fix(twincat): review — a connect failure no longer burns the sum-chunk warning; doc precision
- ReadBucketAsync: the once-per-device "sum-read chunk failed" Warning fires only after a successful connect; a connect/backoff failure is the connect path's to report. TwinCATSumChunkWarningTests pins it (no warning across connect failures, exactly one across two later failing sum polls; red without the guard) plus a source guard that ReadGroupAsync builds its SumRead only via CreateSumRead. - Docs: diagnostics live-gated via the driver harness (/hosts not exercised); TC2 costs 8 reads on the first tick and after each reconnect, then <= 4; read counts attributed to the unit tests. Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
This commit is contained in:
@@ -1151,9 +1151,10 @@ host logger factory (wired in `DriverFactoryBootstrap`; the FOCAS and TwinCAT fa
|
||||
(`CheckNotification`) rides a batch; value-converted pairs (DInt over INT, Real over LREAL/DINT) read singly. Only overall
|
||||
ADS 1793/1794 latch the device to single reads; any other non-comms overall code (1792/1795/1797/1798...) reads that chunk singly for the poll without latching, with a once-per-device Warning; a comms failure neither.
|
||||
Opt-in `diagnosticsEnabled` (default off) puts ADS state/app/online-change/cycle/exec/`HeadroomMs` on the `/hosts`
|
||||
`IDriverDiagnostics` bag (up to 4 extra reads per device per probe tick; TC2 falls back to `.SYSTEMINFO` /
|
||||
`.SYSTEMTASKINFOARR[1]`). Live-gated read-only 2026-10-08 on Z35474 (TC3) + Z34834 (TC2, which answers sum
|
||||
commands); the gate found ⚠️ Beckhoff's `SumRead` ctor throws for a `List<>` of entities (only an array survives
|
||||
`IDriverDiagnostics` bag (≤ 4 extra reads per device per probe tick once settled; TC2 falls back to `.SYSTEMINFO` /
|
||||
`.SYSTEMTASKINFOARR[1]`, costing 8 on the first tick and after each reconnect). Live-gated read-only 2026-10-08 on
|
||||
Z35474 (TC3) + Z34834 (TC2, which answers sum commands) via a harness driving `TwinCATDriver` — `/hosts` end-to-end
|
||||
not run (a stock host has no AMS router); the gate found ⚠️ Beckhoff's `SumRead` ctor throws for a `List<>` of entities (only an array survives
|
||||
its internal cast) — `AdsTwinCATClient.CreateSumRead` owns it. Flat browse stays (VirtualTree is a strict subset
|
||||
on TC3). Sum-write not ported.
|
||||
- **AbLegacy (#636):** `AbLegacyAddress` (in `AbLegacy.Contracts`) is family-aware: PLC-5 `I:`/`O:` indices are OCTAL
|
||||
|
||||
+10
-5
@@ -224,12 +224,16 @@ command is unverified, hence opt-in.
|
||||
|
||||
### `/hosts` diagnostics (`IDriverDiagnostics`, opt-in)
|
||||
|
||||
Behind `diagnosticsEnabled` (default **off** — not yet live-gated). The driver implements the optional
|
||||
Behind `diagnosticsEnabled` (default **off**). Live-gated read-only 2026-10-08 on Z35474 (TC3) and Z34834 (TC2) by
|
||||
driving `TwinCATDriver` from a scratch harness with an in-process AMS router; the `/hosts` page end-to-end was
|
||||
**not** exercised (a stock host has no AMS router). The driver implements the optional
|
||||
`IDriverDiagnostics` bag (the S7 `NegotiatedPduSize` precedent, #640), deliberately not synthetic raw tags.
|
||||
When enabled, after each healthy probe tick **and after the host-state transition** it reads up to four
|
||||
`TwinCAT_SystemInfoVarList` symbols per device — `_AppInfo.AppName`, `_AppInfo.OnlineChangeCnt`,
|
||||
`_TaskInfo[1].CycleTime`, `_TaskInfo[1].LastExecTime` (100 ns ticks) — so up to **4 extra read requests per
|
||||
device per probe interval** (default 5 s). The ADS state is the one `ProbeAsync` already read; no second
|
||||
`_TaskInfo[1].CycleTime`, `_TaskInfo[1].LastExecTime` (100 ns ticks) — so at most **4 extra read requests per
|
||||
device per probe interval** (default 5 s) once settled. On **TwinCAT 2** (fallback below) the first tick, and the
|
||||
first tick after every reconnect, costs **8** (the four TC3 names answer "not found", then the four TC2 names);
|
||||
after that ≤ 4. The ADS state is the one `ProbeAsync` already read; no second
|
||||
ReadState. One device: flat keys `TwinCAT.AdsState`, `.AppName`, `.OnlineChangeCnt`, `.CycleTimeMs`,
|
||||
`.LastExecTimeMs`, `.HeadroomMs` (cycle − last exec; negative = the task overran; this is spare time, not
|
||||
jitter). Several devices: one line per device, `TwinCAT.<DeviceName or host>` =
|
||||
@@ -239,8 +243,9 @@ best-effort: a runtime that does not export one keeps the others, and a symbol a
|
||||
found" is not re-asked until a new client is installed (reconnect). **TwinCAT 2** has no
|
||||
`TwinCAT_SystemInfoVarList`; once a TC3 name answers "not found" the driver reads the TC2 globals instead —
|
||||
`.SYSTEMINFO.PROJECTNAME` (AppName), `.SYSTEMINFO.ONLINECHANGECOUNT` (UINT), `.SYSTEMTASKINFOARR[1].CYCLETIME` /
|
||||
`.LASTEXECTIME` (same 100 ns units). Live on TC2 2.11: 8 reads on the first tick, 4 after; a TC3 target never
|
||||
reads the TC2 names.
