Stop parsing TagConfig twice per tag on the deploy hot path: Phase7Composer's
equipment-tag Select lambda is now block-bodied (captures isHistorized/historianTagname
once), and DeploymentArtifact.BuildEquipmentTagPlans captures locals before result.Add.
Add wrong-type-historianTagname InlineData to ExtractTagHistorizeTests. Extend the
parity round-trip fixture with a 4th tag (isHistorized:false + JSON-null tagname)
exercising the artifact-side private guard path. Align DeploymentArtifact's
ExtractTagHistorize doc-comment with the composer-side phrasing (ExtractTagFullName /
ExtractTagAlarm cross-reference).
Resolves the code-review notes on 95be607a + the AdminUI bundle: the
EnsureVariable docs (IOpcUaAddressSpaceSink, OtOpcUaNodeManager) and the Tag
entity doc no longer say 'Galaxy / SystemPlatform / alias'; the DriverHostActor
ForwardToMux comment now states the real equipment-tag value-routing gap (the
FullName→NodeId 'live values' milestone) instead of claiming Galaxy values map
straight through.
All five suppressed advisories are now resolved at baseline/resolved versions,
so every NuGetAuditSuppress is removed repo-wide:
- System.Security.Cryptography.Xml (GHSA-37gx-xxp4-5rgx / GHSA-w3x6-4m5h-cxqf)
-> fixed by the .NET 10 baseline (10.0.6)
- OPCFoundation Opc.Ua.Core (GHSA-h958-fxgg-g7w3) -> fixed at resolved 1.5.378.106
Two were still live and are now patched via direct security pins:
- OpenTelemetry.Api 1.9.0 -> 1.15.3 (GHSA-g94r-2vxg-569j) pinned in Cluster;
Runtime/ControlPlane/AdminUI + tests inherit via project reference
- Tmds.DBus.Protocol 0.20.0 -> 0.21.3 (GHSA-xrw6-gwf8-vvr9) pinned in Client.UI
Also correct the Historian sidecar runtime comments (x86 -> x64, matching the
csproj PlatformTarget). Solution audit: 0 vulnerable packages; full build clean.
Three code-review points on commit 004558c2 were correct behavior
that was under-documented, not bugs:
1. AlarmConditionDelta gains explicit paragraphs explaining why
CommentAdded is absent: it always originates from a client
AddComment call whose T18 OnAddComment handler returns Good →
SDK auto-fires the comment event (E2); the engine re-projection
carries no delta-field change, so the gate correctly suppresses
the duplicate. Force-firing would double-emit.
2. Same doc explains Retain is intentionally absent: Retain is a
pure function of Active/Acknowledged (both compared), so it
cannot flip without a real delta. Notes future risk if that
ever changes.
3. ReportConditionEvent Time/ReceiveTime comment corrected: the
projection was already applied by WriteAlarmCondition above
with identical values; the restamp is a locality repeat, not a
reorder guard.
Also adds one seam unit-test (103 total, was 102) pinning the
null-vs-empty Message normalization boundary so a change to the
?? string.Empty coalescing is caught at the seam level.
Inbound client acks now route through the engine (T18/T19). On a successful
Acknowledge the T18 gate returns Good, so the SDK applies the acked state to the
AlarmConditionState node and auto-fires its own condition event (E2) -- directly
on the node, bypassing WriteAlarmCondition. The engine then re-projects that same
transition through WriteAlarmCondition, which fired again (E3): a double-emit.
Gate WriteAlarmCondition's ReportConditionEvent on a genuine delta computed
against the node's CURRENT live state (read before projecting the snapshot), not
a last-written cache (which would be stale, since the SDK-applied ack never went
through this method). For a re-projected ack the snapshot equals the node's
already-applied state -> no delta -> suppress E3. Genuine engine-driven
transitions still differ -> fire.
Compared fields (value-equality via AlarmConditionDelta record): Active, Acked,
Confirmed, Enabled, Shelving (mapped from the shelving state machine), Severity
(mapped through MapSeverity to match the bucket the node stores), Message.
Optional Confirmed/Shelving fold to the node read-back default when the child is
absent so they can't register a phantom delta.
