timer fires every 10 s, so at most three attempts fit one
window — threshold 5 could never open. Pinned by its own test.
- An open breaker fast-fails into the same InitializeFailed path as a real
connect failure; the 15 s break window costs at most one extra tick.
The best-effort teardown ShutdownAsync stays unwrapped.
- Companion fix: DriverCapabilityInvokerFactory.Create now invalidates the
instance's tracker snapshots with its pipelines — a respawn during an
outage discarded the only breaker whose OnClosed could clear the OPEN
flag, stranding a false 'Breaker OPEN' chip forever.
Live gate PASSED on docker-dev (image symbol-verified per container):
rtu-gate against dead 10.100.0.35:5021 opened its Initialize breaker on
both centrals with the red 'BREAKER OPEN' chip on /hosts; a socat
5021→5020 forwarder recovered it (both breakers closed within 1 s, panel
back to 'All targets healthy'); healthy MAIN-modbus recorded zero breaker
events. Full suite 50/50 green. Evidence:
docs/plans/2026-08-07-adminui-followups-and-live-gates.md §7.
A driver builds its RawPath -> definition table at init and tolerates a
per-tag miss: an unmappable TagConfig, an unparseable address, a
capability-matrix rejection. That tolerance is right -- one bad tag must not
take down the other few thousand. What was missing is any statement of the
fact afterwards. A skip is not an error and happens before any read, so the
driver stays Healthy, errors/5 min stays 0, Last error stays empty, and Last
read advances live off the tags that did map. On the wonder Makino in #540
that reading held while focas-z-34184 ignored 20 of its 22 tags.
New optional capability ISkippedTagReporter, backed by a shared
SkippedTagLedger so the reset/commit/cap rules are one implementation rather
than one per driver. The report -- authored count, exact skipped count, and a
capped sample of RawPath + reason -- rides DriverHealthChanged to a new Tags
column on /hosts, over the Phase 5 telemetry stream. No table: a driver-only
node has no ConfigDb to write to, the lesson from #521.
The issue named eight drivers. It is twelve -- every driver in
DriverTypeNames.All has an authored-tag skip path. Calculation (no scriptId),
MTConnect (no readable DataItem id), Galaxy (no attributeRef) and OpcUaClient
(no nodeId) were unlisted, and OpcUaClient's was the quietest of the twelve:
NamespaceMap drops such an entry with a bare `continue` and not even a log
line. SkippedTagReporterFleetTests pins the invariant reflectively over every
IDriver in src/Drivers/, so a thirteenth cannot re-introduce the silence.
Sql drops a tag at TWO points and its report is the union of both: a blob
that does not map, AND an identifier the 8.1 catalog gate rejects against the
live catalog. The second is what schema drift produces -- a renamed column, a
dropped view -- months after a deployment sealed green, and reporting only
the first would have that driver claim "0 skipped" while polling half its
tags, which is worse than reporting nothing because the column would then be
actively reassuring.
Deliberately additive to driver state, never a change of it. Latching
non-Healthy for a config problem would satisfy both halves of the #527
comms-loss conjunction -- 90 s without a successful read AND non-Healthy --
and a driver whose tags were ALL skipped has no successful reads by
construction, so it would reconnect-loop forever against a healthy device.
Three details that are load-bearing rather than incidental:
- The skip digest is part of the publish fingerprint. A skipped tag leaves
every other fingerprint component identical to a clean driver's, so without
it PublishHealthSnapshot's dedup swallows exactly the publish carrying the
signal -- the trap that already bit the rediscovery and host-status
channels. The digest covers the sample, not just the counts: a redeploy
that fixes one tag and breaks another leaves both counts unchanged.
- The count is exact; only the sample is capped, and the tooltip says so when
it is showing fewer than it counted. A truncated list that looked complete
would have an operator fix twenty tags and believe the job done.
- The ledger stages and commits, so an init that throws part-way leaves the
previous report standing. A partial snapshot would read as "we now skip
fewer tags", the opposite of the truth.
The proto field needs no companion presence flag, unlike host_statuses: a
singular message field carries real presence in proto3, and a has_ flag would
collide with protoc's generated HasSkippedTags.
Verified red-first three ways: dropping SkippedTagDigest from the fingerprint
fails the two dedup tests, removing the seam from one driver fails the fleet
guard, and dropping the catalog-gate leg fails the Sql union test. Full
solution builds with zero new warnings against 4e22f024.
DriverInstanceActor.DisconnectObserved had no production sender. The only paths
into Reconnecting were a failed *initial* connect and an operator's Force
Reconnect, so a driver that connected and then lost its device stayed Connected
indefinitely: publishing Bad for every tag, never re-initialising, and NOT
recovering when the device returned. PublishHealthSnapshot read GetHealth() for
reporting only and never acted on a driver reporting itself unhealthy.
