fix(runtime): comms loss marks raw + UNS value nodes BadNoCommunication, value retained (archreview 03/S15)
This commit is contained in:
@@ -1244,13 +1244,28 @@ public sealed class DriverHostActor : ReceiveActor, IWithTimers, IWithUnboundedS
|
||||
/// the source had died. <see cref="FanCommsLossToDependencyMux"/> closes that by pushing a
|
||||
/// synthetic Bad for every value ref the driver owns.
|
||||
/// </para>
|
||||
/// <para>
|
||||
/// <b>Archreview 03/S15 — and the EXTERNAL data plane, which the two layers above still left
|
||||
/// out.</b> Conditions and internal consumers learned of the outage; the driver's raw value
|
||||
/// variables and their UNS mirrors — what an OPC UA client actually subscribes to — did not, so
|
||||
/// they served the last value at <c>Good</c> for the whole outage.
|
||||
/// <see cref="FanCommsLossToValueNodes"/> closes that with one status-only batch that keeps each
|
||||
/// node's value and changes only its status. All three fan-outs run on the disconnect edge only;
|
||||
/// the reconnect edge writes nothing to values (recovery is the driver's own re-publish) and
|
||||
/// re-annotates conditions Good, which is a statement about the LINK, not about any tag's value.
|
||||
/// </para>
|
||||
/// </summary>
|
||||
private void OnDriverConnectivityChanged(DriverInstanceActor.ConnectivityChanged msg)
|
||||
{
|
||||
// #481: the mux fan-out is independent of the OPC UA sink — a node with scripted alarms but no
|
||||
// publish actor (the mux-only test/dev path) must still see comms loss. Done before the early
|
||||
// return for exactly that reason.
|
||||
if (!msg.Connected) FanCommsLossToDependencyMux(msg.DriverInstanceId);
|
||||
if (!msg.Connected)
|
||||
{
|
||||
FanCommsLossToDependencyMux(msg.DriverInstanceId);
|
||||
// 03/S15: and the EXTERNAL data plane, which #481 stopped one seam short of.
|
||||
FanCommsLossToValueNodes(msg.DriverInstanceId);
|
||||
}
|
||||
|
||||
if (_opcUaPublishActor is null) return;
|
||||
|
||||
@@ -1282,6 +1297,67 @@ public sealed class DriverHostActor : ReceiveActor, IWithTimers, IWithUnboundedS
|
||||
_localNode, msg.DriverInstanceId, msg.Connected ? "connected" : "disconnected", annotated, statusCode);
|
||||
}
|
||||
|
||||
/// <summary>
|
||||
/// Archreview <b>03/S15</b> — the value-node half of the comms-loss fan-out: stamp
|
||||
/// <see cref="OpcUaStatus.BadNoCommunication"/> on every raw NodeId <b>and</b> every referencing UNS
|
||||
/// NodeId the just-disconnected driver owns, as ONE status batch through the same publish actor the
|
||||
/// value fan-out uses.
|
||||
/// </summary>
|
||||
/// <remarks>
|
||||
/// <para>
|
||||
/// <b>Why it was missing.</b> #481 built the per-driver ref index and wired comms loss to the
|
||||
/// internal consumers (the mux) and to Part 9 conditions, and stopped one seam short of the
|
||||
/// external OPC UA data plane. A client subscribed to a value node therefore saw the last value
|
||||
/// at <b>Good</b> quality for the whole outage, for every driver whose failure shape is "the
|
||||
/// reader stops producing" rather than "publish a Bad snapshot per tag". (Modbus does the
|
||||
/// latter, quickly, which is why the gap looked smaller than it was — a coalesced-read throw, a
|
||||
/// dropped session on a push driver, or simply a driver whose last act was a Good publish all
|
||||
/// held Good indefinitely.)
|
||||
/// </para>
|
||||
/// <para>
|
||||
/// <b>Status-only, so the VALUE is retained.</b> This actor holds no value cache — v3's
|
||||
/// single-source design deliberately removed the independent buffer — so only the node can keep
|
||||
/// the last known value, which is what
|
||||
/// <see cref="OpcUa.OpcUaPublishActor.AttributeStatusBatchUpdate"/> exists for. A Bad node still
|
||||
/// carrying its last reading is OPC UA Part 8's convention and is what a SCADA consumer expects.
|
||||
/// </para>
|
||||
/// <para>
|
||||
/// <b>Nothing is written on reconnect.</b> Publishing Good would assert a quality this actor has
|
||||
/// not observed; recovery is the driver's own re-publish (see
|
||||
/// <see cref="FanCommsLossToDependencyMux"/>'s remark on the detach that makes the poll engine
|
||||
/// force-raise, and MQTT's initial push).
|
||||
/// </para>
|
||||
/// <para>
|
||||
/// Ungated by redundancy role, like the condition annotation: a Secondary keeps its address
|
||||
/// space honest for failover. Re-stamping an already-Bad node is harmless — the SDK's
|
||||
/// <c>StatusValue</c> trigger dedups an unchanged status at the monitored item.
|
||||
/// </para>
|
||||
/// </remarks>
|
||||
/// <param name="driverInstanceId">The driver child that just reported comms loss.</param>
|
||||
private void FanCommsLossToValueNodes(string driverInstanceId)
|
||||
{
|
||||
if (_opcUaPublishActor is null) return;
|
||||
if (!_valueRefsByDriver.TryGetValue(driverInstanceId, out var entries) || entries.Count == 0) return;
|
||||
|
||||
var ts = DateTime.UtcNow;
|
||||
var writes = new List<StatusWrite>(entries.Count);
|
||||
foreach (var (_, nodes) in entries)
|
||||
{
|
||||
foreach (var n in nodes)
|
||||
{
|
||||
writes.Add(new StatusWrite(n.NodeId, OpcUaStatus.BadNoCommunication, ts, n.Realm));
|
||||
}
|
||||
}
|
||||
|
||||
if (writes.Count == 0) return;
|
||||
|
||||
_opcUaPublishActor.Tell(new OpcUa.OpcUaPublishActor.AttributeStatusBatchUpdate(writes));
|
||||
|
||||
_log.Info(
|
||||
"DriverHost {Node}: driver {Driver} disconnected — {Count} value node(s) marked BadNoCommunication (value retained)",
|
||||
_localNode, driverInstanceId, writes.Count);
|
||||
}
|
||||
|
||||
/// <summary>
|
||||
/// #481 (Layer 4) — push a synthetic <see cref="OpcUaStatus.BadNoCommunication"/> into the dependency
|
||||
/// mux for every value ref the just-disconnected driver owns, so scripted alarms and virtual tags see
|
||||
|
||||