AvevaPrerequisites.CheckAllAsync walks eight probe categories producing PrerequisiteCheck rows each with Name (e.g. 'service:aaBootstrap', 'sql:ZB', 'com:LMXProxy', 'registry:ArchestrA.Framework'), Category (AvevaCoreService / AvevaSoftService / AvevaInstall / MxAccessCom / GalaxyRepository / AvevaHistorian / OtOpcUaService / Environment), Status (Pass / Warn / Fail / Skip), and operator-facing Detail message. Report aggregates them: IsLivetestReady (no Fails anywhere) and IsAvevaSideReady (AVEVA-side categories pass, our v2 services can be absent while still considering the environment AVEVA-ready) so different test tiers can use the right threshold.
Individual probes: ServiceProbe.Check queries the Windows Service Control Manager via System.ServiceProcess.ServiceController — treats DemandStart+Stopped as Warn (NmxSvc is DemandStart by design; master pulls it up) but AutoStart+Stopped as Fail; not-installed is Fail for hard-required services, Warn for soft ones; non-Windows hosts get Skip; transitional states like StartPending get Warn with a 'try again' hint. RegistryProbe reads HKLM\SOFTWARE\WOW6432Node\ArchestrA\{Framework,Framework\Platform,MSIInstall} — Framework key presence + populated InstallPath/RootPath values mean System Platform installed; PfeConfigOptions in the Platform subkey (format 'PlatformId=N,EngineId=N,...') indicates a Platform has been deployed from the IDE (PlatformId=0 means never deployed — MXAccess will connect but every subscription will be Bad quality); RebootRequired='True' under MSIInstall surfaces as a loud warn since post-patch behavior is undefined. MxAccessComProbe resolves the LMXProxy.LMXProxyServer ProgID → CLSID → HKLM\SOFTWARE\Classes\WOW6432Node\CLSID\{guid}\InprocServer32, verifying the registered file exists on disk (catches the orphan-registry case where a previous uninstall left the ProgID registered but the DLL is gone — distinguishes it from the 'totally not installed' case by message); also emits a Warn when the test process is 64-bit (MXAccess COM activation fails with REGDB_E_CLASSNOTREG 0x80040154 regardless of registration, so seeing this warning tells operators why the activation would fail even on a fully-installed machine). SqlProbe tests Galaxy Repository via Microsoft.Data.SqlClient using the Windows-auth localhost connection string the repo code defaults to — distinguishes 'SQL Server unreachable' (connection fails) from 'ZB database does not exist' (SELECT DB_ID('ZB') returns null) because they have different remediation paths (sc.exe start MSSQLSERVER vs. restore from .cab backup); a secondary CheckDeployedObjectCountAsync query on 'gobject WHERE deployed_version > 0' warns when the count is zero because discovery smoke tests will return empty hierarchies. NamedPipeProbe opens a 2s NamedPipeClientStream against OtOpcUaGalaxyHost's pipe ('OtOpcUaGalaxy' per the installer default) — pipe accepting a connection proves the Host service is listening; disconnects immediately so we don't consume a session slot.
Service lists kept as internal static data so tests can inspect + override: CoreServices (aaBootstrap + aaGR + NmxSvc + MSSQLSERVER — hard fail if missing), SoftServices (aaLogger + aaUserValidator + aaGlobalDataCacheMonitorSvr — warn only; stack runs without them but diagnostics/auth are degraded), HistorianServices (aahClientAccessPoint + aahGateway — opt-in via Options.CheckHistorian, only matters for HistoryRead IPC paths), OtOpcUaServices (our OtOpcUaGalaxyHost hard-required for end-to-end live tests + OtOpcUa warn + GLAuth warn). Narrower entry points CheckRepositoryOnlyAsync and CheckGalaxyHostPipeOnlyAsync for tests that only care about specific subsystems — avoid paying the full probe cost on every GalaxyRepositoryLiveSmokeTests fact.
Multi-targeting mechanics: System.ServiceProcess.ServiceController + Microsoft.Win32.Registry are NuGet packages on net10 but in-box BCL references on net48; csproj conditions Package vs Reference by TargetFramework. Microsoft.Data.SqlClient v6 supports both frameworks so single PackageReference. Net48Polyfills.cs provides IsExternalInit shim (records/init-only setters) and SupportedOSPlatformAttribute stub so the same Probe sources compile on both frameworks without per-callsite preprocessor guards — lets Roslyn's platform-compatibility analyzer stay useful on net10 without breaking net48 builds.
Existing GalaxyRepositoryLiveSmokeTests updated to delegate its skip decision to AvevaPrerequisites.CheckRepositoryOnlyAsync (legacy ZbReachableAsync kept as a compatibility adapter so the in-test 'if (!await ZbReachableAsync()) return;' pattern keeps working while the surrounding fixtures gradually migrate to Assert.Skip-with-reason). Slnx file registers the new project.
