fix(opcuaclient): scope the #670 F2 late-replay drop to the post-recovery window

The global 'never older than the last Good source time' rule froze a node
whenever an upstream clock stepped backwards (NTP correction, PLC clock
reset) until the clock caught up. The check is now a replay guard armed
only by a same-session recovery (keep-alive bad->good): per ref it holds
the last Good upstream source time (raised by the recovery read), a ref
disarms on its first in-order notification, and the whole guard expires
after max(30 s, 2x the longest subscription keep-alive window). Outside
it every notification is accepted. The steady-state tracker records the
LAST accepted time, not a high-water mark.
This commit is contained in:
Joseph Doherty
2026-10-11 09:15:51 -04:00
parent 99c13e4459
commit 87e8aff786
4 changed files with 157 additions and 27 deletions
@@ -24,7 +24,7 @@ internal sealed class OpcUaClientDiagnostics
public const string KeepAliveMiss = "keepalive_miss";
/// <summary>A keep-alive came back Good after a bad one on the same session (an in-place recovery, #670).</summary>
public const string KeepAliveRecovered = "keepalive_recovered";
/// <summary>A notification older than the newest Good source time already published for its ref was dropped (#670 F2).</summary>
/// <summary>A late replayed notification (older than the ref's last Good source time) was dropped inside the post-recovery replay window (#670 F2).</summary>
public const string StaleNotificationDropped = "stale_notification_dropped";
private readonly string _driverInstanceId;