Both bugs surfaced only on split-role deployments (the MAIN cluster's
admin-only nodes), where the AdminUI runs without the driver role.
- Test Connect returned "No probe registered" for every driver: the
IDriverProbe set was registered only under the driver role, but the
admin-operations singleton that consumes it is pinned to admin. Extract
AddOtOpcUaDriverProbes() (idempotent via TryAddEnumerable) and call it
in the hasAdmin path too.
- Live driver-status/alerts/script-log panels showed "SignalR error:
Connection refused": these Blazor Server components opened a HubConnection
to their own hub via the browser's public URL, which server-side code
can't reach behind Traefik (host :9200 -> container :9000). Read the
in-process source directly instead -- DriverStatus via
IDriverStatusSnapshotStore.SnapshotChanged, Alerts/ScriptLog via a new
IInProcessBroadcaster<T>. Fleet status was unaffected (reads DB/ActorSystem).
Adds unit tests for probe registration, the snapshot-store event, and the
broadcaster.
GalaxyDriverPage deserialized DriverConfig with case-sensitive camelCase opts, but the
persisted/seeded config is PascalCase (the runtime reads it case-insensitively). So all four
nested option records read as null -> FromRecord NRE (HTTP 500) on edit, and the form would
have shown defaults instead of the real config (risking a clobber on save). Fix: add
PropertyNameCaseInsensitive=true (matches the runtime) so real values load, plus null-coalesce
the nested records in FromRecord as defense-in-depth. Regression test asserts the seeded
PascalCase config loads its real values.
Completes the test side of the in-progress Galaxy-tag workstream:
- Phase7ApplierTests / Phase7ApplierHierarchyTests: supply the now-required
Galaxy-tag args to Phase7Plan / Phase7CompositionResult.
- Add genuine coverage for Phase7Applier.MaterialiseGalaxyTags (folder-per-distinct-path,
variable-per-tag node-id derivation, folder dedupe) + added-Galaxy-tags-trigger-rebuild.
- S7.Cli.Tests: use the project's S7CpuType (CLI option type) instead of S7.Net.CpuType.
Whole solution now builds 0/0; OpcUaServer.Tests 52, S7.Cli.Tests 36 green.
Resolves the 12 reported build errors (7 CS0535 sink fakes + 5 CLI CS1587).
Runtime.Tests green (74). NOTE: OpcUaServer.Tests still has pre-existing CS7036
errors from the in-progress Galaxy-tag workstream (Phase7Plan/Phase7CompositionResult
new required params) — separate, test-only, not addressed here.
Capture the original ModbusTagDefinition as _source in ModbusTagRow and
rewrite ToDefinition() to use 'with {}', so StringByteOrder, ArrayCount,
Deadband, UnitId, and CoalesceProhibited survive a load→edit→save cycle.
Two pre-existing test bugs surfaced by the auth-alignment branch:
- Test wanted the 204/JSON contract but never sent Accept:
application/json — endpoint correctly returned 302 (form POST).
- Cookie-name assertion still used OtOpcUa.Auth= (now
ZB.MOM.WW.OtOpcUa.Auth= since the Task 1 default change).
Endpoint behavior is intentional and untouched.
ASP.NET Core's cookie-handler IsAjaxRequest heuristic only checks
X-Requested-With (not Accept). Drop the third test (Accept: application/json
was assumed to → 401 but actually → 302) and the Location.ShouldBeNull
assertion on the XHR test (framework still writes Location alongside 401;
clients ignore it). Renamed _ajax_ → _xhr_ for accuracy. Design doc
updated to match.
Adds protected MapGet("/") in the test host plus three [Fact] methods
exercising the cookie scheme's challenge heuristic for the root route:
browser (Accept: text/html), AJAX (X-Requested-With: XMLHttpRequest),
and JSON (Accept: application/json) callers. Also adds a no-redirect
HttpClient helper so the 302 + Location can be asserted directly.
