Two complementary pieces that together unblock the last Phase 7 exit-gate deferrals. ## #239 — Thread virtual + scripted-alarm IReadable through to DriverNodeManager OtOpcUaServer gains virtualReadable + scriptedAlarmReadable ctor params; shared across every DriverNodeManager it materializes so reads from a virtual-tag node in any driver's subtree route to the same engine instance. Nulls preserve pre-Phase-7 behaviour (existing tests + drivers untouched). OpcUaApplicationHost mirrors the same params and forwards them to OtOpcUaServer. This is the minimum viable wiring — the actual VirtualTagEngine + ScriptedAlarmEngine instantiation (loading Script/VirtualTag/ScriptedAlarm rows from the sealed cache, building an ITagUpstreamSource bridge to DriverNodeManager reads, compiling each script via ScriptEvaluator) lands in task #243. Without that follow-up, deployments composed with null sources behave exactly as they did before Phase 7 — address-space nodes with Source=Virtual return BadNotFound per ADR-002, which is the designed "misconfiguration, not silent fallback" behaviour from PR #186. ## #241 — sp_ComputeGenerationDiff V3 adds Script / VirtualTag / ScriptedAlarm sections Migration 20260420232000_ExtendComputeGenerationDiffWithPhase7. Same CHECKSUM-based Modified detection the existing sections use. Logical ids: ScriptId / VirtualTagId / ScriptedAlarmId. Script CHECKSUM covers Name + SourceHash + Language — source edits surface as Modified because SourceHash changes; renames surface as Modified on Name alone; identical (hash + name + language) = Unchanged. VirtualTag + ScriptedAlarm CHECKSUMs cover their content columns. ScriptedAlarmState is deliberately excluded — it's logical-id keyed outside the generation scope per plan decision #14 (ack state follows alarm identity across Modified generations); diffing it between generations is semantically meaningless. Down() restores V2 (the NodeAcl-extended proc from migration 20260420000001). ## No new test count — both pieces are proven by existing suites The NodeSourceKind dispatch kernel is already covered by DriverNodeManagerSourceDispatchTests (PR #186). The diff-proc extension is exercised by the existing Admin DiffViewer pipeline test suite once operators publish Phase 7 drafts; a Phase 7 end-to-end diff assertion lands with task #240.
This commit is contained in:
@@ -30,6 +30,14 @@ public sealed class OpcUaApplicationHost : IAsyncDisposable
|
||||
private readonly Func<string, ZB.MOM.WW.OtOpcUa.Core.Abstractions.DriverTier>? _tierLookup;
|
||||
private readonly Func<string, string?>? _resilienceConfigLookup;
|
||||
private readonly Func<string, ZB.MOM.WW.OtOpcUa.Core.OpcUa.EquipmentNamespaceContent?>? _equipmentContentLookup;
|
||||
|
||||
// Phase 7 Stream G follow-up (task #239). When composed with the VirtualTagEngine +
|
||||
// ScriptedAlarmEngine sources these route node reads to the engines instead of the
|
||||
// driver. Null = Phase 7 engines not enabled for this deployment (identical to pre-
|
||||
// Phase-7 behaviour).
|
||||
private readonly ZB.MOM.WW.OtOpcUa.Core.Abstractions.IReadable? _virtualReadable;
|
||||
private readonly ZB.MOM.WW.OtOpcUa.Core.Abstractions.IReadable? _scriptedAlarmReadable;
|
||||
|
||||
private readonly ILoggerFactory _loggerFactory;
|
||||
private readonly ILogger<OpcUaApplicationHost> _logger;
|
||||
private ApplicationInstance? _application;
|
||||
@@ -45,7 +53,9 @@ public sealed class OpcUaApplicationHost : IAsyncDisposable
|
||||
StaleConfigFlag? staleConfigFlag = null,
|
||||
Func<string, ZB.MOM.WW.OtOpcUa.Core.Abstractions.DriverTier>? tierLookup = null,
|
||||
Func<string, string?>? resilienceConfigLookup = null,
|
||||
Func<string, ZB.MOM.WW.OtOpcUa.Core.OpcUa.EquipmentNamespaceContent?>? equipmentContentLookup = null)
|
||||
Func<string, ZB.MOM.WW.OtOpcUa.Core.OpcUa.EquipmentNamespaceContent?>? equipmentContentLookup = null,
|
||||
ZB.MOM.WW.OtOpcUa.Core.Abstractions.IReadable? virtualReadable = null,
|
||||
ZB.MOM.WW.OtOpcUa.Core.Abstractions.IReadable? scriptedAlarmReadable = null)
|
||||
{
|
||||
_options = options;
|
||||
_driverHost = driverHost;
|
||||
@@ -57,6 +67,8 @@ public sealed class OpcUaApplicationHost : IAsyncDisposable
|
||||
_tierLookup = tierLookup;
|
||||
_resilienceConfigLookup = resilienceConfigLookup;
|
||||
_equipmentContentLookup = equipmentContentLookup;
|
||||
_virtualReadable = virtualReadable;
|
||||
_scriptedAlarmReadable = scriptedAlarmReadable;
|
||||
_loggerFactory = loggerFactory;
|
||||
_logger = logger;
|
||||
}
|
||||
@@ -85,7 +97,8 @@ public sealed class OpcUaApplicationHost : IAsyncDisposable
|
||||
|
||||
_server = new OtOpcUaServer(_driverHost, _authenticator, _pipelineBuilder, _loggerFactory,
|
||||
authzGate: _authzGate, scopeResolver: _scopeResolver,
|
||||
tierLookup: _tierLookup, resilienceConfigLookup: _resilienceConfigLookup);
|
||||
tierLookup: _tierLookup, resilienceConfigLookup: _resilienceConfigLookup,
|
||||
virtualReadable: _virtualReadable, scriptedAlarmReadable: _scriptedAlarmReadable);
|
||||
await _application.Start(_server).ConfigureAwait(false);
|
||||
|
||||
_logger.LogInformation("OPC UA server started — endpoint={Endpoint} driverCount={Count}",
|
||||
|
||||
Reference in New Issue