fix(modbus): review r0 - FC23 opt-in, explicit maxReadGap 0 = off, legacy coil types load, one health writer
Coordinator rulings and Important findings from review r0: 1. FC23 is opt-in (new UseFC23ForMultiRegisterWrites, default false); a config without it - including the persisted "disableFC23": false every form-saved config carries - keeps the FC16 wire. DisableFC23 stays the hard kill-switch. 2. An explicit maxReadGap 0 means coalescing off again (its pre-lane meaning); the gap-8 default applies only to an absent key. 3. Coils/DiscreteInputs tags persisted with a register dataType (the old editor saved Int16) are coerced to Bool, never refused, with no deploy warning (a warning can be promoted to a blocking error). The editor loads them as Bool. Register region + Bool is still refused. 4. One comms-fault slot for reads and writes: a good read clears a write's transport fault and vice versa. Minors: Dispose writes its own Unknown health (m1); persisted region/address are authoritative over addressString so a Family change cannot remap a live tag (m2); a malformed-but-delivered reply no longer fails the unit fast (m3); a fresh socket published after a concurrent dispose is torn down (m4); the editor resets address text per tag (m5); master merged (m6); the FC23 latch log says re-init restores it (m7). Back-compat tests use the old persisted JSON shapes and fail without the fixes. Refs #741 Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
This commit is contained in:
@@ -89,16 +89,24 @@ public sealed class ModbusDriverOptions
|
|||||||
public bool UseFC16ForSingleRegisterWrites { get; init; } = false;
|
public bool UseFC16ForSingleRegisterWrites { get; init; } = false;
|
||||||
|
|
||||||
/// <summary>
|
/// <summary>
|
||||||
/// Kill-switch for FC23 (Read/Write Multiple Registers). By default a multi-register holding
|
/// Hard kill-switch for FC23 (Read/Write Multiple Registers): when <c>true</c> the driver never
|
||||||
/// write (2–121 registers: 32/64-bit values, arrays, strings) is sent as ONE FC23 that writes
|
/// emits FC23, even with <see cref="UseFC23ForMultiRegisterWrites"/> set. Default <c>false</c>.
|
||||||
/// the block and reads the same block back, so the device confirms what it now holds. A unit
|
/// FC23 is OPT-IN — a config without <see cref="UseFC23ForMultiRegisterWrites"/> keeps the FC16 wire
|
||||||
/// that answers FC23 with exception 01 (MELSEC QJ71MT91, S7 Modbus servers) is moved to FC16
|
/// behaviour, so the persisted <c>"disableFC23": false</c> every form-saved config carries changes
|
||||||
/// automatically, for that write and every later one; one that fails FC23 at the transport is
|
/// nothing on the wire.
|
||||||
/// moved too (that one write is reported as a comms failure). Set <c>true</c> to always use
|
|
||||||
/// FC16. Default <c>false</c>.
|
|
||||||
/// </summary>
|
/// </summary>
|
||||||
public bool DisableFC23 { get; init; } = false;
|
public bool DisableFC23 { get; init; } = false;
|
||||||
|
|
||||||
|
/// <summary>
|
||||||
|
/// Opt-in: send a multi-register holding write (2–121 registers: 32/64-bit values, arrays, strings)
|
||||||
|
/// as ONE FC23 that writes the block and reads the same block back, so the device confirms what it
|
||||||
|
/// now holds. A unit that answers FC23 with exception 01 (MELSEC QJ71MT91, S7 Modbus servers) moves
|
||||||
|
/// to FC16 for that write and every later one until the next initialize; one that fails FC23 at the
|
||||||
|
/// transport moves too (that one write is reported as a comms failure). Ignored when
|
||||||
|
/// <see cref="DisableFC23"/> is set. Default <c>false</c> = FC16, the historical behaviour.
|
||||||
|
/// </summary>
|
||||||
|
public bool UseFC23ForMultiRegisterWrites { get; init; } = false;
|
||||||
|
|
||||||
/// <summary>
|
/// <summary>
|
||||||
/// Interval for the background re-probe loop that retries auto-prohibited
|
/// Interval for the background re-probe loop that retries auto-prohibited
|
||||||
/// coalesced ranges. When non-null, every <c>AutoProhibitReprobeInterval</c>
|
/// coalesced ranges. When non-null, every <c>AutoProhibitReprobeInterval</c>
|
||||||
@@ -110,14 +118,13 @@ public sealed class ModbusDriverOptions
|
|||||||
public TimeSpan? AutoProhibitReprobeInterval { get; init; } = null;
|
public TimeSpan? AutoProhibitReprobeInterval { get; init; } = null;
|
||||||
|
|
||||||
/// <summary>
|
/// <summary>
|
||||||
/// Block-read coalescing budget. The read planner combines tags in the same (UnitId, Region)
|
/// Block-read coalescing budget. When non-zero, the read planner combines tags in the same
|
||||||
/// group whose addresses are at most this many registers (Coils / DiscreteInputs: bits) apart
|
/// (UnitId, Region) group whose addresses are at most this many registers (Coils / DiscreteInputs:
|
||||||
/// into a single FC03/FC04/FC01/FC02 read, then slices the response back into per-tag values.
|
/// bits) apart into a single FC03/FC04/FC01/FC02 read, then slices the response back into per-tag
|
||||||
/// <c>0</c> coalesces only adjacent or overlapping tags (several <c>BitInRegister</c> tags on one
|
/// values (several <c>BitInRegister</c> tags on one status word fold into one read). <c>0</c> = no
|
||||||
/// status word still fold into one read). Default <c>8</c>. A range the device refuses is
|
/// coalescing — an explicitly authored 0 keeps that historical meaning. Default <c>8</c> applies
|
||||||
/// auto-prohibited and read per tag, so a protected hole costs one extra round trip, not data. To
|
/// only when the key is ABSENT. A range the device refuses is auto-prohibited and read per tag.
|
||||||
/// turn coalescing off entirely set <see cref="DisableReadCoalescing"/>, or exempt one tag with
|
/// <see cref="DisableReadCoalescing"/> also turns it off; <c>coalesceProhibited</c> exempts one tag.
|
||||||
/// its <c>coalesceProhibited</c> key.
|
|
||||||
/// </summary>
|
/// </summary>
|
||||||
public ushort MaxReadGap { get; init; } = DefaultMaxReadGap;
|
public ushort MaxReadGap { get; init; } = DefaultMaxReadGap;
|
||||||
|
|
||||||
|
|||||||
+26
-19
@@ -35,12 +35,14 @@ public static class ModbusTagDefinitionFactory
|
|||||||
=> FromTagConfig(tagConfig, rawPath, ModbusFamily.Generic, MelsecFamily.Q_L_iQR, out def);
|
=> FromTagConfig(tagConfig, rawPath, ModbusFamily.Generic, MelsecFamily.Q_L_iQR, out def);
|
||||||
|
|
||||||
/// <summary>
|
/// <summary>
|
||||||
/// Family-aware overload: an <c>addressString</c> key (the Modicon / mnemonic / family-native grammar
|
/// Family-aware overload. The persisted <c>region</c> + <c>address</c> keys are AUTHORITATIVE whenever
|
||||||
/// of <see cref="ModbusAddressParser"/> — <c>40001:F:CDAB</c>, DL205 <c>V2000</c>, MELSEC <c>D100</c>)
|
/// present — the editor resolves an <c>addressString</c> with the driver's family and persists the
|
||||||
/// is resolved with the DRIVER's <paramref name="family"/> / <paramref name="melsecSubFamily"/> and is
|
/// result, so a later Family / MelsecSubFamily change can never silently remap a live tag. A blob that
|
||||||
/// authoritative for region, offset, type, bit, string length, byte order and array count; the
|
/// carries ONLY an <c>addressString</c> (CSV / API authoring, the Modicon / mnemonic / family-native
|
||||||
/// editor also persists the resolved <c>region</c> / <c>address</c> keys beside it for display and for
|
/// grammar of <see cref="ModbusAddressParser"/> — <c>40001:F:CDAB</c>, DL205 <c>V2000</c>, MELSEC
|
||||||
/// readers that predate it. Without an <c>addressString</c> this is exactly the 3-argument overload.
|
/// <c>D100</c>) is resolved here with the DRIVER's <paramref name="family"/> /
|
||||||
|
/// <paramref name="melsecSubFamily"/>. Without an <c>addressString</c> this is exactly the 3-argument
|
||||||
|
/// overload.
|
||||||
/// </summary>
|
/// </summary>
|
||||||
/// <param name="tagConfig">The authored equipment-tag TagConfig JSON.</param>
|
/// <param name="tagConfig">The authored equipment-tag TagConfig JSON.</param>
|
||||||
/// <param name="rawPath">The tag's RawPath — becomes the definition's identity (<c>Name</c>).</param>
|
/// <param name="rawPath">The tag's RawPath — becomes the definition's identity (<c>Name</c>).</param>
|
||||||
@@ -67,8 +69,9 @@ public static class ModbusTagDefinitionFactory
|
|||||||
ushort stringLength;
|
ushort stringLength;
|
||||||
int? arrayCount;
|
int? arrayCount;
|
||||||
var addressText = ReadAddressString(root, out var addressStringInvalid);
|
var addressText = ReadAddressString(root, out var addressStringInvalid);
|
||||||
if (addressStringInvalid) return false;
|
var hasResolvedKeys = root.TryGetProperty("region", out _) && root.TryGetProperty("address", out _);
|
||||||
if (addressText is not null)
|
if (!hasResolvedKeys && addressStringInvalid) return false;
|
||||||
|
if (!hasResolvedKeys && addressText is not null)
|
||||||
{
|
{
|
||||||
if (!ModbusAddressParser.TryParse(addressText, family, melsecSubFamily, out var parsed, out _) || parsed is null)
|
if (!ModbusAddressParser.TryParse(addressText, family, melsecSubFamily, out var parsed, out _) || parsed is null)
|
||||||
return false;
|
return false;
|
||||||
@@ -106,9 +109,12 @@ public static class ModbusTagDefinitionFactory
|
|||||||
var arrayLength = ReadInt(root, "arrayLength");
|
var arrayLength = ReadInt(root, "arrayLength");
|
||||||
arrayCount = (isArray && arrayLength >= 1) ? arrayLength : null;
|
arrayCount = (isArray && arrayLength >= 1) ? arrayLength : null;
|
||||||
}
|
}
|
||||||
// Region/type compatibility: a bit region carries only Bool, a register region never Bool.
