fix(runtime): comms loss marks raw + UNS value nodes BadNoCommunication, value retained (archreview 03/S15)
This commit is contained in:
@@ -678,3 +678,15 @@ test could only pass once the production change landed.
|
||||
- Metered `OpcUaSinkWrite kind:"status"` so a status annotation is separable from a value write on the
|
||||
same counter; the recording fake asserts **zero** value writes, since a handler falling through to the
|
||||
value path would null every node.
|
||||
|
||||
### T8 — `DriverHostActor.FanCommsLossToValueNodes`
|
||||
|
||||
- RED: `--filter "…DriverHostActorCommsLossValueNodesTests"` ⇒ **2 failed**, both
|
||||
`Timeout 00:00:15 while waiting for a message of type …AttributeStatusBatchUpdate` (the disconnect
|
||||
produced no value-node write at all — the finding, reproduced).
|
||||
- GREEN: 10 passed across the new suite + `DriverHostActorCommsLossTests` (mux half) +
|
||||
`DriverHostActorBatchFanOutTests`, all unchanged.
|
||||
- **Deviation (sequencing, not design):** the plan's snippet calls `TrackCommsLatchSet(...)` from inside
|
||||
this method, but that helper is T9's — calling it here would not compile. The call is added in T9,
|
||||
where the latch and its audit timer land together. R3-03 boundary respected: this is a new method plus
|
||||
one branch in `OnDriverConnectivityChanged`; `HandleRestartDriver` and the watchdog are untouched.
|
||||
|
||||
@@ -55,7 +55,7 @@
|
||||
{
|
||||
"id": "T8",
|
||||
"subject": "DriverHostActor.FanCommsLossToValueNodes: one BadNoCommunication status batch over raw + UNS nodes on ConnectivityChanged(false); nothing on reconnect (new method — R3-03 boundary)",
|
||||
"status": "pending",
|
||||
"status": "done",
|
||||
"blockedBy": [
|
||||
"T7"
|
||||
]
|
||||
|
||||
@@ -1244,13 +1244,28 @@ public sealed class DriverHostActor : ReceiveActor, IWithTimers, IWithUnboundedS
|
||||
/// the source had died. <see cref="FanCommsLossToDependencyMux"/> closes that by pushing a
|
||||
/// synthetic Bad for every value ref the driver owns.
|
||||
/// </para>
|
||||
/// <para>
|
||||
/// <b>Archreview 03/S15 — and the EXTERNAL data plane, which the two layers above still left
|
||||
/// out.</b> Conditions and internal consumers learned of the outage; the driver's raw value
|
||||
/// variables and their UNS mirrors — what an OPC UA client actually subscribes to — did not, so
|
||||
/// they served the last value at <c>Good</c> for the whole outage.
|
||||
/// <see cref="FanCommsLossToValueNodes"/> closes that with one status-only batch that keeps each
|
||||
/// node's value and changes only its status. All three fan-outs run on the disconnect edge only;
|
||||
/// the reconnect edge writes nothing to values (recovery is the driver's own re-publish) and
|
||||
/// re-annotates conditions Good, which is a statement about the LINK, not about any tag's value.
|
||||
/// </para>
|
||||
/// </summary>
|
||||
private void OnDriverConnectivityChanged(DriverInstanceActor.ConnectivityChanged msg)
|
||||
{
|
||||
// #481: the mux fan-out is independent of the OPC UA sink — a node with scripted alarms but no
|
||||
// publish actor (the mux-only test/dev path) must still see comms loss. Done before the early
|
||||
// return for exactly that reason.
|
||||
if (!msg.Connected) FanCommsLossToDependencyMux(msg.DriverInstanceId);
|
||||
if (!msg.Connected)
|
||||
{
|
||||
FanCommsLossToDependencyMux(msg.DriverInstanceId);
|
||||
// 03/S15: and the EXTERNAL data plane, which #481 stopped one seam short of.