Both comms-loss quality paths -- #477's native-condition annotation and #481's
scripted-alarm input fan-out -- hang off ConnectivityChanged, so both were
correctly wired to a signal that never fired.
The Connected health tick now evaluates a watchdog and self-sends
DisconnectObserved when the driver reports a non-Healthy state AND its
LastSuccessfulRead has been frozen for DefaultCommsLossTimeout (90s).
The conjunction is the design, and the issue's own proposal -- "non-Healthy for
N consecutive polls" -- is wrong. Degraded means *connected but some data is
bad*; several drivers write health per tag inside the read loop
(ModbusDriver.ReadAsync), so one unreadable address latches Degraded forever
against a perfectly reachable device, and a state-only watchdog would reconnect
that driver every 90s indefinitely -- worse than the bug. LastSuccessfulRead is
the honest evidence: preserved across Degraded/Faulted writes, advanced by any
success. The state check remains the second conjunct so an idle Healthy driver
with nothing subscribed is not declared dead for not reading.
Verified across all 12 drivers that a sustained failure does reach a non-Healthy
state -- nine poll drivers via Degraded, MQTT via live connection state, Galaxy
via its reconnect supervisor. CalculationDriver reports Healthy while running
and so can never trip, which is correct: it has no transport.
Also: the Reconnecting retry now calls ShutdownAsync before InitializeAsync.
ModbusDriver (_transport) and MqttDriver (_connection) overwrite an
IAsyncDisposable field inside InitializeAsync without disposing the previous
one, so re-initialising without a teardown leaks a socket per attempt -- latent
while only a manual Force Reconnect reached this path, but the watchdog makes it
automatic and unbounded (~360 leaks for an hour-long outage at the 10s retry).
Tests: 8 new in DriverInstanceActorCommsLossWatchdogTests, each absence
assertion carrying a positive control (a proven count of processed health-poll
ticks). Falsified five ways -- dropping either conjunct reds exactly the test
written for it, and removing the teardown, the null baseline, or the watchdog
call each reds its own guard.
Live gate PASSED on docker-dev (Modbus + otopcua-pymodbus-standard), run twice:
- fixture stopped -> watchdog fires at ~108s, "declaring comms lost"
- fan-out observed at Debug: "pushed BadNoCommunication for 2 mux ref(s)"
(#481 Layer 4) and the #477 native-condition annotation on a driver
owning conditions
- fixture restarted -> reconnected in ~8s with NO node restart; both the raw
(ns=2) and UNS (ns=3) NodeIds read Good with fresh timestamps
Claude-Session: https://claude.ai/code/session_015p7wGqy3YpZNCpDzTpGMKo
#519 — a driver's OPC UA status code now reaches a client with its sub-code intact.
DriverInstanceActor projected the driver's uint onto a 3-state Good/Uncertain/Bad enum
and OtOpcUaNodeManager re-expanded Bad to a bare 0x80000000, so BadNoCommunication,
BadTypeMismatch and BadNotSupported were indistinguishable on the wire and every
driver's status constants (incl. the 16 #497 had just corrected) were diagnostic in
logs only. Resolved by option (b): the raw uint rides AttributeValuePublished ->
AttributeValueUpdate -> IOpcUaAddressSpaceSink.WriteValue, OpcUaQuality is deleted, and
severity classification is a helper (OpcUaStatus.IsGood/IsUncertain/IsBad).
The surface was wider than the issue costed (41 files, not "the sink and 3
implementations"): OpcUaQuality had non-driver producers with no uint to carry.
Each got its natural code — BadInternalError for a failed virtual-tag script,
BadNoCommunication for driver comms loss — and ScriptedAlarmHostActor's pair of
mutually-inverse uint<->enum mappers is deleted, having round-tripped a code the
engine already held. AddressSpaceApplier's removal writes deliberately keep the
generic Bad: not losing a code the driver had is this issue; inventing one for the
deploy path is a separate call.
Behaviour change: WriteAlarmQuality fires its Part 9 event on a status-code change
rather than a severity-bucket change. While the annotation was 3-state those were the
same predicate; now a move between two Bad reasons changes what a subscriber reads.
New SDK-free named constants live on Commons.OpcUa.OpcUaStatus, and
StatusCodeParityTests is widened to cover them — that guard is reflection-driven, so
it can only see a named constant, never an inline literal.
#517 — the symptom is real but the issue named the wrong path and its fix was unsafe.
ShutdownAsync cannot race: DriverInstanceActor calls it from PostStop, after the
mailbox drains. (Core/Hosting/DriverHost, the one class with a concurrent GetHealth,
has no production call site.) InitializeAsync can: it runs on a fire-and-forget
Task.Run, and MTConnectDriver writes Healthy then starts loops that can throw into a
catch which disposes the client before writing Faulted.