|
// Region/type compatibility. A bit region (Coils / DiscreteInputs) carries only Bool: a non-Bool
|
||||||
// A mismatch used to throw out of the coalescing planner (killing every tag's poll) or
|
// dataType there is COERCED to Bool, never refused — the pre-#741 editor defaulted dataType to
|
||||||
// silently return a bool into an Int32 node.
|
// Int16 and persisted it for coil tags, and the old driver ignored dataType for bit regions, so
|
||||||
|
// those tags read and wrote correctly and must keep doing so. A register region with Bool is
|
||||||
|
// refused: that pair never read (it threw out of the planner and killed every tag's poll).
|
||||||
|
if (region is ModbusRegion.Coils or ModbusRegion.DiscreteInputs) dataType = ModbusDataType.Bool;
|
||||||
if (!IsRegionTypeCompatible(region, dataType)) return false;
|
if (!IsRegionTypeCompatible(region, dataType)) return false;
|
||||||
if (!TagConfigJson.TryReadEnumStrict(root, "stringByteOrder", ModbusStringByteOrder.HighByteFirst, out var stringByteOrder)) return false;
|
if (!TagConfigJson.TryReadEnumStrict(root, "stringByteOrder", ModbusStringByteOrder.HighByteFirst, out var stringByteOrder)) return false;
|
||||||
// Guard: String tags require StringLength >= 1. RegisterCount = (StringLength+1)/2,
|
// Guard: String tags require StringLength >= 1. RegisterCount = (StringLength+1)/2,
|
||||||
@@ -314,14 +320,15 @@ public static class ModbusTagDefinitionFactory
|
|||||||
private static void DescribeRejection(JsonElement root, List<string> warnings)
|
private static void DescribeRejection(JsonElement root, List<string> warnings)
|
||||||
{
|
{
|
||||||
var addressText = ReadAddressString(root, out var addressStringInvalid);
|
var addressText = ReadAddressString(root, out var addressStringInvalid);
|
||||||
if (addressStringInvalid)
|
var hasResolvedKeys = root.TryGetProperty("region", out _) && root.TryGetProperty("address", out _);
|
||||||
|
if (!hasResolvedKeys && addressStringInvalid)
|
||||||
{
|
{
|
||||||
warnings.Add("Modbus TagConfig 'addressString' is not a string — the tag will not resolve (BadNodeIdUnknown).");
|
warnings.Add("Modbus TagConfig 'addressString' is not a string — the tag will not resolve (BadNodeIdUnknown).");
|
||||||
return;
|
return;
|
||||||
}
|
}
|
||||||
if (addressText is not null)
|
if (!hasResolvedKeys && addressText is not null)
|
||||||
{
|
{
|
||||||
// The addressString is authoritative; the other address keys are not read at all.
|
// String-only blob: the addressString is what the driver resolves.
|
||||||
if (!ModbusAddressParser.TryParse(addressText, out _, out var error))
|
if (!ModbusAddressParser.TryParse(addressText, out _, out var error))
|
||||||
warnings.Add($"Modbus 'addressString' '{addressText}' does not parse under any PLC family ({error}) — "
|
warnings.Add($"Modbus 'addressString' '{addressText}' does not parse under any PLC family ({error}) — "
|
||||||
+ "the tag will not resolve (BadNodeIdUnknown).");
|
+ "the tag will not resolve (BadNodeIdUnknown).");
|
||||||
@@ -372,12 +379,12 @@ public static class ModbusTagDefinitionFactory
|
|||||||
? r : ModbusRegion.HoldingRegisters;
|
? r : ModbusRegion.HoldingRegisters;
|
||||||
if (!TagConfigJson.TryReadEnumStrict(root, "dataType", DefaultDataType(region), out var dataType)) return;
|
if (!TagConfigJson.TryReadEnumStrict(root, "dataType", DefaultDataType(region), out var dataType)) return;
|
||||||
|
|
||||||
if (root.TryGetProperty("region", out _) && !IsRegionTypeCompatible(region, dataType))
|
// Only a register region with Bool is refused (a bit region with any type is coerced to Bool).
|
||||||
|
if (root.TryGetProperty("region", out _) && region is not (ModbusRegion.Coils or ModbusRegion.DiscreteInputs)
|
||||||
|
&& !IsRegionTypeCompatible(region, dataType))
|
||||||
{
|
{
|
||||||
warnings.Add(region is ModbusRegion.Coils or ModbusRegion.DiscreteInputs
|
warnings.Add($"Modbus Bool tags only live in Coils / DiscreteInputs; a {region} tag must use a register type "
|
||||||
? $"Modbus region {region} only carries Bool tags; got {dataType} — the tag is rejected (BadNodeIdUnknown)."
|
+ "(use BitInRegister for a bit of a register) — the tag is rejected (BadNodeIdUnknown).");
|
||||||
: $"Modbus Bool tags only live in Coils / DiscreteInputs; a {region} tag must use a register type "
|
|
||||||
+ "(use BitInRegister for a bit of a register) — the tag is rejected (BadNodeIdUnknown).");
|
|
||||||
}
|
}
|
||||||
|
|
||||||
if (dataType == ModbusDataType.String && (ushort)ReadInt(root, "stringLength") < 1)
|
if (dataType == ModbusDataType.String && (ushort)ReadInt(root, "stringLength") < 1)
|
||||||
|
|||||||
@@ -61,11 +61,12 @@ public sealed class ModbusDriver
|
|||||||
/// <summary>Guards <see cref="_generation"/>, the transport/table publish and the health fields.</summary>
|
/// <summary>Guards <see cref="_generation"/>, the transport/table publish and the health fields.</summary>
|
||||||
private readonly object _stateLock = new();
|
private readonly object _stateLock = new();
|
||||||
|
|
||||||
// Health is composed from two independent sides so a good write clears only a WRITE-side
|
// ONE comms-fault slot for reads AND writes: a fault is a property of the shared transport, so the
|
||||||
// Degraded (and a good read only a read-side one). LastSuccessfulRead advances on any evidence the
|
// latest batch of either kind decides — a good read clears a Degraded a write's timeout raised and vice
|
||||||
// device answered — a good read, a good write, a refusal, or a probe answer.
|
// versa (two independent sides latched a single write blip as Degraded forever in a read-mostly plant).
|
||||||
private string? _readFault;
|
// LastSuccessfulRead advances on any evidence the device answered — a good read, a good write, a
|
||||||
private string? _writeFault;
|
// refusal, or a probe answer.
|
||||||
|
private string? _commsFault;
|
||||||
|
|
||||||
// Once-per-tag Warning for deterministic device refusals (exception 01/02/03, undecodable data).
|
// Once-per-tag Warning for deterministic device refusals (exception 01/02/03, undecodable data).
|
||||||
// Replaced (never cleared in place) on every table publish.
|
// Replaced (never cleared in place) on every table publish.
|
||||||
@@ -246,16 +247,13 @@ public sealed class ModbusDriver
|
|||||||
// failure is the re-initialize window itself, which the lifecycle reports on its own.
|
// failure is the re-initialize window itself, which the lifecycle reports on its own.
|
||||||
var current = _health;
|
var current = _health;
|
||||||
if (current.State is DriverState.Faulted or DriverState.Initializing or DriverState.Unknown) return;
|
if (current.State is DriverState.Faulted or DriverState.Initializing or DriverState.Unknown) return;
|
||||||
_readFault = ex.Message;
|
_commsFault = ex.Message;
|
||||||
PublishComposedHealthLocked(current.LastSuccessfulRead);
|
PublishComposedHealthLocked(current.LastSuccessfulRead);
|
||||||
}
|
}
|
||||||
}
|
}
|
||||||
|
|
||||||
// ---- health composition ----
|
// ---- health composition ----
|
||||||
|
|
||||||
/// <summary>Which half of the driver a batch outcome came from.</summary>
|
|
||||||
private enum HealthSide { Read, Write }
|
|
||||||
|
|
||||||
/// <summary>
|
/// <summary>
|
||||||
/// Per-batch accounting: did the device answer anything, did a comms fault happen, and which units
|
/// Per-batch accounting: did the device answer anything, did a comms fault happen, and which units
|
||||||
/// (or the whole endpoint) must the rest of this batch fail fast against.
|
/// (or the whole endpoint) must the rest of this batch fail fast against.
|
||||||
@@ -277,7 +275,7 @@ public sealed class ModbusDriver
|
|||||||
/// <paramref name="generation"/> is still current. A batch that touched no device (every reference
|
/// <paramref name="generation"/> is still current. A batch that touched no device (every reference
|
||||||
/// unknown, every write refused before the wire) changes nothing.
|
/// unknown, every write refused before the wire) changes nothing.