Tests prove both: suppression of the simulated inbound ack re-projection
(EventId unchanged) and that genuine transitions fire while identical
re-projections suppress; plus a direct unit test of the ShouldFireConditionEvent
seam. 102/102 OpcUaServer.Tests green.
The SDK fires OnTimedUnshelve with the node manager's system context (no
session, no user identity) when a TimedShelve duration expires. Routing
through the shared HandleAlarmCommand hit the AlarmAck gate and returned
BadUserAccessDenied, leaving the alarm permanently shelved.
Replace the delegated HandleAlarmCommand call with an inline lambda that
bypasses the client gate, extracts the AlarmId the same way, and routes an
Unshelve command so the engine clears its shelve state. The manual-client
Unshelve path via OnShelve(shelving:false) remains gated.
Update the AlarmCommandRouterTests OnTimedUnshelve test to use a real
system context (no UserIdentity) — reproducing the actual SDK invocation
path — and assert Good, AlarmId, Operation==Unshelve, User==empty.
Add a doc note to AlarmCommand.Operation that Enable/Disable are in the
vocabulary but not yet wired at the node-manager seam.
Wire the materialised AlarmConditionState method handlers so a client calling
Acknowledge/Confirm/Shelve/AddComment is gated on the AlarmAck data-plane role
and, when allowed, routed back to the scripted-alarm engine via a new
`alarm-commands` DistributedPubSub topic.
- Commons: new AlarmCommand DTO (AlarmId/Operation/User/Comment/UnshelveAtUtc).
- ScriptedAlarmHostActor: add AlarmCommandsTopic const.
- OtOpcUaNodeManager: settable AlarmCommandRouter + wire OnAcknowledge/OnConfirm/
OnAddComment/OnShelve/OnTimedUnshelve. Each resolves the principal off
ISessionOperationContext.UserIdentity as RoleCarryingUserIdentity, fails closed
(BadUserAccessDenied) when the AlarmAck role is absent or no identity, else maps
+ routes an AlarmCommand and returns Good. OnShelve discriminates OneShotShelve/
TimedShelve/Unshelve from the SDK flags; TimedShelve expiry = UtcNow + ms.
No Akka/IActorRef handle — only the Action<AlarmCommand> delegate. T20 de-dup
note left; WriteAlarmCondition untouched.
- OpcUaServer.Security: OpcUaDataPlaneRoles.AlarmAck shared const (the role was a
bare string everywhere; introduced one symbol for the gate + tests).
- OtOpcUaSdkServer: SetAlarmCommandRouter pass-through.
- Host: boot wiring publishes each command via mediator.Tell(Publish(...)) using a
lazy ActorSystem accessor (mirrors DpsScriptLogPublisher).
- Tests: 11 new gate + mapping tests (OpcUaServer.Tests 88->99, all green).
Code-review follow-up to T17: copy the roles into a fresh array at construction so a
caller mutating the source list cannot retroactively alter a session's granted roles,
and so the T18 ack gate's per-invocation .Contains(...) runs over a known-small frozen
array.
Stop discarding the authenticator's resolved roles during impersonation.
HandleImpersonation now sets args.Identity to a RoleCarryingUserIdentity
(: UserIdentity) that carries result.Roles, so a downstream method handler
can read them off context.UserIdentity for the inbound AlarmAck gate (T18).
Verified via the decompiled SDK (1.5.378.106) that the instance we assign to
ImpersonateEventArgs.Identity is stored by reference onto Session.Identity /
EffectiveIdentity and surfaced unchanged on OperationContext.UserIdentity --
the custom subclass survives the round-trip. No auth-decision logic changes.
IReadOnlyList<string> DependencyRefs compared by reference in the auto-generated record
equality, causing every VirtualTag with dependencies to be flagged "Changed" on every parse
(fresh list instances from composer and artifact-decoder). Add Equals/GetHashCode overrides
with element-wise ordinal comparison so Phase7Plan.IsEmpty short-circuits a no-op redeploy.
Add regression test Identical_virtualtag_snapshots_diff_to_empty_plan (separate list instances,
same contents → IsEmpty true). Add TODO comment in Phase7Applier near needsRebuild predicate.