Moving the write earlier, as suggested, inverts the terminal state — teardown drains
in-flight loops that write health as they unwind, so a late loop could leave Healthy at
rest with every connection closed. The fix is a bracket (conservative before, terminal
after), applied to MTConnect's init-failure path only; shutdown keeps its single
trailing write, and the rule plus the reachability table are documented on
IDriver.ShutdownAsync.
CalculationDriver.GetHealth returned a hard-coded Healthy that consulted nothing —
Healthy before initialize, after shutdown and after dispose. Now derived from _running.
Its test, named Health_is_always_Connected, asserted the defect and is replaced.
Every new guard was falsified by breaking the production code and watching it go red.
The two sub-code tests each assert two different Bad codes, since a single-code
assertion could pass against a hard-coded constant under the old projection.
Pre-existing failures, verified unchanged on a stashed tree and not chased: 4 in
Driver.AbLegacy.IntegrationTests (slc500/micrologix/plc5 fixtures not up) and 3 in
Host.IntegrationTests.
Closes#517Closes#519
Claude-Session: https://claude.ai/code/session_015p7wGqy3YpZNCpDzTpGMKo
`IHostConnectivityProbe` was a dead surface: eleven drivers implement it, `GetHostStatuses()`
had ZERO production call sites, and `OnHostStatusChanged` had no subscriber outside the Galaxy
driver's own aggregator. Per-host connectivity was computed by every driver and read by nobody.
The issue offered "build the publisher or delete it". The publisher as its entity doc described
it — driver nodes upserting `DriverHostStatus` rows — is not buildable: per-cluster mesh Phase 4
gates `AddOtOpcUaConfigDb` on the `admin` role, so a driver-only node has no ConfigDb connection
to write rows with. So the capability is kept and the transport changed.
`DriverHealthChanged.HostStatuses` now carries the probe result to `/hosts` as a Hosts column.
That channel already reached the page, already survives the mesh split via the Phase 5 gRPC
telemetry stream, and already replays a last-value snapshot on re-subscribe — so per-host state
re-primes after a reconnect without a durable store. Both halves of the interface finally do
what they are for: the event triggers a prompt publish, the pull is the source of truth.
The point of the column is the case the driver-level state chip structurally cannot express: a
multi-device driver stays aggregate-Healthy while ONE of its devices is unreachable.
Two traps, both pinned by tests that were falsified against the prod code:
- The host digest MUST be in the publish fingerprint. On a single-host-down transition every
other fingerprint component is unchanged, so the dedup would swallow exactly the publish
carrying the news — the trap that already bit the rediscovery signal. Removing it turns the
guard test red, verified.
- null (no probe) must stay distinct from empty (probe with no hosts). proto3 cannot tell an
absent repeated field from an empty one, hence the explicit `has_host_statuses` flag;
collapsing them would render every probe-less driver as one whose devices are all fine.
Dropped: the DriverHostStatus entity, enum, DbSet, model config and table (migration
DropDriverHostStatusTable — empty on every deployment, so the scaffolder's data-loss warning is
moot, and Down() recreates it exactly).
Found en route, NOT fixed here: `DriverInstanceResilienceStatus` is the identical defect — no
writer, no reader, only a DbSet declaration, while the live data rides the
`driver-resilience-status` telemetry channel. Its doc-comment now states that rather than
describing the sampler and AdminUI join that were never built. Filed as #524 rather than widening
this schema change beyond what was asked.
Claude-Session: https://claude.ai/code/session_015p7wGqy3YpZNCpDzTpGMKo
Removes the tag-set drift detector shipped in e77c8a35. The design was sound
-- the tautology drivers were correctly gated out, and the structurally
undetectable "vanished" direction was declared rather than faked -- but none of
that is the objection. The feature browsed real plant equipment on a recurring
timer, at a frequency no operator could configure (the interval was a
constructor parameter with no appsettings key), and that outbound traffic was
never once observed against a real PLC, CNC or MTConnect Agent.
Removed: TagSetDrift/TagSetDriftDetector; DriverInstanceActor's drift timer,
tick message, Props/ctor parameter, gate, handler and leaf-collector;
ITagDiscovery.AuthoredDiscoveryRefs + .DiscoveryStreamIncludesAuthoredTags and
their four implementations; 14 tests.
Kept: ITagDiscovery.SupportsOnlineDiscovery (it predates this and drives the
universal browse picker), and the whole IRediscoverable consumption from
09a401b8 -- the driver tells us, we do not poll.
CONSEQUENCE, deliberately accepted: AbCip and FOCAS browse a live backend but
implement no IRediscoverable, so they now have NO tag-change signal at all -- a
PLC re-download is invisible until someone re-browses by hand. Recorded in
CLAUDE.md so the next reader does not have to rediscover it, along with the
shape to reach for if that coverage is wanted back (event-driven, or triggered
by a reconnect/deploy, not a wall-clock timer).