|
||||||
/// </summary>
|
/// </summary>
|
||||||
private void ReportOutcome(int generation, HealthSide side, BatchOutcome batch, DateTime now)
|
private void ReportOutcome(int generation, BatchOutcome batch, DateTime now)
|
||||||
{
|
{
|
||||||
if (!batch.Answered && batch.CommsFault is null) return;
|
if (!batch.Answered && batch.CommsFault is null) return;
|
||||||
lock (_stateLock)
|
lock (_stateLock)
|
||||||
@@ -285,16 +283,15 @@ public sealed class ModbusDriver
|
|||||||
if (generation != _generation) return;
|
if (generation != _generation) return;
|
||||||
var current = _health;
|
var current = _health;
|
||||||
if (current.State is DriverState.Faulted or DriverState.Initializing or DriverState.Unknown) return;
|
if (current.State is DriverState.Faulted or DriverState.Initializing or DriverState.Unknown) return;
|
||||||
if (side == HealthSide.Read) _readFault = batch.CommsFault;
|
_commsFault = batch.CommsFault;
|
||||||
else _writeFault = batch.CommsFault;
|
|
||||||
PublishComposedHealthLocked(batch.Answered ? now : current.LastSuccessfulRead);
|
PublishComposedHealthLocked(batch.Answered ? now : current.LastSuccessfulRead);
|
||||||
}
|
}
|
||||||
}
|
}
|
||||||
|
|
||||||
/// <summary>Writes Healthy/Degraded from the two fault sides. Caller holds <see cref="_stateLock"/>.</summary>
|
/// <summary>Writes Healthy/Degraded from the comms-fault slot. Caller holds <see cref="_stateLock"/>.</summary>
|
||||||
private void PublishComposedHealthLocked(DateTime? lastSuccessfulRead)
|
private void PublishComposedHealthLocked(DateTime? lastSuccessfulRead)
|
||||||
{
|
{
|
||||||
var fault = _readFault ?? _writeFault;
|
var fault = _commsFault;
|
||||||
WriteHealth(fault is null
|
WriteHealth(fault is null
|
||||||
? new DriverHealth(DriverState.Healthy, lastSuccessfulRead, null)
|
? new DriverHealth(DriverState.Healthy, lastSuccessfulRead, null)
|
||||||
: new DriverHealth(DriverState.Degraded, lastSuccessfulRead, fault));
|
: new DriverHealth(DriverState.Degraded, lastSuccessfulRead, fault));
|
||||||
@@ -321,8 +318,7 @@ public sealed class ModbusDriver
|
|||||||
lock (_stateLock)
|
lock (_stateLock)
|
||||||
{
|
{
|
||||||
if (generation != _generation) return;
|
if (generation != _generation) return;
|
||||||
_readFault = null;
|
_commsFault = null;
|
||||||
_writeFault = null;
|
|
||||||
WriteHealth(health);
|
WriteHealth(health);
|
||||||
}
|
}
|
||||||
}
|
}
|
||||||
@@ -370,7 +366,10 @@ public sealed class ModbusDriver
|
|||||||
return StatusBadCommunicationError;
|
return StatusBadCommunicationError;
|
||||||
default:
|
default:
|
||||||
batch.CommsFault ??= ex.Message;
|
batch.CommsFault ??= ex.Message;
|
||||||
batch.FailUnit(unit);
|
// Fail the unit fast only when nothing came back in time (timeout / desync / socket-level IO):
|
||||||
|
// a malformed-but-delivered reply (byte-count mismatch) proves the unit responds, so its
|
||||||
|
// siblings are still tried.
|
||||||
|
if (ex is IOException or TimeoutException or OperationCanceledException) batch.FailUnit(unit);
|
||||||
return StatusBadCommunicationError;
|
return StatusBadCommunicationError;
|
||||||
}
|
}
|
||||||
}
|
}
|
||||||
@@ -493,8 +492,7 @@ public sealed class ModbusDriver
|
|||||||
generation = ++_generation;
|
generation = ++_generation;
|
||||||
previous = _transport;
|
previous = _transport;
|
||||||
_transport = null;
|
_transport = null;
|
||||||
_readFault = null;
|
_commsFault = null;
|
||||||
_writeFault = null;
|
|
||||||
WriteHealth(new DriverHealth(DriverState.Initializing, null, null));
|
WriteHealth(new DriverHealth(DriverState.Initializing, null, null));
|
||||||
}
|
}
|
||||||
|
|
||||||
@@ -728,7 +726,9 @@ public sealed class ModbusDriver
|
|||||||
var results = new DataValueSnapshot[fullReferences.Count];
|
var results = new DataValueSnapshot[fullReferences.Count];
|
||||||
var batch = new BatchOutcome();
|
var batch = new BatchOutcome();
|
||||||
|
|
||||||
var coalesced = !_options.DisableReadCoalescing
|
// MaxReadGap 0 = coalescing OFF (its pre-lane meaning, kept for every persisted config that authored
|
||||||
|
// it); the gap-8 default applies only to an absent key.
|
||||||
|
var coalesced = !_options.DisableReadCoalescing && _options.MaxReadGap > 0
|
||||||
? await ReadCoalescedAsync(transport, table, fullReferences, results, now, batch, cancellationToken).ConfigureAwait(false)
|
? await ReadCoalescedAsync(transport, table, fullReferences, results, now, batch, cancellationToken).ConfigureAwait(false)
|
||||||
: new HashSet<int>();
|
: new HashSet<int>();
|
||||||
|
|
||||||
@@ -774,7 +774,7 @@ public sealed class ModbusDriver
|
|||||||
|
|
||||||
// ONE health write per batch, worst-wins over the batch, generation-checked. It used to be
|
// ONE health write per batch, worst-wins over the batch, generation-checked. It used to be
|
||||||
// last-writer-wins per tag, so health flapped with tag order.
|
// last-writer-wins per tag, so health flapped with tag order.
|
||||||
ReportOutcome(generation, HealthSide.Read, batch, now);
|
ReportOutcome(generation, batch, now);
|
||||||
return results;
|
return results;
|
||||||
}
|
}
|
||||||
|
|
||||||
@@ -1503,9 +1503,9 @@ public sealed class ModbusDriver
|
|||||||
}
|
}
|
||||||
}
|
}
|
||||||
|
|
||||||
// Write-side health: a comms failure degrades it (LastSuccessfulRead preserved); a good write or a
|
// Write outcome feeds the same single health slot as reads: a comms failure degrades (LastSuccessfulRead
|
||||||
// device refusal proves the device answered and clears a write-side Degraded. Generation-checked.
|
// preserved); a good write or a device refusal proves the device answered and clears it. Generation-checked.
|
||||||
ReportOutcome(generation, HealthSide.Write, batch, DateTime.UtcNow);
|
ReportOutcome(generation, batch, DateTime.UtcNow);
|
||||||
return results;
|
return results;
|
||||||
}
|
}
|
||||||
|
|
||||||
@@ -1665,7 +1665,8 @@ public sealed class ModbusDriver
|
|||||||
/// <summary>
|
/// <summary>
|
||||||
/// Multi-register write via FC23 (Read/Write Multiple Registers): the device writes the block and
|
/// Multi-register write via FC23 (Read/Write Multiple Registers): the device writes the block and
|
||||||
/// returns the SAME block read back in one transaction, so the write is confirmed by the device's own
|
/// returns the SAME block read back in one transaction, so the write is confirmed by the device's own
|
||||||
/// post-write registers. Gated by <see cref="ModbusDriverOptions.DisableFC23"/>. A device that does
|
/// post-write registers. OPT-IN via <see cref="ModbusDriverOptions.UseFC23ForMultiRegisterWrites"/>,
|
||||||
|
/// and <see cref="ModbusDriverOptions.DisableFC23"/> is the hard kill-switch. A device that does
|
||||||
/// not implement FC23 (MELSEC QJ71MT91, S7 Modbus servers — exception 01) falls back to FC16 for this
|
/// not implement FC23 (MELSEC QJ71MT91, S7 Modbus servers — exception 01) falls back to FC16 for this
|
||||||
/// write and every later one on that unit, which is safe because an Illegal Function wrote nothing.
|
/// write and every later one on that unit, which is safe because an Illegal Function wrote nothing.
|
||||||
/// A transport failure on FC23 is reported (its outcome is unknown, so it is not retried as FC16) and
|
/// A transport failure on FC23 is reported (its outcome is unknown, so it is not retried as FC16) and
|
||||||
@@ -1681,7 +1682,8 @@ public sealed class ModbusDriver
|
|||||||
var unsupported = Volatile.Read(ref _fc23Unsupported);
|
var unsupported = Volatile.Read(ref _fc23Unsupported);
|
||||||
// Only genuinely multi-register writes: a single register forced onto FC16 (UseFC16ForSingleRegisterWrites)
|
// Only genuinely multi-register writes: a single register forced onto FC16 (UseFC16ForSingleRegisterWrites)
|
||||||
// stays on the function code the operator named.
|
// stays on the function code the operator named.
|
||||||
if (_options.DisableFC23 || qty < 2 || qty > Fc23MaxWriteRegisters || unsupported.ContainsKey(unit)) return false;
|
if (!_options.UseFC23ForMultiRegisterWrites || _options.DisableFC23
|
||||||
|
|| qty < 2 || qty > Fc23MaxWriteRegisters || unsupported.ContainsKey(unit)) return false;
|
||||||
|
|
||||||
var pdu = new byte[10 + 1 + bytes.Length];
|
var pdu = new byte[10 + 1 + bytes.Length];
|
||||||
pdu[0] = 0x17;
|
pdu[0] = 0x17;
|
||||||
@@ -1701,7 +1703,7 @@ public sealed class ModbusDriver
|
|||||||
{
|
{
|
||||||
if (unsupported.TryAdd(unit, 0))
|
if (unsupported.TryAdd(unit, 0))
|
||||||
_logger.LogInformation(
|
_logger.LogInformation(
|
||||||
"Modbus unit {Unit} does not implement FC23 (Illegal Function); multi-register writes use FC16. Driver={DriverInstanceId}",
|
"Modbus unit {Unit} does not implement FC23 (Illegal Function); multi-register writes use FC16 until the driver is re-initialized. Driver={DriverInstanceId}",
|
||||||
unit, _driverInstanceId);
|
unit, _driverInstanceId);
|
||||||
return false;
|
return false;
|
||||||
}
|
}
|
||||||
@@ -1709,7 +1711,7 @@ public sealed class ModbusDriver
|
|||||||
{
|
{
|
||||||
if (unsupported.TryAdd(unit, 0))
|
if (unsupported.TryAdd(unit, 0))
|
||||||
_logger.LogWarning(ex,
|
_logger.LogWarning(ex,
|
||||||
"Modbus FC23 write to unit {Unit} failed at the transport; later multi-register writes to it use FC16. Driver={DriverInstanceId}",
|
"Modbus FC23 write to unit {Unit} failed at the transport; later multi-register writes to it use FC16 until the driver is re-initialized (a redeploy or reconnect restores FC23). Driver={DriverInstanceId}",
|
||||||
unit, _driverInstanceId);
|
unit, _driverInstanceId);
|
||||||
throw;
|
throw;
|
||||||
}
|
}
|
||||||
@@ -2318,7 +2320,13 @@ public sealed class ModbusDriver
|
|||||||
// Dispose supersedes any in-flight (abandoned) initialize up front, even when it then has to
|
// Dispose supersedes any in-flight (abandoned) initialize up front, even when it then has to
|
||||||
// bypass the gate: that initialize will find its generation moved on and release its own
|
// bypass the gate: that initialize will find its generation moved on and release its own
|
||||||
// transport instead of publishing it after this teardown.