Adds the EquipmentVirtualTagPlan sealed record (VirtualTagId, EquipmentId,
FolderPath, Name, DataType, Expression, DependencyRefs) and the
EquipmentVirtualTags init-only member on Phase7CompositionResult, mirroring
the existing EquipmentTagPlan / EquipmentTags pattern. Type-only: no producer
logic yet. Two new tests cover the default-empty guarantee and the record shape.
Two bundle-review fixes + idempotency coverage:
- CRITICAL: the planner ignored EquipmentTags, so an incremental deploy changing only
equipment tags produced an empty plan and HandleRebuild short-circuited before
materialising them. Add TagId to EquipmentTagPlan + Added/Removed/ChangedEquipmentTags
to Phase7Plan (diffed by TagId, in IsEmpty, driving Apply's needsRebuild) — mirroring
the GalaxyTags treatment.
- IMPORTANT: equipment variable NodeId was the raw driver FullName, which collides across
identical machines (e.g. two PLCs both exposing register 40001) — the second variable
was silently dropped. NodeId is now folder-scoped (parent/Name); FullName stays on
EquipmentTagPlan for the later values-routing milestone.
- Task 4: SDK-backed idempotency test (double-apply -> single variable); restart-safety
confirmed (RestoreApplied reuses the same RebuildAddressSpace -> HandleRebuild path).
- Minor: align composer equipment-tag sort with the artifact decoder (coalesce FolderPath).
Equipment folder DisplayName was the colloquial MachineCode; the live rebuild (artifact
ReadEquipmentNode) + composer now use the UNS level-5 Name segment, matching Area/Line
folders + EquipmentNodeWalker. NodeId stays the logical EquipmentId so browse-path
resolution + ACLs are unaffected.
Add Phase7Applier.MaterialiseEquipmentTags — a sink-based pass (Task-0 decision A) that
ensures each EquipmentTagPlan's Variable (NodeId = FullName) under its existing equipment
folder, nesting any FolderPath as a sub-folder. Wire it into OpcUaPublishActor.HandleRebuild
after the Galaxy pass. Variables start BadWaitingForInitialData; never re-creates equipment
folders (decision #4).
Add EquipmentTagPlan + an init-only EquipmentTags member on Phase7CompositionResult
(mirror of GalaxyTags). Populate it compose-side (Tag.EquipmentId != null AND owning
namespace Kind == Equipment) and artifact-decode-side via BuildEquipmentTagPlans, with
FullName extracted from Tag.TagConfig. Init-only member (not a 7th positional param) so
existing convenience constructors + call sites are untouched.
Opc.Ua.Server was pinned 1.5.374.126 while Client/Configuration were 1.5.378.106, so the
published Host unified Opc.Ua.Core to 1.5.378 (which dropped Opc.Ua.INodeIdFactory that Server
1.5.374 referenced). Every driver-role node (and the fused site nodes) failed to start the OPC
UA server with TypeLoadException, leaving the OPC data plane dead and the site UIs at 503.
Align all OPC UA packages to 1.5.378.106 (bump Server; drop the Opc.Ua.Configuration/Client
VersionOverrides in OpcUaServer + its integration tests) and port the server host to the
1.5.378 async API:
- ApplicationInstance requires an ITelemetryContext ctor (DefaultTelemetry.Create)
- Start/Stop/LoadApplicationConfiguration/Validate -> async; CheckApplicationInstanceCertificate
-> CheckApplicationInstanceCertificatesAsync
- ImpersonateEventHandler is now (ISession, ImpersonateEventArgs)
- UserNameIdentityToken.DecryptedPassword is now byte[] (UTF-8 decode)
- tests ported (byte[] passwords; async discovery/session/read client API)
Verified: full solution builds, OpcUaServer unit tests 52/52, and in docker-dev all six OPC
endpoints (4840-4845) listen and the site UIs return 302 (were 503). End-to-end OPC behaviour
(read/write/subscribe/security under 1.5.378) still needs a functional client test.
Adds <summary>, <param>, <typeparam>, and <inheritdoc/> tags to public
members surfaced by commentchecker — resolves 5,847 of 5,869 issues
(99.6%) across three /fixdocs passes.
Closes the gap where Tag rows with EquipmentId=NULL + Namespace.Kind=SystemPlatform
(Galaxy hierarchy) existed in ConfigDb but were never surfaced in the OPC UA
address space. Now they materialise as Variable nodes under a folder named for
their FolderPath, browseable through any OPC UA client.