|
||||
FanCommsLossToValueNodes(msg.DriverInstanceId);
|
||||
}
|
||||
|
||||
if (_opcUaPublishActor is null) return;
|
||||
|
||||
@@ -1282,6 +1297,67 @@ public sealed class DriverHostActor : ReceiveActor, IWithTimers, IWithUnboundedS
|
||||
_localNode, msg.DriverInstanceId, msg.Connected ? "connected" : "disconnected", annotated, statusCode);
|
||||
}
|
||||
|
||||
/// <summary>
|
||||
/// Archreview <b>03/S15</b> — the value-node half of the comms-loss fan-out: stamp
|
||||
/// <see cref="OpcUaStatus.BadNoCommunication"/> on every raw NodeId <b>and</b> every referencing UNS
|
||||
/// NodeId the just-disconnected driver owns, as ONE status batch through the same publish actor the
|
||||
/// value fan-out uses.
|
||||
/// </summary>
|
||||
/// <remarks>
|
||||
/// <para>
|
||||
/// <b>Why it was missing.</b> #481 built the per-driver ref index and wired comms loss to the
|
||||
/// internal consumers (the mux) and to Part 9 conditions, and stopped one seam short of the
|
||||
/// external OPC UA data plane. A client subscribed to a value node therefore saw the last value
|
||||
/// at <b>Good</b> quality for the whole outage, for every driver whose failure shape is "the
|
||||
/// reader stops producing" rather than "publish a Bad snapshot per tag". (Modbus does the
|
||||
/// latter, quickly, which is why the gap looked smaller than it was — a coalesced-read throw, a
|
||||
/// dropped session on a push driver, or simply a driver whose last act was a Good publish all
|
||||
/// held Good indefinitely.)
|
||||
/// </para>
|
||||
/// <para>
|
||||
/// <b>Status-only, so the VALUE is retained.</b> This actor holds no value cache — v3's
|
||||
/// single-source design deliberately removed the independent buffer — so only the node can keep
|
||||
/// the last known value, which is what
|
||||
/// <see cref="OpcUa.OpcUaPublishActor.AttributeStatusBatchUpdate"/> exists for. A Bad node still
|
||||
/// carrying its last reading is OPC UA Part 8's convention and is what a SCADA consumer expects.
|
||||
/// </para>
|
||||
/// <para>
|
||||
/// <b>Nothing is written on reconnect.</b> Publishing Good would assert a quality this actor has
|
||||
/// not observed; recovery is the driver's own re-publish (see
|
||||
/// <see cref="FanCommsLossToDependencyMux"/>'s remark on the detach that makes the poll engine
|
||||
/// force-raise, and MQTT's initial push).
|
||||
/// </para>
|
||||
/// <para>
|
||||
/// Ungated by redundancy role, like the condition annotation: a Secondary keeps its address
|
||||
/// space honest for failover. Re-stamping an already-Bad node is harmless — the SDK's
|
||||
/// <c>StatusValue</c> trigger dedups an unchanged status at the monitored item.
|
||||
/// </para>
|
||||
/// </remarks>
|
||||
/// <param name="driverInstanceId">The driver child that just reported comms loss.</param>
|
||||
private void FanCommsLossToValueNodes(string driverInstanceId)
|
||||
{
|
||||
if (_opcUaPublishActor is null) return;
|
||||
if (!_valueRefsByDriver.TryGetValue(driverInstanceId, out var entries) || entries.Count == 0) return;
|
||||
|
||||
var ts = DateTime.UtcNow;
|
||||
var writes = new List<StatusWrite>(entries.Count);
|
||||
foreach (var (_, nodes) in entries)
|
||||
{
|
||||
foreach (var n in nodes)
|
||||
{
|
||||
writes.Add(new StatusWrite(n.NodeId, OpcUaStatus.BadNoCommunication, ts, n.Realm));