|
// transport instead of publishing it after this teardown.
|
||||||
lock (_stateLock) _generation++;
|
int generation;
|
||||||
|
DateTime? lastRead;
|
||||||
|
lock (_stateLock)
|
||||||
|
{
|
||||||
|
generation = ++_generation;
|
||||||
|
lastRead = _health.LastSuccessfulRead;
|
||||||
|
}
|
||||||
if (await _lifecycleGate.WaitAsync(LifecycleGateTimeout).ConfigureAwait(false))
|
if (await _lifecycleGate.WaitAsync(LifecycleGateTimeout).ConfigureAwait(false))
|
||||||
{
|
{
|
||||||
try
|
try
|
||||||
@@ -2329,14 +2337,18 @@ public sealed class ModbusDriver
|
|||||||
{
|
{
|
||||||
_lifecycleGate.Release();
|
_lifecycleGate.Release();
|
||||||
}
|
}
|
||||||
|
}
|
||||||
return;
|
else
|
||||||
|
{
|
||||||
|
_logger.LogWarning(
|
||||||
|
"Modbus lifecycle gate still held at dispose; tearing the transport down anyway. Driver={DriverInstanceId}",
|
||||||
|
_driverInstanceId);
|
||||||
|
await TeardownAsync().ConfigureAwait(false);
|
||||||
}
|
}
|
||||||
|
|
||||||
_logger.LogWarning(
|
// Dispose's own final health write. Bumping the generation above drops a still-running shutdown's
|
||||||
"Modbus lifecycle gate still held at dispose; tearing the transport down anyway. Driver={DriverInstanceId}",
|
// Unknown write, so without this a disposed driver kept reporting whatever it last was (e.g. Healthy).
|
||||||
_driverInstanceId);
|
WriteLifecycleHealth(generation, new DriverHealth(DriverState.Unknown, lastRead, null));
|
||||||
await TeardownAsync().ConfigureAwait(false);
|
|
||||||
}
|
}
|
||||||
|
|
||||||
/// <summary>
|
/// <summary>
|
||||||
|
|||||||
@@ -85,6 +85,7 @@ public static class ModbusDriverFactoryExtensions
|
|||||||
UseFC15ForSingleCoilWrites = dto.UseFC15ForSingleCoilWrites ?? false,
|
UseFC15ForSingleCoilWrites = dto.UseFC15ForSingleCoilWrites ?? false,
|
||||||
UseFC16ForSingleRegisterWrites = dto.UseFC16ForSingleRegisterWrites ?? false,
|
UseFC16ForSingleRegisterWrites = dto.UseFC16ForSingleRegisterWrites ?? false,
|
||||||
DisableFC23 = dto.DisableFC23 ?? false,
|
DisableFC23 = dto.DisableFC23 ?? false,
|
||||||
|
UseFC23ForMultiRegisterWrites = dto.UseFC23ForMultiRegisterWrites ?? false,
|
||||||
WriteOnChangeOnly = dto.WriteOnChangeOnly ?? false,
|
WriteOnChangeOnly = dto.WriteOnChangeOnly ?? false,
|
||||||
MaxReadGap = dto.MaxReadGap ?? ModbusDriverOptions.DefaultMaxReadGap,
|
MaxReadGap = dto.MaxReadGap ?? ModbusDriverOptions.DefaultMaxReadGap,
|
||||||
DisableReadCoalescing = dto.DisableReadCoalescing ?? false,
|
DisableReadCoalescing = dto.DisableReadCoalescing ?? false,
|
||||||
@@ -187,6 +188,8 @@ public static class ModbusDriverFactoryExtensions
|
|||||||
public bool? UseFC16ForSingleRegisterWrites { get; init; }
|
public bool? UseFC16ForSingleRegisterWrites { get; init; }
|
||||||
/// <summary>Gets or sets a value indicating whether to disable function code 23.</summary>
|
/// <summary>Gets or sets a value indicating whether to disable function code 23.</summary>
|
||||||
public bool? DisableFC23 { get; init; }
|
public bool? DisableFC23 { get; init; }
|
||||||
|
/// <summary>Gets or sets a value indicating whether multi-register writes opt in to FC23 write + read-back.</summary>
|
||||||
|
public bool? UseFC23ForMultiRegisterWrites { get; init; }
|
||||||
/// <summary>Gets or sets a value indicating whether to write only on change.</summary>
|
/// <summary>Gets or sets a value indicating whether to write only on change.</summary>
|
||||||
public bool? WriteOnChangeOnly { get; init; }
|
public bool? WriteOnChangeOnly { get; init; }
|
||||||
/// <summary>Gets or sets the maximum gap between register addresses for coalescing.</summary>
|
/// <summary>Gets or sets the maximum gap between register addresses for coalescing.</summary>
|
||||||
|
|||||||
@@ -103,6 +103,13 @@ public sealed class ModbusSocketLifecycle : IAsyncDisposable
|
|||||||
_stream = client.GetStream();
|
_stream = client.GetStream();
|
||||||
_client = client;
|
_client = client;
|
||||||
client = null; // ownership transferred
|
client = null; // ownership transferred
|
||||||
|
if (Volatile.Read(ref _disposed) != 0)
|
||||||
|
{
|
||||||
|
// A DisposeAsync that ran between the check above and the publish has already torn down;
|
||||||
|
// tear the fresh socket down ourselves so it is never stranded for the finalizer.
|
||||||
|
await TearDownAsync().ConfigureAwait(false);
|
||||||
|
throw new ObjectDisposedException(nameof(ModbusSocketLifecycle));
|
||||||
|
}
|
||||||
_lastSuccessUtc = DateTime.UtcNow;
|
_lastSuccessUtc = DateTime.UtcNow;
|
||||||
}
|
}
|
||||||
catch (OperationCanceledException) when (!ct.IsCancellationRequested)
|
catch (OperationCanceledException) when (!ct.IsCancellationRequested)
|
||||||
|
|||||||
+11
-2
@@ -80,7 +80,7 @@
|
|||||||
<div class="col-md-3">
|
<div class="col-md-3">
|
||||||
<label class="form-label">Max read gap (coalescing)</label>
|
<label class="form-label">Max read gap (coalescing)</label>
|
||||||
<InputNumber @bind-Value="_form.MaxReadGap" @bind-Value:after="EmitAsync" class="form-control form-control-sm" />
|
<InputNumber @bind-Value="_form.MaxReadGap" @bind-Value:after="EmitAsync" class="form-control form-control-sm" />
|
||||||
<div class="form-text">Default 8. 0 = adjacent tags only. Refused ranges fall back per tag.</div>
|
<div class="form-text">0 = no coalescing. Default 8. Refused ranges fall back per tag.</div>
|
||||||
</div>
|
</div>
|
||||||
<div class="col-md-3">
|
<div class="col-md-3">
|
||||||
<div class="form-check form-switch mt-4">
|
<div class="form-check form-switch mt-4">
|
||||||
@@ -112,7 +112,13 @@
|
|||||||
<div class="col-md-4">
|
<div class="col-md-4">
|
||||||
<div class="form-check form-switch">
|
<div class="form-check form-switch">
|
||||||
<InputCheckbox @bind-Value="_form.DisableFC23" @bind-Value:after="EmitAsync" class="form-check-input" id="disableFC23" />
|
<InputCheckbox @bind-Value="_form.DisableFC23" @bind-Value:after="EmitAsync" class="form-check-input" id="disableFC23" />
|
||||||
<label class="form-check-label" for="disableFC23">Disable FC23 (multi-register writes use FC16 instead of FC23 write + read-back)</label>
|
<label class="form-check-label" for="disableFC23">Disable FC23 (never send FC23, even when opted in below)</label>
|
||||||
|
</div>
|
||||||
|
</div>
|
||||||
|
<div class="col-md-4">
|
||||||
|
<div class="form-check form-switch">
|
||||||
|
<InputCheckbox @bind-Value="_form.UseFC23ForMultiRegisterWrites" @bind-Value:after="EmitAsync" class="form-check-input" id="useFC23" />
|
||||||
|
<label class="form-check-label" for="useFC23">Use FC23 write + read-back for multi-register writes (opt-in; default FC16)</label>
|
||||||
</div>
|
</div>
|
||||||
</div>
|
</div>
|
||||||
<div class="col-md-4">
|
<div class="col-md-4">
|
||||||
@@ -324,6 +330,7 @@
|
|||||||
public bool UseFC15ForSingleCoilWrites { get; set; } = false;
|
public bool UseFC15ForSingleCoilWrites { get; set; } = false;
|
||||||
public bool UseFC16ForSingleRegisterWrites { get; set; } = false;
|
public bool UseFC16ForSingleRegisterWrites { get; set; } = false;
|
||||||
public bool DisableFC23 { get; set; } = false;
|
public bool DisableFC23 { get; set; } = false;
|
||||||
|
public bool UseFC23ForMultiRegisterWrites { get; set; } = false;
|
||||||
public bool WriteOnChangeOnly { get; set; } = false;
|
public bool WriteOnChangeOnly { get; set; } = false;
|
||||||
|
|
||||||
// Keep-alive
|
// Keep-alive
|
||||||
@@ -368,6 +375,7 @@
|
|||||||
UseFC15ForSingleCoilWrites = o.UseFC15ForSingleCoilWrites,
|
UseFC15ForSingleCoilWrites = o.UseFC15ForSingleCoilWrites,
|
||||||
UseFC16ForSingleRegisterWrites = o.UseFC16ForSingleRegisterWrites,
|
UseFC16ForSingleRegisterWrites = o.UseFC16ForSingleRegisterWrites,
|
||||||
DisableFC23 = o.DisableFC23,
|
DisableFC23 = o.DisableFC23,
|
||||||
|
UseFC23ForMultiRegisterWrites = o.UseFC23ForMultiRegisterWrites,
|
||||||
WriteOnChangeOnly = o.WriteOnChangeOnly,
|
WriteOnChangeOnly = o.WriteOnChangeOnly,
|
||||||
KeepAliveEnabled = o.KeepAlive.Enabled,
|
KeepAliveEnabled = o.KeepAlive.Enabled,
|
||||||