Layers touched:
- IOpcUaAddressSpaceSink: new EnsureVariable(nodeId, parentFolderId, displayName,
dataType) signature on the sink interface, NullSink, DeferredSink, SdkSink.
- OtOpcUaNodeManager.EnsureVariable: creates a BaseDataVariableState parented
under the named folder (or root), initial Value=null +
StatusCode=BadWaitingForInitialData; resolves Tag.DataType strings to the
matching OPC UA built-in NodeId. Idempotent.
- Phase7CompositionResult: new GalaxyTags collection of GalaxyTagPlan records
carrying (TagId, DriverInstanceId, FolderPath, DisplayName, DataType,
MxAccessRef). Constructor overloads keep existing call sites compiling.
- Phase7Composer.Compose: now takes Tag + Namespace inputs, filters for
SystemPlatform-namespace tags with EquipmentId=NULL, emits GalaxyTagPlan
rows with MXAccess ref "FolderPath.Name".
- Phase7Plan: new AddedGalaxyTags / RemovedGalaxyTags / ChangedGalaxyTags
collections + GalaxyTagDelta record; IsEmpty + needsRebuild updated.
- Phase7Planner.Compute: diffs GalaxyTags by TagId via existing DiffById helper.
- DeploymentArtifact.ParseComposition: reads the Tags + Namespaces +
DriverInstances arrays the ConfigComposer already emits, applies the same
SystemPlatform filter, returns the same GalaxyTagPlan list as the composer
so artifact-side and compose-side plans agree.
- Phase7Applier: new MaterialiseGalaxyTags pass that ensures one folder per
distinct FolderPath then one Variable per tag. NodeId for the variable is
"<FolderPath>.<Name>" matching the MXAccess ref so the future Galaxy
SubscribeBulk wiring can address them directly.
- OpcUaPublishActor.RebuildAddressSpace: invokes MaterialiseGalaxyTags after
MaterialiseHierarchy. _lastApplied initialiser updated for the new ctor.
- seed-clusters.sql: pre-existing TestMachine_001.TestAlarm001..003 rows
needed no change — the composer/applier now picks them up automatically.
Verified end-to-end via docker-dev: deploy click → driver-a logs
"Phase7Applier: Galaxy tags materialised (tags=3, folders=1)" → OPC UA Client
CLI browses the three Variable nodes under TestMachine_001 folder. Reads
return BadWaitingForInitialData status (expected — Galaxy driver's
SubscribeBulk wiring to push values into the nodes is the remaining
follow-up).
Phase7Composer now carries UnsAreaProjection + UnsLineProjection lists so
the applier can materialise the full UNS topology in the OPC UA address
space. New IOpcUaAddressSpaceSink.EnsureFolder(folderNodeId, parentNodeId,
displayName) seam (no-op default, recorded in tests, forwarded by
DeferredAddressSpaceSink, implemented by SdkAddressSpaceSink). The SDK-
side OtOpcUaNodeManager gains an EnsureFolder API that creates
FolderState nodes with proper parent linkage; RebuildAddressSpace now
clears folders too so re-applies don't accumulate stale topology.
Phase7Applier.MaterialiseHierarchy walks composition.UnsAreas →
composition.UnsLines → composition.EquipmentNodes, calling EnsureFolder
with the correct parent at each level. Idempotent — calling twice with
the same composition is a no-op. OpcUaPublishActor.HandleRebuild invokes
it after Phase7Applier.Apply so OPC UA clients browsing the server now
see Area/Line/Equipment as proper folders rather than flat tag ids.
DeploymentArtifact.ParseComposition reads UnsAreas + UnsLines from the
JSON snapshot the ControlPlane emits, populating the new fields when
present.
Phase7Composer.Compose now accepts UnsAreas + UnsLines; a 3-arg overload
preserves the old signature for legacy callers + existing tests. The
Phase7CompositionResult convenience ctor likewise keeps the planner
tests working without UNS data.
3 new hierarchy tests (pure unit + boot-verify against a real
OtOpcUaSdkServer); OpcUaServer suite is 48/48 green (was 45, +3),
Runtime 74/74 unchanged.
Closes#85.