Runtime.Tests 476 pass / 13 skipped (skip set unchanged); FOCAS 275, TwinCAT
192, MTConnect 491, AbCip 342, Core.Abstractions 266 all green.
Claude-Session: https://claude.ai/code/session_015p7wGqy3YpZNCpDzTpGMKo
The second thing #516/§8.2 deliberately did not build. The original objection
stands — Modbus, S7, MQTT, AbLegacy and Sql echo authored config from
DiscoverAsync, so diffing discovered against authored is a tautology for them
— but it is now ENCODED rather than used as a reason not to build.
The discriminator already existed: ITagDiscovery.SupportsOnlineDiscovery is
documented as "enumerates the tag set from the live backend rather than
replaying pre-declared/authored tags", and it separates the fleet cleanly —
FOCAS, TwinCAT, MTConnect and AbCip true; the five config-echo drivers
explicitly false. The check runs only for a driver that is
SupportsOnlineDiscovery AND reports the new AuthoredDiscoveryRefs. That is
nullable rather than empty-by-default on purpose: an empty collection
legitimately means "nothing authored, everything discovered is new", so
conflating the two would report total drift for a driver that never opted in.
Where the value is: AbCip and FOCAS browse a live backend but implement no
IRediscoverable, so before this they had no change signal at all. A periodic
compare is the only way to notice a PLC re-download.
A finding that changed the design: FOCAS, TwinCAT and AbCip all re-emit their
authored tags into the same DiscoverAsync stream as device-derived ones, so
the browse picker can show an operator their existing tags. Discovered is
therefore always a superset of authored, and a VANISHED tag can never appear
missing — one whole direction is structurally undetectable for three of the
four. Shipping a Vanished list that is permanently empty for them would have
been the half-inert seam this whole exercise removes. So the driver declares
DiscoveryStreamIncludesAuthoredTags, the detector does not compute the
undetectable half, and the operator message says "missing-tag detection
unavailable for this driver" rather than letting the absence of a missing-tag
clause read as reassurance. MTConnect is the only driver where both directions
work — its stream is purely probe-model-derived.
Behaviour: a failed browse is not drift (an unreachable device would otherwise
report every authored tag as vanished); a truncated capture is skipped for the
same reason; an unchanged drift is reported once rather than re-stamping its
timestamp; drift that resolves clears the prompt. Interval defaults to 5
minutes — it browses a real device, and a tag set changing is an engineering
event, not a runtime one. It reuses the Stage-2 surfacing, raising the same
/hosts re-browse prompt, and never rebuilds the served address space.
Comparison logic is a pure, separately-tested type rather than actor-inline.
14 new tests. The gate was verified load-bearing by deleting the
SupportsOnlineDiscovery half: the tautology-driver test goes red, and it
asserts discovery was never invoked rather than merely "no prompt raised",
which would have passed for the wrong reason if the timer never fired.
Full suite green except the same three pre-existing fixture-gated integration
suites, identical counts.
#507 was filed as "injection inert in v3, re-migrate onto the raw subtree".
Reading it, the retained code is not revivable: it resolves equipment from
EquipmentNode.DriverInstanceId UNION EquipmentTags, and BOTH are structurally
empty in v3 (AddressSpaceComposer always constructs EquipmentNode with a null
DriverInstanceId; DeploymentArtifact hard-codes an empty EquipmentTags set).
Removing the guard would have changed a log line and injected nothing. So it
is deleted rather than fixed, and #507 closes as superseded by /raw
browse-commit.
Removed: HandleDiscoveredNodes, PartitionDiscoveredByDeviceHost,
ShouldWarnPartition, PlansRoutingEqual, ApplyDiscoveredPlansForDriver,
_discoveredByDriver, the redeploy re-inject tail, DiscoveredNodeMapper,
DiscoveredInjection, AddressSpaceApplier.MaterialiseDiscoveredNodes,
OpcUaPublishActor.MaterialiseDiscoveredNodes, and the Runtime-local copies of
CapturingAddressSpaceBuilder/DiscoveredNode.
The connect-time discovery loop goes too (StartDiscovery, RediscoverTick,
HandleRediscoverAsync, DiscoveredNodesReady, TriggerRediscovery). With
injection gone it had no consumer, and leaving it would either dead-letter or
keep browsing real devices up to ~15x per connect to drop the result.