Single Cookie auth scheme; framework default challenge restores 302 → /login
for browsers + 401 for AJAX. OtOpcUaCookieOptions now flows through to
CookieAuthenticationOptions via PostConfigure (fixes a latent bug where the
options class was bound but ignored). Cookie name moves to
ZB.MOM.WW.OtOpcUa.Auth; existing sessions get a one-time forced sign-out.
- DriverTestConnectE2eTests: 3 scenarios (sim/wrong-port/black-hole)
against the Modbus Docker fixture. Sim + wrong-port skip if fixture
unreachable; black-hole uses ModbusDriverProbe directly (no fixture).
- DriverReconnectE2eTests: message round-trip through AdminOperationsActor
cluster singleton — Ok=true + audit write, without live driver side effect.
- DriverStatusHubE2eTests: bridge-mocked fallback — spawns
DriverStatusSignalRBridge in the harness ActorSystem with a mock
IHubContext, publishes DriverHealthChanged to the driver-health DPS
topic, asserts store upsert + hub SendAsync call.
- DockerFixtureAvailability helper: TCP-connect probe for skip guards.
- Moq 4.20.72 added to central package management for hub mocking.
- Design doc §8.3 replaced with concrete pre-ship operator runbook.
- DriverTagPicker shell: modal chrome + per-driver picker body
rendered as ChildContent.
- 9 picker bodies (Modbus/AbCip/AbLegacy/S7/TwinCat/FOCAS/
OpcUaClient/Galaxy/Historian.Wonderware). 5 have computed
builder logic + unit tests; 4 are free-text passthroughs
(live browse for OPC UA + Galaxy is a documented follow-up).
- Each typed driver page gets a "Pick address" button that opens
the modal with the matching body. Picked address surfaces in
the modal footer for manual copy — no JS interop in v1.
- IDriverProbe abstraction in Core.Abstractions; one impl per driver
type, resolved by DriverType string. Phase 7.3 + 7.4 add concrete
probes for the 9 supported driver types.
- TestDriverConnect / TestDriverConnectResult messages.
- AdminOperationsActor.HandleTestDriverConnectAsync looks up the probe
by DriverType, runs it with a [1,60]s clamped timeout, and returns
success/latency or failure/message. Probes that throw or time out
surface as soft failures.
- S7DriverPage.FormModel now preserves Tags through Form ↔ Options
translation (was hard-coding Tags = [] on every save, silently
destroying any tag list that operators had configured).
- Add FormModel_RoundTrip tests for OpcUaClient and Historian
mirror classes — both were translating Options ↔ form-model
entirely untested.
- Surface S7 Tags in the round-trip test so this regression
can't reach merge again.
Adds <summary>, <param>, <typeparam>, and <inheritdoc/> tags to public
members surfaced by commentchecker — resolves 5,847 of 5,869 issues
(99.6%) across three /fixdocs passes.
RoslynScriptedAlarmEvaluator mirrors F8b's pattern for alarm predicates:
caches a compiled ScriptEvaluator<AlarmPredicateContext, bool> per unique
predicate, runs against the dependency dictionary with a 2s timeout, and
turns every failure (compile error, sandbox violation, runtime throw,
ctx.SetVirtualTag attempt — predicates must be pure) into a
ScriptedAlarmEvalResult.Failure. ScriptedAlarmActor preserves prior state
on Failure so a broken predicate can't flip Active/Inactive spuriously.
Program.cs binds both evaluators on driver-role hosts — this fully
satisfies #107 ("bind production VirtualTagEngine + ScriptedAlarmEngine
adapters"). The two Roslyn adapters together replace the F8 + F9 Null
defaults, so VirtualTagActor + ScriptedAlarmActor now run real user
scripts in production.
7 new adapter tests cover: predicate true → Active, predicate false →
Inactive, cache reuse, compile-error denial, write-attempt denial,
empty-predicate denial, post-dispose denial. Host.IntegrationTests now
17/17 green.
Closes#80 + #107. All major v2 follow-ups are now complete; only
cleanup + observability polish remains.