|
||||
`.LASTEXECTIME` (same 100 ns units). The read counts — 8 on the first tick and after each reconnect, 4 after, and
|
||||
none of the TC2 names on a TC3 target — are pinned by `TwinCATDiagnosticsTests`; the live run proved the values
|
||||
(all six keys on TC2 2.11), not the counts.
|
||||
|
||||
## Capability surface
|
||||
|
||||
|
||||
@@ -386,9 +386,13 @@ public sealed class TwinCATDriver : IDriver, IReadable, IWritable, ITagDiscovery
|
||||
continue;
|
||||
}
|
||||
|
||||
// Set once the connect succeeded: a connect / backoff failure is the connect path's to report (it
|
||||
// logs its own Warning) and must not consume the once-per-device sum-chunk-failure Warning below.
|
||||
var connected = false;
|
||||
try
|
||||
{
|
||||
var client = await EnsureConnectedAsync(device, cancellationToken).ConfigureAwait(false);
|
||||
connected = true;
|
||||
var items = new TwinCATBulkReadItem[chunk.Count];
|
||||
for (var k = 0; k < chunk.Count; k++)
|
||||
items[k] = new TwinCATBulkReadItem(chunk[k].SymbolName, chunk[k].Def.DataType, chunk[k].BitIndex, chunk[k].Def.ArrayLength);
|
||||
@@ -429,7 +433,7 @@ public sealed class TwinCATDriver : IDriver, IReadable, IWritable, ITagDiscovery
|
||||
_health = new DriverHealth(DriverState.Degraded, _health.LastSuccessfulRead, ex.Message);
|
||||
// Once per device: the health message is overwritten by the next good read in the same poll, so
|
||||
// without this a sum-read path failing on every poll left no trace (hw2 live gate, 2026-10-08).
|
||||
if (!device.SumChunkFailureWarned)
|
||||
if (connected && !device.SumChunkFailureWarned)
|
||||
{
|
||||
device.SumChunkFailureWarned = true;
|
||||
_logger.LogWarning(ex,
|
||||
|
||||
@@ -0,0 +1,99 @@
|
||||
using System.Text.RegularExpressions;
|
||||
using Microsoft.Extensions.Logging;
|
||||
using Shouldly;
|
||||
using Xunit;
|
||||
using ZB.MOM.WW.OtOpcUa.Driver.TwinCAT;
|
||||
|
||||
namespace ZB.MOM.WW.OtOpcUa.Driver.TwinCAT.Tests;
|
||||
|
||||
/// <summary>
|
||||
/// hw2 review of the live-gate fix: the once-per-device "sum-read chunk failed" Warning exists to surface a
|
||||
/// sum-read path that fails on every poll (the gate's silent failure). A device that is merely unreachable must
|
||||
/// not consume it — the connect path reports that itself — or the later real defect is logged nowhere.