ITagDiscovery itself stays — the /raw browse picker drives it through
Commons/Browsing/DiscoveryDriverBrowser, which never went through the actor,
so the picker is unaffected.
deferment.md §4.4 called the 18 DiscoveryInjectionDormantV3 tests "Real —
blocked on #507". They are not: they assert an equipment-rooted graft
(EquipmentRootNodeId == "EQ-1") that v3 cannot produce, so they could never
have unskipped as written. Deleted along with DiscoveredNodeMapperTests, the
CapturingAddressSpaceBuilder tests, and the MaterialiseDiscoveredNodes tests
in AddressSpaceApplierTests/OpcUaPublishActorTests. Runtime.Tests skipped:
31 -> 13.
IHostConnectivityProbe is deliberately NOT resolved here. GetHostStatuses()
has no production call site and nothing writes a DriverHostStatus row, but the
table was re-created in the v3 initial migration, so deleting on inference
would be wrong. Split to Gitea #521 with both options costed.
CLAUDE.md, docs/drivers/{Galaxy,TwinCAT,MTConnect}.md updated — they described
the seam as dead.
Build clean; Runtime.Tests 476 passed / 13 skipped; OpcUaServer.Tests 362
passed / 4 skipped.
Nine drivers raise IRediscoverable.OnRediscoveryNeeded when they observe that
a remote's tag set may have changed — a Galaxy redeploy, a TwinCAT
symbol-version bump, an MTConnect agent restart, a Sparkplug rebirth. Nothing
in src/ subscribed, so every raise went into the void. Drivers even wrap the
invoke in try/catch for "subscriber threw"; there has never been a subscriber.
DriverInstanceActor now attaches the event in PreStart and detaches in
PostStop, mirroring AttachAlarmSource/DetachAlarmSource. Attach is per-actor,
not per-connect: the raise has no connection affinity and can land while the
driver is between connects. The detach is load-bearing rather than tidy — the
IDriver instance outlives the actor when the host respawns a child around the
same driver object, so a missing -= accumulates one handler per respawn, each
holding a dead Self.
The signal rides the existing driver-health snapshot to /hosts as a
"re-browse" chip. It is ADVISORY: the served address space is deliberately not
rebuilt, because v3 authors raw tags explicitly through the /raw
browse-commit flow and a runtime graft would materialise nodes no operator
approved and no deployment artifact records.
Two things worth knowing:
- PublishHealthSnapshot dedups on a health fingerprint, and a rediscovery
raise on an otherwise-healthy driver changes none of the four fields it
hashed. Without adding the timestamp to that tuple the dedup swallows the
exact publish carrying the signal. Reverting that one line turns 3 of the 5
new tests red, which is how it was confirmed rather than assumed.
- The new test stub implements IDriver from scratch instead of deriving from
the shared StubDriver, whose GetHealth() returns DateTime.UtcNow — its
fingerprint differs on every call, so the dedup never engages and the dedup
test would have passed vacuously either way.
The planned discovery-result drift detector was NOT built. Modbus, S7, MQTT,
AbLegacy and Sql all echo authored config from DiscoverAsync rather than
browsing the device, so a discovered-vs-authored diff is permanently empty for
them — it would have been another plausible-looking inert seam, which is the
class this audit exists to remove. IRediscoverable is the trustworthy signal
because the driver asserts it deliberately.
DriverHealthChanged, IDriverHealthPublisher.Publish and HostsDriverRow gain
defaulted optional parameters, so no existing call site changed. telemetry.proto
gains fields 8/9 and both Phase-5 mappers carry them.
Runtime.Tests 512 passed / 31 skipped.
Option A from the issue — the cheap consistency check, no interface change.
The desired ref set was re-applied on a Connected TRANSITION (`ResubscribeDesired`)
and on a deploy's `SetDesiredSubscriptions`, and nowhere else. A subscription lost
while the driver STAYED Connected — a subscribe that failed and was never retried,
a handle dropped down an error path — left the actor subscribed to nothing while
still reporting Healthy, indefinitely.
`ReconcileSubscription` now rides the existing 30 s `health-poll` tick: while
Connected, a driver holding a desired set but no live handle is re-subscribed.
Gated on `ISubscribable`. A driver that cannot subscribe at all can still be handed
a desired set, and without the guard it would be told `Subscribe` every tick and
fail every tick, forever.
This is a state-machine consistency check, NOT a probe — it can only see that this
actor holds no handle, never that a handle is present but dead server-side, because
`ISubscriptionHandle` is opaque. That is option B, and it stays deferred until a
real occurrence shows the handle outliving the subscription; it would need a
liveness member implemented across all eight drivers with different subscription
mechanics.
A redundant `Subscribe` is possible (a tick queued ahead of an already-queued one
observes the same no-handle state) and is harmless: `HandleSubscribeAsync` is a
`ReceiveAsync`, so no tick is processed mid-subscribe, and it drops any prior
subscription before establishing the new one. Suppressing it would need a
pending-subscribe flag threaded through every self-tell site — more state than the
race is worth.