KeepAliveTimeSeconds = (int)o.KeepAlive.Time.TotalSeconds,
|
KeepAliveTimeSeconds = (int)o.KeepAlive.Time.TotalSeconds,
|
||||||
@@ -404,6 +412,7 @@
|
|||||||
UseFC15ForSingleCoilWrites = UseFC15ForSingleCoilWrites,
|
UseFC15ForSingleCoilWrites = UseFC15ForSingleCoilWrites,
|
||||||
UseFC16ForSingleRegisterWrites = UseFC16ForSingleRegisterWrites,
|
UseFC16ForSingleRegisterWrites = UseFC16ForSingleRegisterWrites,
|
||||||
DisableFC23 = DisableFC23,
|
DisableFC23 = DisableFC23,
|
||||||
|
UseFC23ForMultiRegisterWrites = UseFC23ForMultiRegisterWrites,
|
||||||
AutoProhibitReprobeInterval = AutoProhibitReprobeIntervalSeconds > 0
|
AutoProhibitReprobeInterval = AutoProhibitReprobeIntervalSeconds > 0
|
||||||
? TimeSpan.FromSeconds(AutoProhibitReprobeIntervalSeconds) : null,
|
? TimeSpan.FromSeconds(AutoProhibitReprobeIntervalSeconds) : null,
|
||||||
MaxReadGap = (ushort)Math.Clamp(MaxReadGap, 0, 65535),
|
MaxReadGap = (ushort)Math.Clamp(MaxReadGap, 0, 65535),
|
||||||
|
|||||||
+4
-1
@@ -80,7 +80,10 @@
|
|||||||
if (ConfigJson == _lastConfigJson) { return; }
|
if (ConfigJson == _lastConfigJson) { return; }
|
||||||
_lastConfigJson = ConfigJson;
|
_lastConfigJson = ConfigJson;
|
||||||
_m = ModbusTagConfigModel.FromJson(ConfigJson);
|
_m = ModbusTagConfigModel.FromJson(ConfigJson);
|
||||||
_addressText ??= _m.AddressString;
|
// Reset on EVERY config change: a reused editor instance switched to another tag must not show the
|
||||||
|
// previous tag's address text.
|
||||||
|
_addressText = _m.AddressString;
|
||||||
|
_addressError = null;
|
||||||
_family = ModbusTagConfigModel.ReadFamily(GetDriverConfigJson()).Family;
|
_family = ModbusTagConfigModel.ReadFamily(GetDriverConfigJson()).Family;
|
||||||
}
|
}
|
||||||
|
|
||||||
|
|||||||
@@ -32,9 +32,10 @@ public sealed class ModbusTagConfigModel
|
|||||||
|
|
||||||
/// <summary>
|
/// <summary>
|
||||||
/// The address in the parser grammar (<c>40001:F:CDAB</c>, DL205 <c>V2000</c>, MELSEC <c>D100</c>) when
|
/// The address in the parser grammar (<c>40001:F:CDAB</c>, DL205 <c>V2000</c>, MELSEC <c>D100</c>) when
|
||||||
/// the tag was authored that way; <c>null</c> for a tag authored by region + numeric address. When
|
/// the tag was authored that way; <c>null</c> for a tag authored by region + numeric address. The
|
||||||
/// present the driver re-resolves it with ITS family at runtime, so it is authoritative — editing any
|
/// persisted resolved fields are what the driver reads (the string is only resolved by the driver for a
|
||||||
/// resolved field by hand clears it (<see cref="ClearAddressString"/>).
|
/// string-only blob), so editing any resolved field by hand clears it (<see cref="ClearAddressString"/>)
|
||||||
|
/// to keep the two from disagreeing.
|
||||||
/// </summary>
|
/// </summary>
|
||||||
public string? AddressString { get; set; }
|
public string? AddressString { get; set; }
|
||||||
|
|
||||||
@@ -130,9 +131,12 @@ public sealed class ModbusTagConfigModel
|
|||||||
_source = json ?? "",
|
_source = json ?? "",
|
||||||
Region = TagConfigJson.GetEnum(o, "region", ModbusRegion.HoldingRegisters),
|
Region = TagConfigJson.GetEnum(o, "region", ModbusRegion.HoldingRegisters),
|
||||||
Address = TagConfigJson.GetInt(o, "address"),
|
Address = TagConfigJson.GetInt(o, "address"),
|
||||||
// Absent dataType defaults per region, exactly as the driver's factory does (Bool for a bit region).
|
// Absent dataType defaults per region, exactly as the driver's factory does (Bool for a bit region),
|
||||||
DataType = TagConfigJson.GetEnum(o, "dataType",
|
// and a bit region shows Bool whatever was persisted — the driver coerces a legacy coil/DI
|
||||||
ModbusTagDefinitionFactory.DefaultDataType(TagConfigJson.GetEnum(o, "region", ModbusRegion.HoldingRegisters))),
|
// "dataType":"Int16" (what the pre-#741 editor saved) to Bool, so the editor shows what is polled.
|
||||||
|
DataType = TagConfigJson.GetEnum(o, "region", ModbusRegion.HoldingRegisters) is ModbusRegion.Coils or ModbusRegion.DiscreteInputs
|
||||||
|
? ModbusDataType.Bool
|
||||||
|
: TagConfigJson.GetEnum(o, "dataType", ModbusDataType.Int16),
|
||||||
ByteOrder = TagConfigJson.GetEnum(o, "byteOrder", ModbusByteOrder.BigEndian),
|
ByteOrder = TagConfigJson.GetEnum(o, "byteOrder", ModbusByteOrder.BigEndian),
|
||||||
BitIndex = TagConfigJson.GetInt(o, "bitIndex"),
|
BitIndex = TagConfigJson.GetInt(o, "bitIndex"),
|
||||||
StringLength = TagConfigJson.GetInt(o, "stringLength"),
|
StringLength = TagConfigJson.GetInt(o, "stringLength"),
|
||||||
|
|||||||
+7
-7
@@ -87,26 +87,26 @@ public sealed class CommsRecoveryTests(ModbusSimulatorFixture sim)
|
|||||||
}
|
}
|
||||||
|
|
||||||
/// <summary>
|
/// <summary>
|
||||||
/// U1 (DisableFC23 wired): a multi-register write on the default (FC23 write + read-back) path
|
/// U1 (FC23 opt-in, DisableFC23 kill-switch): a multi-register write on the opted-in FC23 write + read-back path
|
||||||
/// round-trips against the real server — whether it implements FC23 or answers Illegal Function and
|
/// round-trips against the real server — whether it implements FC23 or answers Illegal Function and
|
||||||
/// is moved to FC16 — and so does the forced-FC16 path. Uses the standard profile's scratch HR[200..209].
|
/// is moved to FC16 — and so does the default FC16 path. Uses the standard profile's scratch HR[200..209].
|
||||||
/// </summary>
|
/// </summary>
|
||||||
[Theory]
|
[Theory]
|
||||||
[InlineData(false, 200)]
|
[InlineData(true, 200)]
|
||||||
[InlineData(true, 202)]
|
[InlineData(false, 202)]
|
||||||
public async Task Multi_register_write_round_trips_with_and_without_FC23(bool disableFc23, int address)
|
public async Task Multi_register_write_round_trips_with_and_without_FC23(bool useFc23, int address)
|
||||||
{
|
{
|
||||||
SkipUnlessStandardLive();
|
SkipUnlessStandardLive();
|
||||||
var tag = new ModbusTagDefinition("F", ModbusRegion.HoldingRegisters, (ushort)address, ModbusDataType.Float32);
|
var tag = new ModbusTagDefinition("F", ModbusRegion.HoldingRegisters, (ushort)address, ModbusDataType.Float32);
|
||||||
var opts = new ModbusDriverOptions
|
var opts = new ModbusDriverOptions
|
||||||
{
|
{
|
||||||
Host = sim.Host, Port = sim.Port, UnitId = 1, Timeout = TimeSpan.FromSeconds(2), DisableFC23 = disableFc23,
|
Host = sim.Host, Port = sim.Port, UnitId = 1, Timeout = TimeSpan.FromSeconds(2), UseFC23ForMultiRegisterWrites = useFc23,
|
||||||
RawTags = ModbusRawTags.Entries([tag]), Probe = new ModbusProbeOptions { Enabled = false },
|
RawTags = ModbusRawTags.Entries([tag]), Probe = new ModbusProbeOptions { Enabled = false },
|
||||||
};
|
};
|
||||||
await using var driver = new ModbusDriver(opts, "modbus-u1");
|
await using var driver = new ModbusDriver(opts, "modbus-u1");
|
||||||
await driver.InitializeAsync("{}", TestContext.Current.CancellationToken);
|
await driver.InitializeAsync("{}", TestContext.Current.CancellationToken);
|
||||||
|
|
||||||
var value = disableFc23 ? 12.25f : 6.5f;
|
var value = useFc23 ? 6.5f : 12.25f;
|
||||||
for (var i = 0; i < 2; i++) // second write exercises the latched path when the server lacks FC23
|
for (var i = 0; i < 2; i++) // second write exercises the latched path when the server lacks FC23
|
||||||
{
|
{
|
||||||
var w = await driver.WriteAsync([new WriteRequest("F", value + i)], TestContext.Current.CancellationToken);
|
var w = await driver.WriteAsync([new WriteRequest("F", value + i)], TestContext.Current.CancellationToken);
|
||||||
|
|||||||
@@ -49,6 +49,32 @@ public sealed class ModbusCoalescingDefaultsTests
|
|||||||
r.Select(s => (short)s.Value!).ShouldBe(Enumerable.Range(1, 10).Select(i => (short)i));
|
r.Select(s => (short)s.Value!).ShouldBe(Enumerable.Range(1, 10).Select(i => (short)i));
|
||||||
}
|
}
|
||||||
|
|
||||||
|
/// <summary>
|
||||||
|
/// Fix round 1 (coordinator ruling 2): an explicitly authored maxReadGap 0 — what the pre-#741 form
|
||||||
|
/// persisted on every driver — keeps its old meaning, NO coalescing; the gap-8 default applies only to an
|
||||||
|
/// absent key (positive control).