RoslynVirtualTagEvaluator wraps Core.Scripting.ScriptEvaluator + Core
.VirtualTags.VirtualTagContext into a single-tag IVirtualTagEvaluator
adapter. Caches the compiled ScriptEvaluator per unique expression so
the second-and-onwards Evaluate is an in-process method call against the
dependency dictionary. Compile/sandbox/runtime errors all surface as
VirtualTagEvalResult.Failure rather than propagating exceptions through
the VirtualTagActor message loop.
Single-tag scope: cross-tag ctx.SetVirtualTag writes are dropped + logged
because fan-out between actors is owned by DependencyMuxActor. Cycle
detection + cascade ordering stay in Core.VirtualTags.VirtualTagEngine
where they belong (loaded fleet-wide); this adapter keeps the actor
message handler simple.
Host adds Core.Scripting + Core.VirtualTags project refs, plus a
TargetWarningsAsErrors NU1608 suppression — Microsoft.CodeAnalysis.CSharp
.Scripting 4.12.0 pins Common to 4.12.0 but ASP.NET Core transitively
brings Microsoft.CodeAnalysis.Common 5.0.0; the surface we use is stable
across the drift (verified by Core.Scripting.Tests).
Program.cs binds RoslynVirtualTagEvaluator → IVirtualTagEvaluator on
driver-role hosts, replacing the F8-default NullVirtualTagEvaluator so
VirtualTagActor evaluates real user scripts at runtime.
6 new adapter tests cover: simple expression sums, cache reuse across
calls, compile-error denial, runtime-throw denial, empty-expression
denial, post-dispose denial. Host.IntegrationTests now 10/10 green.
Closes#79. F9b + #107 next.
Phase7Composer now carries UnsAreaProjection + UnsLineProjection lists so
the applier can materialise the full UNS topology in the OPC UA address
space. New IOpcUaAddressSpaceSink.EnsureFolder(folderNodeId, parentNodeId,
displayName) seam (no-op default, recorded in tests, forwarded by
DeferredAddressSpaceSink, implemented by SdkAddressSpaceSink). The SDK-
side OtOpcUaNodeManager gains an EnsureFolder API that creates
FolderState nodes with proper parent linkage; RebuildAddressSpace now
clears folders too so re-applies don't accumulate stale topology.
Phase7Applier.MaterialiseHierarchy walks composition.UnsAreas →
composition.UnsLines → composition.EquipmentNodes, calling EnsureFolder
with the correct parent at each level. Idempotent — calling twice with
the same composition is a no-op. OpcUaPublishActor.HandleRebuild invokes
it after Phase7Applier.Apply so OPC UA clients browsing the server now
see Area/Line/Equipment as proper folders rather than flat tag ids.
DeploymentArtifact.ParseComposition reads UnsAreas + UnsLines from the
JSON snapshot the ControlPlane emits, populating the new fields when
present.
Phase7Composer.Compose now accepts UnsAreas + UnsLines; a 3-arg overload
preserves the old signature for legacy callers + existing tests. The
Phase7CompositionResult convenience ctor likewise keeps the planner
tests working without UNS data.
3 new hierarchy tests (pure unit + boot-verify against a real
OtOpcUaSdkServer); OpcUaServer suite is 48/48 green (was 45, +3),
Runtime 74/74 unchanged.
Closes#85.
Boots a real StandardServer + OpcUaApplicationHost, wires
SdkServiceLevelPublisher into a DeferredServiceLevelPublisher (production
binding pattern), spawns OpcUaPublishActor against the deferred
publisher, sends RedundancyStateChanged snapshots, and asserts that
ServerObject.ServiceLevel.Value reflects the role-derived byte:
Primary + RoleLeaderForDriver → 240
Secondary → 100
Together with the F13b endpoint-security tests (which already verify
ServerConfiguration.SecurityPolicies populates the three baseline
profiles), this closes Task 60's "dual-endpoint + ServiceLevel" scope.
Cross-node failover tests stay in the 2-node integration harness
(Task 59 / FailoverScenarioTests).
Runtime suite now 74 / 74 green (+2). Closes Task 60.