`healthPollInterval` becomes an optional Props parameter, mirroring the existing
`rediscoverInterval` seam, so a test can drive the reconcile without waiting 30 s.
Three tests. The reconcile itself is proven by a stub whose FIRST subscribe throws:
nothing else would ever retry it, so a second attempt can only come from the
reconcile — disabling `ReconcileSubscription` turns it red. The two guard tests are
absence assertions and are bounded by a positive control rather than a sleep: a
counting health publisher makes ticks PROCESSED observable, so "still one subscribe"
means the reconcile ran and declined, not that the timer had not fired.
Explicitly not deploy-time drift (#486) — re-asserting an already-correct desired
set would not have helped there.
Part 9 ConditionType.Quality was never assigned; default(StatusCode)==Good
so every native + scripted condition reported Good unconditionally — a
comms-lost device still showed a healthy, inactive, Good condition (a
wrong-VALUE bug, distinct from the null-value #473/#475). Clients (and HMIs
bucketing on IsGood) could not tell "genuinely inactive" from "lost contact".
Layer 1 — make Quality a real, plumbed field:
- AlarmConditionSnapshot gains OpcUaQuality Quality (default Good).
- MaterialiseAlarmCondition sets it (native BadWaitingForInitialData, scripted Good).
- WriteAlarmCondition projects snapshot.Quality; the delta-gate gains a Quality
member so a quality-bucket change fires a Part 9 event.
Layer 2 — drive native quality from driver connectivity (a comms-lost driver
emits no alarm transitions, and an alarm-bearing raw tag has no value variable,
so quality can't come from either existing channel):
- DriverInstanceActor Tells parent ConnectivityChanged on Connected/Reconnecting.
- DriverHostActor fans it to every native condition the driver owns as
OpcUaPublishActor.AlarmQualityUpdate (Good on connect, Bad on disconnect).
- New dedicated IOpcUaAddressSpaceSink.WriteAlarmQuality sets ONLY Quality and
fires only on a bucket change — never touches Active/Acked/Retain (an active
alarm that loses comms stays active). Not a full-snapshot re-projection, so it
can't clobber severity/message and works for a never-fired condition.
Forwarded through DeferredAddressSpaceSink (F10b trap; auto-verified by the
reflection forwarding guard). Ungated by redundancy role; no /alerts row.
Scripted conditions stay Good; worst-of-input quality deferred to #478 (Layer 3).
Tests: node-level (materialise/project/no-clobber/unknown-node no-op),
NativeAlarmProjector, DriverInstanceActor connectivity emission, DriverHostActor
fan-out, OpcUaPublishActor routing, and the wire-level guard
(Condition_event_Quality_tracks_source_connectivity_on_the_wire) — RED-verified
against a simulated pre-fix always-Good server. Existing DriverInstanceActor
parent probes ignore the new ConnectivityChanged.
Docs: docs/AlarmTracking.md §"Condition source-data Quality (#477)";
design doc docs/plans/2026-07-17-alarm-condition-quality-477-design.md.
A calc-tag add/remove/edit or a script edit changes the merged DriverConfig,
which DriverSpawnPlanner routes to an in-place ApplyDelta (not a respawn), i.e.
CalculationDriver.ReinitializeAsync. The old ReinitializeAsync ignored the new
config: the tag table + dependency-ref set were built once at construction and
never rebuilt, so after a redeploy added tags never computed, removed tags kept
publishing, and edited scripts served stale results (deploy reported success).
Part 1 (HIGH): extract RebuildTagTable(config) — shared by the ctor and reinit
so they cannot drift — and have ReinitializeAsync re-bind the new config
(ParseOptions) and rebuild _tagsByRawPath/_changeDependents/_dependencyRefs/
_stateByRawPath under _lock, preserving last-known state for surviving tags,
dropping removed tags, and starting new tags fresh. _dependencyRefs now reflects
the new authored tags. Corrected the now-false ReinitializeAsync comment.
Part 2 (MEDIUM ordering hazard): the host's ReRegister was Tell-ed synchronously
alongside the ApplyDelta Tell, so the adapter re-read DependencyRefs before the
async ReinitializeAsync rebuilt them (stale set, no self-correction). Now
DriverInstanceActor sends DeltaApplied(driverInstanceId) to DriverHostActor
AFTER ReinitializeAsync completes, and HandleDeltaApplied re-registers only that
driver's adapter — sequenced after the rebuild. Removed the inline loop.
Test: added a redeploy test to CalculationDependencyFlowTests exercising the
real DependencyMuxActor + adapter + driver — a new tag reading a NEW dep flows +
computes, a removed tag stops publishing, an edited script serves the new
result, and DependencyRefs re-registers the new set. Fails on pre-fix code
(DependencyRefs stays stale ["src/a"]), passes after the fix.