|
||||||
|
/// </summary>
|
||||||
|
[Theory]
|
||||||
|
[InlineData("""{"host":"h","maxReadGap":0,"disableFC23":false}""", 2)]
|
||||||
|
[InlineData("""{"host":"h"}""", 1)]
|
||||||
|
public async Task A_persisted_maxReadGap_0_keeps_coalescing_off(string legacyConfig, int expectedReads)
|
||||||
|
{
|
||||||
|
var parsed = ModbusDriverFactoryExtensions.ParseOptions("m1", legacyConfig);
|
||||||
|
var tags = new[]
|
||||||
|
{
|
||||||
|
new ModbusTagDefinition("A", ModbusRegion.HoldingRegisters, 100, ModbusDataType.Int16),
|
||||||
|
new ModbusTagDefinition("B", ModbusRegion.HoldingRegisters, 101, ModbusDataType.Int16),
|
||||||
|
};
|
||||||
|
var (drv, t) = await StartAsync(new ModbusDriverOptions
|
||||||
|
{
|
||||||
|
Host = "f", MaxReadGap = parsed.MaxReadGap, DisableReadCoalescing = parsed.DisableReadCoalescing,
|
||||||
|
RawTags = ModbusRawTags.Entries(tags), Probe = new ModbusProbeOptions { Enabled = false },
|
||||||
|
});
|
||||||
|
await using var _ = drv;
|
||||||
|
await drv.ReadAsync(["A", "B"], TestContext.Current.CancellationToken);
|
||||||
|
t.Requests(0x03).Count.ShouldBe(expectedReads);
|
||||||
|
}
|
||||||
|
|
||||||
[Fact]
|
[Fact]
|
||||||
public async Task DisableReadCoalescing_reads_every_tag_alone()
|
public async Task DisableReadCoalescing_reads_every_tag_alone()
|
||||||
{
|
{
|
||||||
|
|||||||
@@ -42,9 +42,9 @@ public sealed class ModbusCoalescingTests
|
|||||||
public ValueTask DisposeAsync() => ValueTask.CompletedTask;
|
public ValueTask DisposeAsync() => ValueTask.CompletedTask;
|
||||||
}
|
}
|
||||||
|
|
||||||
/// <summary>MaxReadGap=0 coalesces only adjacent tags: a one-register hole splits the read.</summary>
|
/// <summary>MaxReadGap=0 means no coalescing (its historical meaning, kept for persisted configs).</summary>
|
||||||
[Fact]
|
[Fact]
|
||||||
public async Task MaxReadGap_Zero_Does_Not_Bridge_A_Gap()
|
public async Task MaxReadGap_Zero_Means_No_Coalescing()
|
||||||
{
|
{
|
||||||
var fake = new CountingTransport();
|
var fake = new CountingTransport();
|
||||||
var t1 = new ModbusTagDefinition("T1", ModbusRegion.HoldingRegisters, 100, ModbusDataType.Int16);
|
var t1 = new ModbusTagDefinition("T1", ModbusRegion.HoldingRegisters, 100, ModbusDataType.Int16);
|
||||||
@@ -56,7 +56,7 @@ public sealed class ModbusCoalescingTests
|
|||||||
|
|
||||||
await drv.ReadAsync(["T1", "T2"], CancellationToken.None);
|
await drv.ReadAsync(["T1", "T2"], CancellationToken.None);
|
||||||
|
|
||||||
// A one-register gap with MaxReadGap=0: expect 2 separate FC03 reads.
|
// MaxReadGap=0 is coalescing OFF: expect 2 separate FC03 reads.
|
||||||
var fc03Reads = fake.Reads.Where(r => r.Fc == 0x03).ToList();
|
var fc03Reads = fake.Reads.Where(r => r.Fc == 0x03).ToList();
|
||||||
fc03Reads.Count.ShouldBe(2);
|
fc03Reads.Count.ShouldBe(2);
|
||||||
}
|
}
|
||||||
|
|||||||
@@ -39,12 +39,12 @@ public sealed class ModbusFamilyWiringTests
|
|||||||
}
|
}
|
||||||
|
|
||||||
[Fact]
|
[Fact]
|
||||||
public void The_address_string_carries_type_order_and_count_and_keeps_the_other_keys()
|
public void A_string_only_blob_carries_type_order_and_count_and_keeps_the_other_keys()
|
||||||
{
|
{
|
||||||
ModbusTagDefinitionFactory.FromTagConfig(
|
ModbusTagDefinitionFactory.FromTagConfig(
|
||||||
"""{"addressString":"40011:F:CDAB:4","writable":false,"unitId":3,"region":"Coils","address":9}""",
|
"""{"addressString":"40011:F:CDAB:4","writable":false,"unitId":3}""",
|
||||||
"T", ModbusFamily.Generic, MelsecFamily.Q_L_iQR, out var def).ShouldBeTrue();
|
"T", ModbusFamily.Generic, MelsecFamily.Q_L_iQR, out var def).ShouldBeTrue();
|
||||||
def.Region.ShouldBe(ModbusRegion.HoldingRegisters, "addressString is authoritative over stale resolved keys");
|
def.Region.ShouldBe(ModbusRegion.HoldingRegisters);
|
||||||
def.Address.ShouldBe((ushort)10);
|
def.Address.ShouldBe((ushort)10);
|
||||||
def.DataType.ShouldBe(ModbusDataType.Float32);
|
def.DataType.ShouldBe(ModbusDataType.Float32);
|
||||||
def.ByteOrder.ShouldBe(ModbusByteOrder.WordSwap);
|
def.ByteOrder.ShouldBe(ModbusByteOrder.WordSwap);
|
||||||
@@ -53,6 +53,22 @@ public sealed class ModbusFamilyWiringTests
|
|||||||
def.UnitId.ShouldBe((byte)3);
|
def.UnitId.ShouldBe((byte)3);
|
||||||
}
|
}
|
||||||
|
|
||||||
|
/// <summary>
|
||||||
|
/// Fix round 1 (review m2): persisted region/address are authoritative over an addressString, so a
|
||||||
|
/// later Family / MelsecSubFamily change can never silently remap a live tag the editor resolved.
|
||||||
|
/// </summary>
|
||||||
|
[Fact]
|
||||||
|
public void Persisted_resolved_keys_win_over_the_address_string_so_a_family_change_cannot_remap()
|
||||||
|
{
|
||||||
|
// The editor resolved D100 under MELSEC and persisted HR 100; the driver is later switched to DL205.