SdkServiceLevelPublisher writes Server.ServiceLevel through the SDK's
ServerObjectState — the standard OPC UA non-transparent-redundancy signal
clients use to pick a primary. Writes are guarded by DiagnosticsLock so
concurrent SDK diagnostics scans don't fight with our updates.
DeferredServiceLevelPublisher mirrors the DeferredAddressSpaceSink late-
binding pattern: Akka actors resolve IServiceLevelPublisher at construction,
hosted service swaps the SDK publisher in after StandardServer.Start. Host
Program.cs registers DeferredServiceLevelPublisher as the singleton bound
to IServiceLevelPublisher; OtOpcUaServerHostedService gets it injected and
fills it once IServerInternal is available.
Tests boot a real StandardServer on a free port (cross-platform), call
Publish, then verify ServerObject.ServiceLevel.Value reflects the write.
5 new tests; OpcUaServer suite now 45/45 green (was 40, +5).
Closes#81 residual. Unblocks Task 60 (OPC UA dual-endpoint + ServiceLevel
tests).
OtOpcUaTelemetry (Commons/Observability) centralizes the project's Meter
+ ActivitySource so all instrumentation points emit through a single
named surface. Counters cover the hot paths:
otopcua.deploy.applied (outcome=ack|reject)
otopcua.deploy.apply.duration (s, histogram)
otopcua.driver.lifecycle (event=spawn|spawn_stub|stop|fault)
otopcua.virtualtag.eval (outcome=ok|fail|skip)
otopcua.scriptedalarm.transition (state=activated|acknowledged|cleared)
otopcua.opcua.sink.write (kind=value|alarm|rebuild)
otopcua.redundancy.service_level_change (level=byte)
Plus two ActivitySource spans:
otopcua.deploy.apply wraps DriverHostActor.ApplyAndAck
otopcua.opcua.address_space_rebuild wraps OpcUaPublishActor.HandleRebuild
Instruments are no-op until a listener attaches, so tests + dev hosts
pay nothing for unread telemetry.
Host Program.cs gains AddOtOpcUaObservability() (binds the OtOpcUa Meter
+ ActivitySource to OpenTelemetry, attaches a Prometheus exporter) and
MapOtOpcUaMetrics() (mounts /metrics scrape endpoint). Driver-side
internals + ASP.NET request metrics deliberately stay off — the scrape
payload is scoped to OtOpcUa signals only.
Tests use MeterListener + ActivityListener to verify
VirtualTagActor.eval, OpcUaPublishActor.AttributeValueUpdate, and
RebuildAddressSpace actually emit on the central instruments. Runtime
suite is 72 / 72 green (+3).
Closes#105. Path A (F13b/c/d) complete; next batch options: #85 UNS
folder hierarchy in SDK, or F8b/F9b production engine bindings.
Adds IOpcUaUserAuthenticator seam in OpcUaServer.Security with a deny-all
NullOpcUaUserAuthenticator default. OpcUaApplicationHost subscribes to
SessionManager.ImpersonateUser after _application.Start so UserName tokens
flow through the authenticator and either attach a UserIdentity to the
session (Allow) or set IdentityValidationError = BadIdentityTokenRejected
(Deny / authenticator exception). Anonymous + X509 tokens fall through to
SDK defaults.
LdapOpcUaUserAuthenticator (Host project) bridges to the same
ILdapAuthService that AddOtOpcUaAuth uses for Admin cookies / JWT, so a
single LDAP source-of-truth governs both Admin control plane and OPC UA
data plane. Program.cs registers LdapOptions + LdapAuthService +
IOpcUaUserAuthenticator on driver-role hosts; admin-only nodes are
unchanged.
OtOpcUaServerHostedService threads the resolved authenticator into
OpcUaApplicationHost so the seam respects Host DI.
10 new tests: 6 in OpcUaServer.Tests cover the pure HandleImpersonation
static method (success / denial / anonymous fallthrough / authenticator-
throw / null-username / Null authenticator); 4 in Host.IntegrationTests
cover the LdapOpcUaUserAuthenticator adapter (LDAP allow → Allow with
roles, LDAP deny → Deny, exception → backend-error denial, display-name
fallback). OpcUaServer suite is 40 / 40 green.
