fix(modbus): review r0 - FC23 opt-in, explicit maxReadGap 0 = off, legacy coil types load, one health writer
Coordinator rulings and Important findings from review r0: 1. FC23 is opt-in (new UseFC23ForMultiRegisterWrites, default false); a config without it - including the persisted "disableFC23": false every form-saved config carries - keeps the FC16 wire. DisableFC23 stays the hard kill-switch. 2. An explicit maxReadGap 0 means coalescing off again (its pre-lane meaning); the gap-8 default applies only to an absent key. 3. Coils/DiscreteInputs tags persisted with a register dataType (the old editor saved Int16) are coerced to Bool, never refused, with no deploy warning (a warning can be promoted to a blocking error). The editor loads them as Bool. Register region + Bool is still refused. 4. One comms-fault slot for reads and writes: a good read clears a write's transport fault and vice versa. Minors: Dispose writes its own Unknown health (m1); persisted region/address are authoritative over addressString so a Family change cannot remap a live tag (m2); a malformed-but-delivered reply no longer fails the unit fast (m3); a fresh socket published after a concurrent dispose is torn down (m4); the editor resets address text per tag (m5); master merged (m6); the FC23 latch log says re-init restores it (m7). Back-compat tests use the old persisted JSON shapes and fail without the fixes. Refs #741 Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
This commit is contained in:
@@ -103,6 +103,13 @@ public sealed class ModbusSocketLifecycle : IAsyncDisposable
|
||||
_stream = client.GetStream();
|
||||
_client = client;
|
||||
client = null; // ownership transferred
|
||||
if (Volatile.Read(ref _disposed) != 0)
|
||||
{
|
||||
// A DisposeAsync that ran between the check above and the publish has already torn down;
|
||||
// tear the fresh socket down ourselves so it is never stranded for the finalizer.
|
||||
await TearDownAsync().ConfigureAwait(false);
|
||||
throw new ObjectDisposedException(nameof(ModbusSocketLifecycle));
|
||||
}
|
||||
_lastSuccessUtc = DateTime.UtcNow;
|
||||
}
|
||||
catch (OperationCanceledException) when (!ct.IsCancellationRequested)
|
||||
|
||||
Reference in New Issue
Block a user