|
||||||
|
const string json = """{"addressString":"D100","region":"HoldingRegisters","address":100,"dataType":"Int16"}""";
|
||||||
|
foreach (var family in new[] { ModbusFamily.MELSEC, ModbusFamily.DL205, ModbusFamily.Generic })
|
||||||
|
{
|
||||||
|
ModbusTagDefinitionFactory.FromTagConfig(json, "T", family, MelsecFamily.Q_L_iQR, out var def).ShouldBeTrue();
|
||||||
|
def.Address.ShouldBe((ushort)100, $"family {family}");
|
||||||
|
}
|
||||||
|
}
|
||||||
|
|
||||||
[Fact]
|
[Fact]
|
||||||
public void An_unparseable_address_string_rejects_the_tag_and_the_deploy_gate_says_why()
|
public void An_unparseable_address_string_rejects_the_tag_and_the_deploy_gate_says_why()
|
||||||
{
|
{
|
||||||
@@ -83,31 +99,52 @@ public sealed class ModbusFamilyWiringTests
|
|||||||
[Fact]
|
[Fact]
|
||||||
public void Family_and_MelsecSubFamily_parse_from_the_driver_config()
|
public void Family_and_MelsecSubFamily_parse_from_the_driver_config()
|
||||||
{
|
{
|
||||||
var o = ModbusDriverFactoryExtensions.ParseOptions("m1", """{"host":"h","family":"MELSEC","melsecSubFamily":"F_iQF","disableFC23":true}""");
|
var o = ModbusDriverFactoryExtensions.ParseOptions("m1",
|
||||||
|
"""{"host":"h","family":"MELSEC","melsecSubFamily":"F_iQF","disableFC23":true,"useFC23ForMultiRegisterWrites":true}""");
|
||||||
o.Family.ShouldBe(ModbusFamily.MELSEC);
|
o.Family.ShouldBe(ModbusFamily.MELSEC);
|
||||||
o.MelsecSubFamily.ShouldBe(MelsecFamily.F_iQF);
|
o.MelsecSubFamily.ShouldBe(MelsecFamily.F_iQF);
|
||||||
o.DisableFC23.ShouldBeTrue();
|
o.DisableFC23.ShouldBeTrue();
|
||||||
|
o.UseFC23ForMultiRegisterWrites.ShouldBeTrue();
|
||||||
}
|
}
|
||||||
|
|
||||||
// ---------------- DisableFC23 gates the FC23 multi-register write ----------------
|
// ---------------- FC23 is OPT-IN; DisableFC23 is the kill-switch ----------------
|
||||||
|
|
||||||
private static async Task<(ModbusDriver, ScriptedTransport)> StartWriteAsync(bool disableFc23)
|
private static async Task<(ModbusDriver, ScriptedTransport)> StartWriteAsync(string driverConfigJson)
|
||||||
{
|
{
|
||||||
var t = new ScriptedTransport();
|
var t = new ScriptedTransport();
|
||||||
var opts = new ModbusDriverOptions
|
var opts = ModbusDriverFactoryExtensions.ParseOptions("m1", driverConfigJson) is var parsed
|
||||||
{
|
? new ModbusDriverOptions
|
||||||
Host = "f", DisableFC23 = disableFc23, Probe = new ModbusProbeOptions { Enabled = false },
|
{
|
||||||
RawTags = ModbusRawTags.Entries([new ModbusTagDefinition("F", ModbusRegion.HoldingRegisters, 20, ModbusDataType.Float32)]),
|
Host = "f", DisableFC23 = parsed.DisableFC23,
|
||||||
};
|
UseFC23ForMultiRegisterWrites = parsed.UseFC23ForMultiRegisterWrites,
|
||||||
|
Probe = new ModbusProbeOptions { Enabled = false },
|
||||||
|
RawTags = ModbusRawTags.Entries([new ModbusTagDefinition("F", ModbusRegion.HoldingRegisters, 20, ModbusDataType.Float32)]),
|
||||||
|
}
|
||||||
|
: null!;
|
||||||
var drv = new ModbusDriver(opts, "m1", _ => t);
|
var drv = new ModbusDriver(opts, "m1", _ => t);
|
||||||
await drv.InitializeAsync("{}", TestContext.Current.CancellationToken);
|
await drv.InitializeAsync("{}", TestContext.Current.CancellationToken);
|
||||||
return (drv, t);
|
return (drv, t);
|
||||||
}
|
}
|
||||||
|
|
||||||
[Fact]
|
/// <summary>
|
||||||
public async Task Multi_register_writes_use_FC23_write_and_read_back_by_default()
|
/// Fix round 1 (coordinator ruling 1): a config without the opt-in key keeps the FC16 wire — including the
|
||||||
|
/// legacy shape every form-saved config carries ("disableFC23": false).
|
||||||
|
/// </summary>
|
||||||
|
[Theory]
|
||||||
|
[InlineData("""{"host":"h"}""")]
|
||||||
|
[InlineData("""{"host":"h","disableFC23":false,"maxReadGap":0,"useFC15ForSingleCoilWrites":false}""")]
|
||||||
|
public async Task Without_the_opt_in_multi_register_writes_stay_on_FC16(string legacyConfig)
|
||||||
{
|
{
|
||||||
var (drv, t) = await StartWriteAsync(disableFc23: false);
|
var (drv, t) = await StartWriteAsync(legacyConfig);
|
||||||
|
await using var _ = drv;
|
||||||
|
(await drv.WriteAsync([new WriteRequest("F", 1.5f)], TestContext.Current.CancellationToken))[0].StatusCode.ShouldBe(0u);
|
||||||
|
t.Sent.Select(s => s.Pdu[0]).ShouldBe([(byte)0x10]);
|
||||||
|
}
|
||||||
|
|
||||||
|
[Fact]
|
||||||
|
public async Task Opted_in_multi_register_writes_use_FC23_write_and_read_back()
|
||||||
|
{
|
||||||
|
var (drv, t) = await StartWriteAsync("""{"host":"h","useFC23ForMultiRegisterWrites":true}""");
|
||||||
await using var _ = drv;
|
await using var _ = drv;
|
||||||
var w = await drv.WriteAsync([new WriteRequest("F", 1.5f)], TestContext.Current.CancellationToken);
|
var w = await drv.WriteAsync([new WriteRequest("F", 1.5f)], TestContext.Current.CancellationToken);
|
||||||
w[0].StatusCode.ShouldBe(0u);
|
w[0].StatusCode.ShouldBe(0u);
|
||||||
@@ -116,18 +153,18 @@ public sealed class ModbusFamilyWiringTests
|
|||||||
}
|
}
|
||||||
|
|
||||||
[Fact]
|
[Fact]
|
||||||
public async Task DisableFC23_writes_with_FC16()
|
public async Task DisableFC23_overrides_the_opt_in()
|
||||||
{
|
{
|
||||||
var (drv, t) = await StartWriteAsync(disableFc23: true);
|
var (drv, t) = await StartWriteAsync("""{"host":"h","useFC23ForMultiRegisterWrites":true,"disableFC23":true}""");
|
||||||
await using var _ = drv;
|
await using var _ = drv;
|
||||||
(await drv.WriteAsync([new WriteRequest("F", 1.5f)], TestContext.Current.CancellationToken))[0].StatusCode.ShouldBe(0u);
|
(await drv.WriteAsync([new WriteRequest("F", 1.5f)], TestContext.Current.CancellationToken))[0].StatusCode.ShouldBe(0u);
|
||||||
t.Sent.Select(s => s.Pdu[0]).ShouldBe([(byte)0x10]);
|
t.Sent.Select(s => s.Pdu[0]).ShouldBe([(byte)0x10]);
|
||||||
}
|
}
|
||||||
|
|
||||||
[Fact]
|
[Fact]
|
||||||
public async Task A_device_without_FC23_falls_back_to_FC16_once_and_stays_on_it()
|
public async Task An_opted_in_device_without_FC23_falls_back_to_FC16_once_and_stays_on_it()
|
||||||
{
|
{
|
||||||
var (drv, t) = await StartWriteAsync(disableFc23: false);
|
var (drv, t) = await StartWriteAsync("""{"host":"h","useFC23ForMultiRegisterWrites":true}""");
|
||||||
await using var _ = drv;
|
await using var _ = drv;
|
||||||
t.Handler = (_, pdu, _) => pdu[0] == 0x17
|
t.Handler = (_, pdu, _) => pdu[0] == 0x17
|
||||||
? Task.FromException<byte[]>(new ModbusException(0x17, 0x01, "illegal function"))
|
? Task.FromException<byte[]>(new ModbusException(0x17, 0x01, "illegal function"))
|
||||||
|
|||||||
@@ -156,8 +156,10 @@ public sealed class ModbusHealthContractTests
|
|||||||
// ---------------- H7: write status mapping + write-side health ----------------
|
// ---------------- H7: write status mapping + write-side health ----------------
|
||||||
|
|
||||||
[Fact]
|
[Fact]
|
||||||
public async Task Write_transport_failure_is_BadCommunicationError_and_degrades_the_write_side()
|
public async Task Write_transport_failure_is_BadCommunicationError_and_a_good_read_clears_it()
|
||||||
{
|
{
|
||||||
|
// Fix round 1 (review Important #3): ONE health writer for reads and writes. A single write blip used
|
||||||
|
// to latch Degraded until the next good WRITE — forever, in a read-mostly plant.
|
||||||
var (drv, t) = await StartAsync(Opts(Hr("A", 10)));
|
var (drv, t) = await StartAsync(Opts(Hr("A", 10)));
|
||||||
await using var _ = drv;
|
await using var _ = drv;
|
||||||
t.Handler = (_, pdu, _) => pdu[0] == 0x06 ? Task.FromException<byte[]>(new IOException("dropped")) : null;
|
t.Handler = (_, pdu, _) => pdu[0] == 0x06 ? Task.FromException<byte[]>(new IOException("dropped")) : null;
|
||||||
@@ -166,16 +168,49 @@ public sealed class ModbusHealthContractTests
|
|||||||
w[0].StatusCode.ShouldBe(BadCommunicationError);
|
w[0].StatusCode.ShouldBe(BadCommunicationError);
|
||||||
drv.GetHealth().State.ShouldBe(DriverState.Degraded);
|
drv.GetHealth().State.ShouldBe(DriverState.Degraded);
|
||||||
|
|
||||||
// A good READ does not clear a write-side fault...
|
|
||||||
(await drv.ReadAsync(["A"], TestContext.Current.CancellationToken))[0].StatusCode.ShouldBe(Good);
|
(await drv.ReadAsync(["A"], TestContext.Current.CancellationToken))[0].StatusCode.ShouldBe(Good);
|
||||||
|
drv.GetHealth().State.ShouldBe(DriverState.Healthy, "a good read proves the shared transport answered");
|
||||||
|
}
|
||||||
|
|
||||||
|
[Fact]
|
||||||
|
public async Task A_good_write_clears_a_read_side_comms_fault()
|
||||||
|
{
|
||||||
|
var (drv, t) = await StartAsync(Opts(Hr("A", 10)));
|
||||||
|
await using var _ = drv;
|
||||||
|
t.Handler = (_, pdu, _) => pdu[0] == 0x03 ? Task.FromException<byte[]>(new IOException("dropped")) : null;
|
||||||
|
await drv.ReadAsync(["A"], TestContext.Current.CancellationToken);
|
||||||
drv.GetHealth().State.ShouldBe(DriverState.Degraded);
|
drv.GetHealth().State.ShouldBe(DriverState.Degraded);
|
||||||
|
|
||||||
// ...a good WRITE does.