|
||||
}
|
||||
}
|
||||
|
||||
if (writes.Count == 0) return;
|
||||
|
||||
_opcUaPublishActor.Tell(new OpcUa.OpcUaPublishActor.AttributeStatusBatchUpdate(writes));
|
||||
|
||||
_log.Info(
|
||||
"DriverHost {Node}: driver {Driver} disconnected — {Count} value node(s) marked BadNoCommunication (value retained)",
|
||||
_localNode, driverInstanceId, writes.Count);
|
||||
}
|
||||
|
||||
/// <summary>
|
||||
/// #481 (Layer 4) — push a synthetic <see cref="OpcUaStatus.BadNoCommunication"/> into the dependency
|
||||
/// mux for every value ref the just-disconnected driver owns, so scripted alarms and virtual tags see
|
||||
|
||||
+126
@@ -0,0 +1,126 @@
|
||||
using Akka.Actor;
|
||||
using Shouldly;
|
||||
using Xunit;
|
||||
using ZB.MOM.WW.OtOpcUa.Commons.OpcUa;
|
||||
using ZB.MOM.WW.OtOpcUa.Commons.Types;
|
||||
using ZB.MOM.WW.OtOpcUa.Runtime.Drivers;
|
||||
using ZB.MOM.WW.OtOpcUa.Runtime.OpcUa;
|
||||
using ZB.MOM.WW.OtOpcUa.Runtime.Tests.Harness;
|
||||
using static ZB.MOM.WW.OtOpcUa.Runtime.Tests.Harness.V3ArtifactSeeder;
|
||||
|
||||
namespace ZB.MOM.WW.OtOpcUa.Runtime.Tests.Drivers;
|
||||
|
||||
/// <summary>
|
||||
/// Archreview <b>03/S15</b> — the value-node half of the comms-loss fan-out. Until this, a driver
|
||||
/// declared comms-lost annotated its Part 9 conditions and pushed a synthetic Bad into the dependency
|
||||
/// mux, but its <b>raw and UNS value variables</b> — the product's external surface — got nothing: an
|
||||
/// OPC UA client subscribed to a value node saw the last value at <b>Good</b> quality for the whole
|
||||
/// outage, for every driver whose failure shape is "reader stops producing" rather than "per-tag Bad
|
||||
/// snapshot".
|
||||
///
|
||||
/// <para><b>Status-only, value retained.</b> The write goes through
|
||||
/// <see cref="OpcUaPublishActor.AttributeStatusBatchUpdate"/> so the node keeps its last known value
|
||||
/// under <c>BadNoCommunication</c> (OPC UA Part 8's convention). The host holds no value cache — v3's
|
||||
/// single-source design — so only the node itself can retain it.</para>
|
||||
///
|
||||
/// <para><b>Nothing is published on reconnect</b>, deliberately: publishing Good would assert a
|
||||
/// quality this actor has not observed. Recovery is the driver's own re-publish (the poll engine's
|
||||
/// <c>forceRaise</c> on a fresh subscription, or the push-model initial push). That contract is
|
||||
/// end-to-end tested in <see cref="DriverHostCommsLossRecoveryTests"/>.</para>
|
||||
/// </summary>
|
||||
public sealed class DriverHostActorCommsLossValueNodesTests : RuntimeActorTestBase
|
||||
{
|
||||
private static readonly NodeId TestNode = NodeId.Parse("driver-commsloss-values");
|
||||
private static readonly RevisionHash RevA = RevisionHash.Parse(new string('c', 64));
|
||||
|
||||
/// <summary>
|
||||
/// A disconnect produces ONE status batch naming exactly the disconnected driver's raw nodes plus
|
||||
/// every referencing UNS mirror, all <c>BadNoCommunication</c>. The second driver's ref is the
|
||||
/// control: a fan-out that walked every value ref on the node instead of the per-driver index would
|
||||
/// mark a perfectly healthy driver's nodes Bad, and no assertion about the first driver's nodes
|
||||
/// would notice.
