Task #249 — Driver test-client CLIs: shared lib + Modbus CLI first

Mirrors the v1 otopcua-cli value prop (ad-hoc shell-level PLC validation) for
the Modbus-TCP driver, and lays down the shared scaffolding that AB CIP, AB
Legacy, S7, and TwinCAT CLIs will build on.

New projects:
  - src/ZB.MOM.WW.OtOpcUa.Driver.Cli.Common/ — DriverCommandBase (verbose
    flag + Serilog config) + SnapshotFormatter (single-tag + table +
    write-result renders with invariant-culture value formatting + OPC UA
    status-code shortnames + UTC-normalised timestamps).
  - src/ZB.MOM.WW.OtOpcUa.Driver.Modbus.Cli/ — otopcua-modbus-cli executable.
    Commands: probe, read, write, subscribe. ModbusCommandBase carries the
    host/port/unit-id flags + builds ModbusDriverOptions with Probe.Enabled
    =false (CLI runs are one-shot; driver-internal keep-alive would race).

Commands + coverage:
  - probe              single FC03 + GetHealth() + pretty-print
  - read               region × address × type synth into one driver tag
  - write              same shape + --value parsed per --type
  - subscribe          polled-subscription stream until Ctrl+C

Tests (38 total):
  - 16 SnapshotFormatterTests covering: status-code shortnames, unknown
    codes fall back to hex, null value + timestamp placeholders, bool
    lowercase, float invariant culture, string quoting, write-result shape,
    aligned table columns, mismatched-length rejection, UTC normalisation.
  - 22 Modbus CLI tests:
      · ReadCommandTests.SynthesiseTagName (5 theory cases)
      · WriteCommandParseValueTests (17 cases: bool aliases, unknown rejected,
        Int16 bounds, UInt16/Bcd16 type, Float32/64 invariant culture,
        String passthrough, BitInRegister, Int32 MinValue, non-numeric reject)

Wiring:
  - ZB.MOM.WW.OtOpcUa.slnx grew 4 entries (2 src + 2 tests).
  - docs/Driver.Modbus.Cli.md — operator-facing runbook with examples per
    command + output format + typical workflows.

Regression: full-solution build clean; shared-lib tests 16/0, Modbus CLI tests
22/0.

Next up: repeat the pattern for AB CIP (shares ~40% more with Modbus via
libplctag), then AB Legacy, S7, TwinCAT. The shared base stays as-is unless
one of those exposes a gap the Modbus-first pass missed.

Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
This commit is contained in:
Joseph Doherty
2026-04-21 08:15:14 -04:00
parent b644b26310
commit 5dac2e9375
17 changed files with 1086 additions and 0 deletions