Closes#104. Unblocks Task 60 (dual-endpoint + ServiceLevel tests) once
#81 residual lands.
OpcUaApplicationHost.BuildConfigurationAsync now populates
ServerConfiguration.SecurityPolicies + UserTokenPolicies from the new
OpcUaSecurityProfile enum on OpcUaApplicationHostOptions. Defaults expose
all three baseline profiles (None + Basic256Sha256-Sign +
Basic256Sha256-SignAndEncrypt) matching docs/security.md. UserName tokens
are SDK-encrypted with the server cert so they work on None endpoints too;
F13c will plug the LDAP validator into SessionManager.
AutoAcceptUntrustedClientCertificates surfaces as an option for dev flows;
production keeps the default (false) and operators promote rejected certs
through the Admin UI.
InternalsVisibleTo added so BuildSecurityPolicies / BuildUserTokenPolicies
stay encapsulated but unit-testable. 6 new tests cover the pure builders +
two boot-verify cases (3-profile default + hardened single-profile),
bringing the suite to 34 / 34 passing.
Closes#103. Unblocks #104 (F13c LDAP user-token validator).
Wires the OPC UA SDK into the fused Host's lifecycle on driver-role
nodes + spawns OpcUaPublishActor with the proper sink/publisher/dbFactory/
applier resolution. The full read+write data path is now live in
production: Deploy → DriverHost → OpcUaPublish → SDK NodeManager →
subscribed OPC UA clients.
DeferredAddressSpaceSink (Commons.OpcUa):
- Thread-safe wrapper IOpcUaAddressSpaceSink that delegates to an
inner sink swapped in at runtime. Needed because Akka actors
resolve the sink at construction time, but the production sink
(SdkAddressSpaceSink wrapping OtOpcUaNodeManager) only exists
after the SDK StandardServer has started.
- Defaults to NullOpcUaAddressSpaceSink so calls before swap are
safe; SetSink(null) reverts (for graceful shutdown).
OtOpcUaServerHostedService (Host.OpcUa):
- IHostedService that owns the OPC UA SDK lifecycle. Reads
OpcUaApplicationHostOptions from the 'OpcUa' config section,
creates an OtOpcUaSdkServer, boots it through OpcUaApplicationHost,
then swaps a real SdkAddressSpaceSink into the DeferredAddressSpaceSink
singleton.
- SDK boot failure is logged + non-fatal — the rest of the host
(admin UI, driver actors) keeps running. Stop reverts to null sink.
WithOtOpcUaRuntimeActors (Runtime):
- Now spawns OpcUaPublishActor (new actor) + threads its ActorRef
into DriverHostActor's Props so successful applies trigger the
address-space rebuild pipeline.
- Phase7Applier is constructed here from the resolved sink + a
logger; OpcUaPublishActor takes both.
- Prepends the opcua-synchronized-dispatcher HOCON so the extension
is self-contained — consumers (Host, tests) don't need to redeclare
the dispatcher block.
- New OpcUaPublishActorKey + OpcUaPublishActorName for actor-registry
resolution.
- AddOtOpcUaRuntime now also TryAddSingleton's NullOpcUaAddressSpaceSink
+ NullServiceLevelPublisher so admin-only nodes (or tests that
don't bind the Deferred sink) stay safe.
Host.Program.cs (driver-role only):
- Binds DeferredAddressSpaceSink as singleton + as IOpcUaAddressSpaceSink
- AddHostedService<OtOpcUaServerHostedService>()
Tests: OpcUaServer 24 -> 28 (+4 DeferredAddressSpaceSink unit tests),
Runtime 69 -> 69 (existing ServiceCollectionExtensionsTests extended
to verify the new mux + publish actor registration).
All 6 v2 test suites green: 177 tests passing.
Closes#108. Engine-wiring is now production-bound end-to-end on
driver-role nodes — Deploy reaches real OPC UA Variable nodes that
subscribed clients see.