Claude-Session: https://claude.ai/code/session_01LVneM3eh1UtJxEisFXgmox
Remediates RESILIENCE-DISPATCH-GAP (surfaced by the 07/C-1 analyzer): the Phase 6.1
CapabilityInvoker resilience pipeline (retry / breaker / bulkhead / telemetry) was
constructed only in tests — the production dispatch layer called driver-capability
methods directly, bypassing it entirely.
The filed plan (thread CapabilityInvoker directly into DriverInstanceActor) is
INFEASIBLE: Runtime is deliberately Polly-free (references Core.Abstractions, not
Core — the same boundary IDriverFactory documents). So this introduces a seam,
mirroring IDriverFactory exactly:
- Core.Abstractions: IDriverCapabilityInvoker (+ NullDriverCapabilityInvoker
pass-through) and IDriverCapabilityInvokerFactory (+ null factory).
- Core: CapabilityInvoker now implements the interface; new
DriverCapabilityInvokerFactory builds a per-instance invoker over the
process-singleton pipeline builder + status tracker + tier resolver.
- Runtime: DriverInstanceActor takes an IDriverCapabilityInvoker (default =
pass-through) and routes all 6 dispatch sites (write, alarm-ack, subscribe,
unsubscribe, alarm-subscribe, discover) through it; per-host key resolved via
IPerCallHostResolver for single-ref calls, driver-instance key for bulk calls.
DriverHostActor builds + injects the real invoker per spawned driver.
- Host: DriverFactoryBootstrap registers the tracker, pipeline builder, and
concrete factory (needs DriverFactoryRegistry.GetTier). Runtime SCE resolves the
factory from DI like IDriverFactory; pass-through on nodes without it bound.
- Analyzer: IDriverCapabilityInvoker.ExecuteAsync/ExecuteWriteAsync are now
recognized wrapper homes (interface-typed invoker calls must suppress OTOPCUA0001
too). All 6 RESILIENCE-DISPATCH-GAP pragmas removed — the analyzer (an error in
Runtime) is now the standing regression guard.
Also adds retry / breaker-open / breaker-close LOGGING to the pipeline builder —
the operator-facing observability surface (the Admin /hosts reader, Phase 6.1
Stream E.2/E.3, was never built, so the pipeline otherwise runs silently).
Scope notes:
- Tier-DEFAULT policy only: DriverInstanceSpec (the deploy artifact) does not carry
the per-instance ResilienceConfig JSON, so overrides aren't applied yet (tracked
follow-up: plumb ResilienceConfig through the composer/artifact).
- GenericDriverNodeManager's call is NOT wired: that class is test-only scaffolding
(zero production references — the Server has its own address-space path); its
pragma is re-annotated accordingly, not left as a "tracked gap".
Verification (unit + analyzer; live behavioral gate still pending — see FOLLOWUP-10):
- Negative control: unwrapping any site fails the Runtime build with OTOPCUA0001.
- New Runtime guard (recording invoker): write routes via ExecuteWriteAsync with the
IPerCallHostResolver host; subscribe via ExecuteAsync — proves runtime routing.
- New analyzer test: the interface is a valid wrapper home.
- New pipeline-builder test: retry events are logged.
- Full solution builds clean (0 errors); Runtime.Tests 357, Core.Tests 238,
Analyzers.Tests 32 all green; pass-through default keeps existing dispatch tests
byte-for-byte unchanged.
Inject the custom UnwrappedCapabilityCallAnalyzer as an OutputItemType=Analyzer
ProjectReference from Directory.Build.props (excluding the analyzer + its test
project) so OTOPCUA0001 runs on every src/ and tests/ compilation — it previously
enforced its CapabilityInvoker-wrapping rule against nothing but its own 31 unit
tests (the 'built-but-never-wired' failure mode).
Triage of the ~280 surfaced hits, three categories:
1. RESILIENCE-DISPATCH-GAP (7 sites, DriverInstanceActor x6 + GenericDriverNodeManager
x1): a REAL, previously-untracked gap the analyzer caught on first wiring — the
Phase 6.1 CapabilityInvoker resilience pipeline (retry/breaker/bulkhead/telemetry)
is constructed ONLY in tests and was never wired into the production dispatch
layer. Scoped per-site #pragma with a greppable RESILIENCE-DISPATCH-GAP marker
explicitly noting these are tracked-but-not-intentional, pending the dispatch-wiring
remediation (filed as a follow-up). Keeps the analyzer live everywhere else in
those projects so a NEW unwrapped call still fails the build.
2. Driver-INTERNAL self-calls (3 sites, AbCipAlarmProjection x2 + S7Driver x1):
a driver's own poll/ack path calling its own capability method. The invoker wraps
the driver from the dispatch layer OUTWARD; a driver re-wrapping its own internal
calls would double-wrap. Genuinely intentional — scoped #pragma with that rationale.