121
docs/Driver.Modbus.Cli.md Normal file
View File

@@ -0,0 +1,121 @@
# `otopcua-modbus-cli` — Modbus-TCP test client
Ad-hoc probe / read / write / subscribe tool for talking to Modbus-TCP devices
through the **same** `ModbusDriver` the OtOpcUa server uses. Mirrors the v1
OPC UA `otopcua-cli` shape so the muscle memory carries over: drop to a shell,
point at a PLC, watch registers move.
First of four driver test-client CLIs (Modbus → AB CIP → AB Legacy → S7 →
TwinCAT). Built on the shared `ZB.MOM.WW.OtOpcUa.Driver.Cli.Common` library
so each downstream CLI inherits verbose/log wiring + snapshot formatting
without copy-paste.
## Build + run
```powershell
dotnet build src/ZB.MOM.WW.OtOpcUa.Driver.Modbus.Cli
dotnet run --project src/ZB.MOM.WW.OtOpcUa.Driver.Modbus.Cli -- --help
```
Or publish a self-contained binary:
```powershell
dotnet publish src/ZB.MOM.WW.OtOpcUa.Driver.Modbus.Cli -c Release -o publish/modbus-cli
publish/modbus-cli/otopcua-modbus-cli.exe --help
```
## Common flags
Every command accepts:
| Flag | Default | Purpose |
|---|---|---|
| `-h` / `--host` | **required** | Modbus-TCP server hostname or IP |
| `-p` / `--port` | `502` | TCP port |
| `-U` / `--unit-id` | `1` | Modbus unit / slave ID |
| `--timeout-ms` | `2000` | Per-PDU timeout |
| `--disable-reconnect` | off | Turn off mid-transaction reconnect-and-retry |
| `--verbose` | off | Serilog debug output |
## Commands
### `probe` — is the PLC up?
Connects, reads one holding register, prints driver health. Fastest sanity
check after swapping a network cable or deploying a new device.
```powershell
otopcua-modbus-cli probe -h 192.168.1.10
otopcua-modbus-cli probe -h 192.168.1.10 --probe-address 100 # device locks HR[0]
```
### `read` — single register / coil / string
Synthesises a one-tag driver config on the fly from `--region` + `--address`
+ `--type` flags.
```powershell
# Holding register as UInt16
otopcua-modbus-cli read -h 192.168.1.10 -r HoldingRegisters -a 100 -t UInt16
# Float32 with word-swap (CDAB) — common on Siemens / some AB families
otopcua-modbus-cli read -h 192.168.1.10 -r HoldingRegisters -a 200 -t Float32 --byte-order WordSwap
# Single bit out of a packed holding register
otopcua-modbus-cli read -h 192.168.1.10 -r HoldingRegisters -a 10 -t BitInRegister --bit-index 3
# 40-char ASCII string — DirectLOGIC packs the first char in the low byte
otopcua-modbus-cli read -h 192.168.1.10 -r HoldingRegisters -a 300 -t String --string-length 40 --string-byte-order LowByteFirst
# Discrete input / coil
otopcua-modbus-cli read -h 192.168.1.10 -r DiscreteInputs -a 5 -t Bool
```
### `write` — single value
Same flag shape as `read` plus `-v` / `--value`. Values parse per `--type`
using invariant culture (period as decimal separator). Booleans accept
`true`/`false`/`1`/`0`/`yes`/`no`/`on`/`off`.
```powershell
otopcua-modbus-cli write -h 192.168.1.10 -r HoldingRegisters -a 100 -t UInt16 -v 42
otopcua-modbus-cli write -h 192.168.1.10 -r HoldingRegisters -a 200 -t Float32 -v 3.14
otopcua-modbus-cli write -h 192.168.1.10 -r Coils -a 5 -t Bool -v on
```
**Writes are non-idempotent by default** — a timeout after the device
already applied the write will NOT auto-retry. This matches the driver's
production contract (plan decisions #44 + #45).
### `subscribe` — watch a register until Ctrl+C
Uses the driver's `ISubscribable` surface (polling under the hood via
`PollGroupEngine`). Prints every data-change event with a timestamp.
```powershell
otopcua-modbus-cli subscribe -h 192.168.1.10 -r HoldingRegisters -a 100 -t Int16 -i 500
```
## Output format
- `probe` / `read` emit a multi-line per-tag block: `Tag / Value / Status /
Source Time / Server Time`.
- `write` emits one line: `Write <tag>: 0x... (Good | BadCommunicationError | …)`.
- `subscribe` emits one line per change: `[HH:mm:ss.fff] <tag> = <value> (<status>)`.
Status codes are rendered as `0xXXXXXXXX (Name)` for the OPC UA shortlist
(`Good`, `BadCommunicationError`, `BadTimeout`, `BadNodeIdUnknown`,
`BadTypeMismatch`, `Uncertain`, …). Unknown codes fall back to bare hex.
## Typical workflows
**"Is the PLC alive?"** → `probe`.
**"Does my recipe write land?"** → `write` + `read` back against the same
address.
**"Why is tag X flipping?"** → `subscribe` + wait for the operator scenario.
**"What's the right byte order for this family?"** → `read` with
`--byte-order BigEndian`, then with `--byte-order WordSwap`. The one that
gives plausible values is the correct one for that device.