|
||||
/// </summary>
|
||||
[Trait("Category", "Unit")]
|
||||
public sealed class TwinCATSumChunkWarningTests
|
||||
{
|
||||
private const string Host = "ads://5.23.91.23.1.1:851";
|
||||
private const string ChunkWarning = "an ADS sum-read chunk";
|
||||
|
||||
[Fact]
|
||||
public async Task A_connect_failure_does_not_burn_the_warning_and_a_later_real_chunk_failure_warns_once()
|
||||
{
|
||||
var connectFails = true;
|
||||
var factory = new FakeTwinCATClientFactory
|
||||
{
|
||||
Customise = () => new FakeTwinCATClient
|
||||
{
|
||||
ThrowOnConnect = connectFails,
|
||||
Exception = new InvalidOperationException("device down"),
|
||||
SumReadException = new InvalidOperationException("sum path broken"),
|
||||
},
|
||||
};
|
||||
var logger = new CapturingLogger();
|
||||
var drv = new TwinCATDriver(new TwinCATDriverOptions
|
||||
{
|
||||
Devices = [new TwinCATDeviceOptions(Host)],
|
||||
RawTags = TwinCATRawTags.Entries([
|
||||
new TwinCATTagDefinition("A", Host, "MAIN.A", TwinCATDataType.DInt),
|
||||
new TwinCATTagDefinition("B", Host, "MAIN.B", TwinCATDataType.DInt),
|
||||
]),
|
||||
Probe = new TwinCATProbeOptions { Enabled = false },
|
||||
UseSumRead = true,
|
||||
SumReadMaxItems = 10,
|
||||
}, "drv-warn", factory, logger);
|
||||
await drv.InitializeAsync("{}", CancellationToken.None);
|
||||
|
||||
// Unreachable: the connect attempt fails, then the backoff window rejects further attempts.
|
||||
for (var i = 0; i < 3; i++)
|
||||
(await drv.ReadAsync(["A", "B"], CancellationToken.None))
|
||||
.ShouldAllBe(s => s.StatusCode == TwinCATStatusMapper.BadCommunicationError);
|
||||
logger.Warnings.Count(w => w.Contains(ChunkWarning)).ShouldBe(0);
|
||||
|
||||
// Device comes back, but the sum path itself fails: wait out the 1 s connect backoff, then two polls.
|
||||
connectFails = false;
|
||||
var deadline = DateTime.UtcNow + TimeSpan.FromSeconds(5);
|
||||
while (!factory.Clients.Any(c => c.IsConnected) && DateTime.UtcNow < deadline)
|
||||
{
|
||||
await drv.ReadAsync(["A", "B"], CancellationToken.None);
|
||||
await Task.Delay(50);
|
||||
}
|
||||
factory.Clients.Any(c => c.IsConnected).ShouldBeTrue("the device must reconnect for the second half to mean anything");
|
||||
await drv.ReadAsync(["A", "B"], CancellationToken.None);
|
||||
await drv.ReadAsync(["A", "B"], CancellationToken.None);
|
||||
|
||||
logger.Warnings.Count(w => w.Contains(ChunkWarning)).ShouldBe(1);
|
||||
}
|
||||
|
||||
/// <summary>Source guard: the driver's only Beckhoff <c>SumRead</c> construction is inside
|
||||
/// <c>CreateSumRead</c>, so re-inlining a <c>List</c>-based construction in <c>ReadGroupAsync</c> goes red.</summary>
|
||||
[Fact]
|
||||
public void ReadGroupAsync_builds_its_sum_command_through_CreateSumRead_only()
|
||||
{
|
||||
var dir = new DirectoryInfo(AppContext.BaseDirectory);
|
||||
while (dir is not null && !File.Exists(Path.Combine(dir.FullName, "ZB.MOM.WW.OtOpcUa.slnx"))) dir = dir.Parent;
|
||||
dir.ShouldNotBeNull("repo root not found");
|
||||
var src = File.ReadAllText(Path.Combine(dir!.FullName,
|
||||
"src", "Drivers", "ZB.MOM.WW.OtOpcUa.Driver.TwinCAT", "AdsTwinCATClient.cs"));
|
||||
|
||||
Regex.Matches(src, @"new\s+SumRead\s*\(").Count.ShouldBe(1);
|
||||
var create = src.IndexOf("internal static SumRead CreateSumRead(", StringComparison.Ordinal);
|
||||
create.ShouldBeGreaterThan(0);
|
||||
var ctor = Regex.Match(src, @"new\s+SumRead\s*\(").Index;
|
||||
ctor.ShouldBeGreaterThan(create);
|
||||
src.IndexOf("private const uint SymbolValueByHandle", StringComparison.Ordinal).ShouldBeGreaterThan(ctor);
|
||||
Regex.IsMatch(src, @"await\s+CreateSumRead\(_client").ShouldBeTrue();
|
||||
}
|
||||
|
||||
private sealed class CapturingLogger : ILogger<TwinCATDriver>
|
||||
{
|
||||
public List<string> Warnings { get; } = [];
|
||||
public IDisposable? BeginScope<TState>(TState state) where TState : notnull => null;
|
||||
public bool IsEnabled(LogLevel logLevel) => true;
|
||||
public void Log<TState>(LogLevel logLevel, EventId eventId, TState state, Exception? exception,
|
||||
Func<TState, Exception?, string> formatter)
|
||||
{
|
||||
if (logLevel == LogLevel.Warning) lock (Warnings) Warnings.Add(formatter(state, exception));
|
||||
}
|
||||
}
|
||||
}
|
||||
Reference in New Issue