|
|
||||||
t.Handler = null;
|
|
||||||
(await drv.WriteAsync([new WriteRequest("A", (short)2)], TestContext.Current.CancellationToken))[0].StatusCode.ShouldBe(Good);
|
(await drv.WriteAsync([new WriteRequest("A", (short)2)], TestContext.Current.CancellationToken))[0].StatusCode.ShouldBe(Good);
|
||||||
drv.GetHealth().State.ShouldBe(DriverState.Healthy);
|
drv.GetHealth().State.ShouldBe(DriverState.Healthy);
|
||||||
}
|
}
|
||||||
|
|
||||||
|
[Fact]
|
||||||
|
public async Task A_malformed_reply_does_not_fail_the_rest_of_the_unit_fast()
|
||||||
|
{
|
||||||
|
// Review m3: a byte-count mismatch is a reply that ARRIVED — only a timeout / desync / IO fails the unit fast.
|
||||||
|
var (drv, t) = await StartAsync(Opts(Hr("Bad", 10), Hr("Fine", 50)) is var o
|
||||||
|
? new ModbusDriverOptions { Host = o.Host, RawTags = o.RawTags, Probe = o.Probe, DisableReadCoalescing = true }
|
||||||
|
: null!);
|
||||||
|
await using var _ = drv;
|
||||||
|
t.Bank.HoldingRegisters[50] = 9;
|
||||||
|
t.Handler = (_, pdu, _) => Addr(pdu) == 10 ? Task.FromResult(new byte[] { 0x03, 0x04, 0, 0 }) : null;
|
||||||
|
|
||||||
|
var r = await drv.ReadAsync(["Bad", "Fine"], TestContext.Current.CancellationToken);
|
||||||
|
r[0].StatusCode.ShouldBe(BadCommunicationError);
|
||||||
|
r[1].Value.ShouldBe((short)9, "the sibling on the same unit is still read");
|
||||||
|
}
|
||||||
|
|
||||||
|
[Fact]
|
||||||
|
public async Task DisposeAsync_leaves_health_Unknown()
|
||||||
|
{
|
||||||
|
// Review m1: Dispose bumps the generation (dropping a concurrent shutdown's write), so it must write its own.
|
||||||
|
var (drv, _) = await StartAsync(Opts(Hr("A", 10)));
|
||||||
|
drv.GetHealth().State.ShouldBe(DriverState.Healthy);
|
||||||
|
await drv.DisposeAsync();
|
||||||
|
drv.GetHealth().State.ShouldBe(DriverState.Unknown);
|
||||||
|
}
|
||||||
|
|
||||||
[Fact]
|
[Fact]
|
||||||
public async Task A_write_refusal_counts_as_answered_and_clears_a_write_side_fault()
|
public async Task A_write_refusal_counts_as_answered_and_clears_a_write_side_fault()
|
||||||
{
|
{
|
||||||
|
|||||||
+37
-4
@@ -14,14 +14,47 @@ namespace ZB.MOM.WW.OtOpcUa.Driver.Modbus.Tests;
|
|||||||
public sealed class ModbusRegionTypeValidationTests
|
public sealed class ModbusRegionTypeValidationTests
|
||||||
{
|
{
|
||||||
[Theory]
|
[Theory]
|
||||||
[InlineData("""{"region":"Coils","address":1,"dataType":"Int16"}""")]
|
|
||||||
[InlineData("""{"region":"DiscreteInputs","address":1,"dataType":"Float32"}""")]
|
|
||||||
[InlineData("""{"region":"HoldingRegisters","address":1,"dataType":"Bool"}""")]
|
[InlineData("""{"region":"HoldingRegisters","address":1,"dataType":"Bool"}""")]
|
||||||
[InlineData("""{"region":"InputRegisters","address":1,"dataType":"Bool"}""")]
|
[InlineData("""{"region":"InputRegisters","address":1,"dataType":"Bool"}""")]
|
||||||
public void Incompatible_region_and_type_is_rejected(string json)
|
public void A_register_region_with_Bool_is_rejected(string json)
|
||||||
{
|
{
|
||||||
|
// That pair never read (RegisterCount threw), so refusing it breaks nothing that worked.
|
||||||
ModbusTagDefinitionFactory.FromTagConfig(json, "T", out _).ShouldBeFalse();
|
ModbusTagDefinitionFactory.FromTagConfig(json, "T", out _).ShouldBeFalse();
|
||||||
ModbusTagDefinitionFactory.Inspect(json).ShouldContain(w => w.Contains("only") || w.Contains("register"));
|
ModbusTagDefinitionFactory.Inspect(json).ShouldContain(w => w.Contains("register"));
|
||||||
|
}
|
||||||
|
|
||||||
|
/// <summary>
|
||||||
|
/// Fix round 1 (review Important #2): the pre-#741 editor defaulted dataType to Int16 and persisted it for
|
||||||
|
/// coil / DI tags, and the old driver ignored it for bit regions — those tags worked and must keep loading.
|
||||||
|
/// A bit region with any type is coerced to Bool and draws no deploy warning (a warning can be promoted to
|
||||||
|
/// a blocking error by TagConfigValidationMode.Error, which would refuse an existing config).
|
||||||
|
/// </summary>
|
||||||
|
[Theory]
|
||||||
|
[InlineData("""{"region":"Coils","address":3,"dataType":"Int16","byteOrder":"BigEndian","bitIndex":0,"stringLength":0}""")]
|
||||||
|
[InlineData("""{"region":"DiscreteInputs","address":1,"dataType":"Float32"}""")]
|
||||||
|
public void A_legacy_bit_region_tag_with_a_register_type_still_loads_as_Bool(string legacyJson)
|
||||||
|
{
|
||||||
|
ModbusTagDefinitionFactory.FromTagConfig(legacyJson, "T", out var def).ShouldBeTrue();
|
||||||
|
def.DataType.ShouldBe(ModbusDataType.Bool);
|
||||||
|
ModbusTagDefinitionFactory.Inspect(legacyJson).ShouldBeEmpty();
|
||||||
|
}
|
||||||
|
|
||||||
|
[Fact]
|
||||||
|
public async Task A_legacy_Int16_coil_tag_reads_and_writes_the_coil()
|
||||||
|
{
|
||||||
|
var fake = new ModbusDriverTests.FakeTransport();
|
||||||
|
fake.Coils[3] = true;
|
||||||
|
var opts = new ModbusDriverOptions
|
||||||
|
{
|
||||||
|
Host = "f", Probe = new ModbusProbeOptions { Enabled = false },
|
||||||
|
RawTags = [new RawTagEntry("Run", """{"region":"Coils","address":3,"dataType":"Int16","byteOrder":"BigEndian","bitIndex":0,"stringLength":0}""", false)],
|
||||||
|
};
|
||||||
|
await using var drv = new ModbusDriver(opts, "m1", _ => fake);
|
||||||
|
await drv.InitializeAsync("{}", TestContext.Current.CancellationToken);
|
||||||
|
|
||||||
|
(await drv.ReadAsync(["Run"], TestContext.Current.CancellationToken))[0].Value.ShouldBe(true);
|
||||||
|
(await drv.WriteAsync([new WriteRequest("Run", false)], TestContext.Current.CancellationToken))[0].StatusCode.ShouldBe(0u);
|
||||||
|
fake.Coils[3].ShouldBeFalse();
|
||||||
}
|
}
|
||||||
|
|
||||||
[Theory]
|
[Theory]
|
||||||
|
|||||||
@@ -137,10 +137,24 @@ public sealed class ModbusTagConfigModelTests
|
|||||||
ModbusTagConfigModel.FromJson(m.ToJson()).Validate().ShouldBeNull();
|
ModbusTagConfigModel.FromJson(m.ToJson()).Validate().ShouldBeNull();
|
||||||
}
|
}
|
||||||
|
|
||||||
/// <summary>A Coils + Int16 blob (CSV / API) is refused at authoring, matching the driver.</summary>
|
/// <summary>A register region with Bool (CSV / API) is refused at authoring, matching the driver.</summary>
|
||||||
[Fact]
|
[Fact]
|
||||||
public void Validate_refuses_an_incompatible_region_and_type()
|
public void Validate_refuses_a_register_region_with_Bool()
|
||||||
=> ModbusTagConfigModel.FromJson("""{"region":"Coils","address":1,"dataType":"Int16"}""").Validate().ShouldNotBeNull();
|
=> ModbusTagConfigModel.FromJson("""{"region":"HoldingRegisters","address":1,"dataType":"Bool"}""").Validate().ShouldNotBeNull();
|
||||||
|
|
||||||
|
/// <summary>
|
||||||
|
/// Fix round 1: the exact blob the pre-#741 editor persisted for a coil (dataType defaulted to Int16)
|
||||||
|
/// still validates, loads as Bool (what the driver polls), and re-saves as Bool.
|
||||||
|
/// </summary>
|
||||||
|
[Fact]
|
||||||
|
public void A_legacy_Int16_coil_blob_validates_and_loads_as_Bool()
|
||||||
|
{
|
||||||
|
const string legacy = """{"region":"Coils","address":3,"dataType":"Int16","byteOrder":"BigEndian","bitIndex":0,"stringLength":0}""";
|
||||||
|
var m = ModbusTagConfigModel.FromJson(legacy);
|
||||||
|
m.Validate().ShouldBeNull();
|
||||||
|
m.DataType.ShouldBe(ModbusDataType.Bool);
|
||||||
|
m.ToJson().ShouldContain("\"dataType\":\"Bool\"");
|
||||||
|
}
|
||||||
|
|
||||||
/// <summary>Review 07 U1: the editor resolves an address string with the DRIVER's family and persists
|
/// <summary>Review 07 U1: the editor resolves an address string with the DRIVER's family and persists
|
||||||
/// both the string and the resolved fields; the driver re-resolves the string with its family.</summary>
|
/// both the string and the resolved fields; the driver re-resolves the string with its family.</summary>
|
||||||
|
|||||||
Reference in New Issue