3. Wire-level test suites + manual-testing CLIs (12 projects): invoke drivers directly
by design — the analyzer's own documented intentional case. Project-level NoWarn
with a comment.
Verified: full solution build green, 0 OTOPCUA0001 hits; analyzer's 31 tests pass;
negative control — dropping one dispatch-gap pragma re-fires OTOPCUA0001 and fails
the Runtime build, proving the analyzer is genuinely live tree-wide, not disabled.
Adds <summary>/<param>/<returns>/<inheritdoc> where missing and removes
project bookkeeping IDs (task/tracking refs) from shipped code comments,
so the docs read cleanly and CommentChecker is quiet except for known
false positives (PLC/protocol terms, event/IEqualityComparer inheritdoc).
Doc/comment-only; no logic changed; solution builds clean.
The HistorianGateway driver is now the sole historian read/write+alarm backend, so the
Wonderware sidecar projects are dead code. Removes the 5 Wonderware projects (driver,
.Client, .Client.Contracts, + their 2 test projects) from the solution and tree, and fully
retires the vestigial 'Historian.Wonderware' driver type (UI/probe-only; it had no driver
factory): the Host probe registration, the AdminUI driver-config surface (driver page,
tag-config editor/model/validator entry, address picker/builder, driver-type catalog +
dropdown + edit-router entries), and their tests. Prunes the now-unused Wonderware
connection fields (Host/Port/UseTls/ServerCertThumbprint/SharedSecret) from
AlarmHistorianOptions (keeping Enabled + the SQLite store-and-forward knobs) and refreshes
the stale XML docs that named Wonderware as the production backend.
Claude-Session: https://claude.ai/code/session_012SDSQ3AcaXqPcBtDESBRii
GalaxyDriver's StreamAlarms feed is session-less and survives an in-place
reconnect, so DriverInstanceActor re-subscribed on every Connected re-entry
(after dropping its own cached handle without an Unsubscribe — sync teardown).
The re-subscribe was additive: _alarmSubscriptions.Add grew the list by one
untracked handle per reconnect cycle — a slow unbounded leak. Functionally
harmless (the gate is Count>0 and OnAlarmFeedTransition only reads [0], firing
once regardless), but it accumulated forever.
Fix: SubscribeAlarmsAsync clears the set before adding, collapsing to a single
live handle (under the existing _alarmHandlersLock, atomic w.r.t. the fan-out
reader). There is exactly one consumer per driver instance (factory-per-actor
lifecycle), so replacing the set with the latest handle is faithful. Chosen
over making the actor's sync DetachAlarmSource call UnsubscribeAlarmsAsync
async/fire-and-forget — disproportionate for a minor leak.
Regression test Re_subscribe_collapses_to_a_single_handle_no_accumulation
(TDD-verified: FAILS without the Clear — releasing the latest handle leaves
the feed open because stale handles remain; PASSES with the fix). Galaxy tests
263 pass / 3 skip; Runtime native-alarm 24 pass. Code-reviewed (approved).
- Correct the misleading DetachAlarmSource comment: a session-less feed (Galaxy) is NOT
torn down on an in-place reconnect, so re-subscribe is additive (harmless; gate reads [0]).
- Add trace-only SubscribeAlarms drop handlers in Connecting/Reconnecting (symmetry with
NativeAlarmRaised) so a self-tell overtaken by a queued disconnect doesn't dead-letter.
- Document the deliberate no-unsubscribe-on-empty asymmetry vs the value path.
Behavior-neutral for the un-gate path. Minor handle-accumulation leak tracked as follow-up.
Phase B native alarms never fired end-to-end: GalaxyDriver suppresses OnAlarmEvent until
an alarm subscription exists (_alarmSubscriptions.Count > 0), but the runtime only attached
the OnAlarmEvent handler and never called SubscribeAlarmsAsync — so the central feed stayed
gated and no transition reached the Part 9 condition / /alerts. Unit tests passed because
they inject through the IAlarmSource seam directly; the deferred live /run surfaced it.
DriverHostActor computes per-driver alarm refs (alarm-bearing tags' FullNames) and hands them
via SetDesiredSubscriptions; DriverInstanceActor calls SubscribeAlarmsAsync for IAlarmSource
drivers on Connected entry and whenever alarm refs are pushed while Connected (the deploy path),
idempotent via a cached handle reset on detach so reconnect re-subscribes.
A DriverInstanceActor stuck Reconnecting/Connecting now adopts a config delivered via ApplyDelta and
re-initialises with it, instead of dead-lettering and retrying the stale config forever. A monotonic
init generation supersedes the in-flight init so the corrected config always wins.