Tests — AvevaPrerequisitesLiveTests (8 new Integration cases, Category=LiveGalaxy): the helper correctly reports Framework install (registry pass), aaBootstrap Running (service pass), aaGR Running (service pass), MxAccess COM registered (com pass), ZB database reachable (sql pass), deployed-object count > 0 (warn-upgraded-to-pass because this box has 49 objects deployed), the AVEVA side is ready even when our own services (OtOpcUaGalaxyHost) aren't installed yet (IsAvevaSideReady=true), and the helper emits rows for OtOpcUaGalaxyHost + OtOpcUa + GLAuth even when not installed (regression guard — nobody can accidentally ship a check that omits our own services). Full Galaxy.Host.Tests Category=LiveGalaxy suite: 13 pass (5 prior smoke + 8 new prerequisites). Full solution build clean, 0 errors.
What's NOT in this PR: end-to-end Galaxy stack smoke (Proxy → Host pipe → MXAccess → real Galaxy tag). That's the next PR — this one is the gate the end-to-end smoke will call first to produce actionable skip messages instead of silent returns.
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
ModbusSimulatorFixture is a collection fixture so the 2s TCP probe runs once per run, not per test; SkipReason gets a clear operator-facing message ('start ModbusPal or override MODBUS_SIM_ENDPOINT'). Tests call Assert.Skip(sim.SkipReason) rather than silently returning — matches the test-plan convention and reads cleanly in CI logs. DL205Profile.BuildOptions deliberately disables the background probe loop since integration tests drive reads explicitly and the probe would race with assertions. Tag naming uses the DL205_ prefix so filter 'DisplayName~DL205' surfaces device-specific failures at a glance.
Project references: xunit.v3 + Shouldly + Microsoft.NET.Test.Sdk + xunit.runner.visualstudio (matches the existing Driver.Modbus.Tests unit project), project ref to src/Driver.Modbus. Registered in ZB.MOM.WW.OtOpcUa.slnx under tests/. ModbusPal/README.md documents the dev loop (install ModbusPal jar, load profile, start simulator, dotnet test), explains MODBUS_SIM_ENDPOINT override for real-PLC benchwork, and flags DL205.xmpp as the first profile to add in a follow-up PR.
dotnet test run against the scaffold (no simulator running) skips cleanly: 0 failed, 0 passed, 1 skipped, with the SkipReason surfaced. dotnet build clean (0 warnings, 0 errors). Updated docs/v2/modbus-test-plan.md to mark the scaffold PR done and renumbered future PRs from 'PR 27+' to 'PR 31+' to stay in sync with the actual PR chain.
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
Renames all 11 projects (5 src + 6 tests), the .slnx solution file, all source-file namespaces, all axaml namespace references, and all v1 documentation references in CLAUDE.md and docs/*.md (excluding docs/v2/ which is already in OtOpcUa form). Also updates the TopShelf service registration name from "LmxOpcUa" to "OtOpcUa" per Phase 0 Task 0.6.
Preserves runtime identifiers per Phase 0 Out-of-Scope rules to avoid breaking v1/v2 client trust during coexistence: OPC UA `ApplicationUri` defaults (`urn:{GalaxyName}:LmxOpcUa`), server `EndpointPath` (`/LmxOpcUa`), `ServerName` default (feeds cert subject CN), `MxAccessConfiguration.ClientName` default (defensive — stays "LmxOpcUa" for MxAccess audit-trail consistency), client OPC UA identifiers (`ApplicationName = "LmxOpcUaClient"`, `ApplicationUri = "urn:localhost:LmxOpcUaClient"`, cert directory `%LocalAppData%\LmxOpcUaClient\pki\`), and the `LmxOpcUaServer` class name (class rename out of Phase 0 scope per Task 0.5 sed pattern; happens in Phase 1 alongside `LmxNodeManager → GenericDriverNodeManager` Core extraction). 23 LmxOpcUa references retained, all enumerated and justified in `docs/v2/implementation/exit-gate-phase-0.md`.
Build clean: 0 errors, 30 warnings (lower than baseline 167). Tests at strict improvement over baseline: 821 passing / 1 failing vs baseline 820 / 2 (one flaky pre-existing failure passed this run; the other still fails — both pre-existing and unrelated to the rename). `Client.UI.Tests`, `Historian.Aveva.Tests`, `Client.Shared.Tests`, `IntegrationTests` all match baseline exactly. Exit gate compliance results recorded in `docs/v2/implementation/exit-gate-phase-0.md` with all 7 checks PASS or DEFERRED-to-PR-review (#7 service install verification needs Windows service permissions on the reviewer's box).
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>