|
||||
/// </summary>
|
||||
[Fact]
|
||||
public void Disconnect_marks_the_drivers_raw_and_uns_value_nodes_BadNoCommunication()
|
||||
{
|
||||
var db = NewInMemoryDbFactory();
|
||||
var deploymentId = SeedV3Deployment(db, RevA,
|
||||
rawTags: new[]
|
||||
{
|
||||
(Driver: "drv-1", DriverName: "Modbus", Device: "dev1", Tag: "speed", DataType: "Double", Writable: false),
|
||||
(Driver: "drv-1", DriverName: "Modbus", Device: "dev1", Tag: "temp", DataType: "Double", Writable: false),
|
||||
(Driver: "drv-2", DriverName: "S7", Device: "dev2", Tag: "other", DataType: "Double", Writable: false),
|
||||
},
|
||||
unsRefs: new[] { (Area: "filling", Line: "line1", Equip: "station1", BackingTag: "speed", Effective: (string?)null) });
|
||||
|
||||
var (actor, publish, _) = SpawnHostAndApply(this, db, TestNode, deploymentId, RevA);
|
||||
|
||||
actor.Tell(new DriverInstanceActor.ConnectivityChanged("drv-1", Connected: false));
|
||||
|
||||
var batch = publish.ExpectMsg<OpcUaPublishActor.AttributeStatusBatchUpdate>(PresenceBudget);
|
||||
batch.Items.Select(i => i.NodeId).ShouldBe(new[]
|
||||
{
|
||||
"Plant/Modbus/dev1/speed",
|
||||
"filling/line1/station1/speed",
|
||||
"Plant/Modbus/dev1/temp",
|
||||
}, ignoreOrder: true);
|
||||
|
||||
batch.Items.ShouldAllBe(i => i.StatusCode == OpcUaStatus.BadNoCommunication);
|
||||
batch.Items.Single(i => i.NodeId == "Plant/Modbus/dev1/speed").Realm.ShouldBe(AddressSpaceRealm.Raw);
|
||||
batch.Items.Single(i => i.NodeId == "filling/line1/station1/speed").Realm.ShouldBe(AddressSpaceRealm.Uns);
|
||||
|
||||
// The control: the OTHER driver's node is untouched by drv-1's outage.
|
||||
batch.Items.ShouldNotContain(i => i.NodeId == "Plant/S7/dev2/other");
|
||||
|
||||
// ONE batch, not one message per node.
|
||||
publish.ExpectNoMsg(TimeSpan.FromMilliseconds(300));
|
||||
}
|
||||
|
||||
/// <summary>
|
||||
/// A reconnect publishes <b>nothing</b> to the value nodes. Writing Good here would claim a quality
|
||||
/// the host has not observed — the device may be answering the transport and still returning
|
||||
/// garbage — and it would race the driver's own first real value.
|
||||
/// </summary>
|
||||
[Fact]
|
||||
public void Reconnect_publishes_no_value_or_status_message()
|
||||
{
|
||||
var db = NewInMemoryDbFactory();
|
||||
var deploymentId = SeedV3Deployment(db, RevA,
|
||||
rawTags: new[]
|
||||
{
|
||||
(Driver: "drv-1", DriverName: "Modbus", Device: "dev1", Tag: "speed", DataType: "Double", Writable: false),
|
||||
},
|
||||
unsRefs: Array.Empty<(string, string, string, string, string?)>());
|
||||
|
||||
var (actor, publish, _) = SpawnHostAndApply(this, db, TestNode, deploymentId, RevA);
|
||||
|
||||
actor.Tell(new DriverInstanceActor.ConnectivityChanged("drv-1", Connected: false));
|
||||
publish.ExpectMsg<OpcUaPublishActor.AttributeStatusBatchUpdate>(PresenceBudget);
|
||||
|
||||
actor.Tell(new DriverInstanceActor.ConnectivityChanged("drv-1", Connected: true));
|
||||
|
||||
publish.ExpectNoMsg(TimeSpan.FromMilliseconds(500));
|
||||
}
|
||||
|
||||
/// <summary>
|
||||
/// A driver that owns no value refs produces no message at all — an empty batch would cost a hop
|
||||
/// and a sink call for nothing on every flap of an alarm-only or freshly-added driver.
|
||||
/// </summary>
|
||||
[Fact]
|
||||
public void A_driver_with_no_value_refs_publishes_nothing()
|
||||
{
|
||||
var db = NewInMemoryDbFactory();
|
||||
var deploymentId = SeedV3Deployment(db, RevA,
|
||||
rawTags: new[]
|
||||
{
|
||||
(Driver: "drv-1", DriverName: "Modbus", Device: "dev1", Tag: "speed", DataType: "Double", Writable: false),
|
||||
},
|
||||
unsRefs: Array.Empty<(string, string, string, string, string?)>());
|
||||
|
||||
var (actor, publish, _) = SpawnHostAndApply(this, db, TestNode, deploymentId, RevA);
|
||||
|
||||
actor.Tell(new DriverInstanceActor.ConnectivityChanged("drv-unknown", Connected: false));
|
||||
|
||||
publish.ExpectNoMsg(TimeSpan.FromMilliseconds(500));
|
||||
}
|
||||
}
|
||||
Reference in New Issue