Merge hw2-makino: hardware live-gate fixes (hw2-makino)
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
This commit is contained in:
+24
-4
@@ -244,6 +244,13 @@ control's raw codes, published verbatim as Int32 so a client sees exactly what t
|
||||
| `Edit`, `TmMode` | program-edit state; T/M mode |
|
||||
|
||||
Author one the same way as any fixed-tree tag — `FIXED:Status/Run` (Int32), `FIXED:Status/RunText` (String).
|
||||
Live (hw2 gate, 2026-10-08, Makino Z-34184 31i-B, idle): `cnc_statinfo` answers a 14-byte primary block and read
|
||||
steadily `Auto=3 Run=0 (RESET) Motion=0 Mstb=0 Emergency=0 Alarm=0 Edit=0 TmMode=0` over 6 minutes, with an empty
|
||||
`cnc_rdalmmsg2` list — consistent. ⚠️ `Auto=3` (EDIT on the table above) disagrees with `OperationMode/ModeText`,
|
||||
which read `AUTO` (`cnc_rdopmode` 0x0057 = 1) throughout; ignitionoee independently found 0x0057 toggling 1↔2 with
|
||||
no explained meaning on the same machine, so treat `OperationMode/` as unconfirmed on the 31i-B and confirm `Auto`
|
||||
against the panel before relying on either.
|
||||
|
||||
Like `Program/`, the subtree is gated on a bootstrap probe: a control that refuses `cnc_statinfo` gets no
|
||||
`Status/` nodes and the rest of the tree is unaffected. Reads are served from the poll snapshot, so they
|
||||
issue no wire traffic and go `BadCommunicationError` once the device has stopped answering.
|
||||
@@ -317,12 +324,19 @@ FANUC signal map:
|
||||
|
||||
| Signal | PMC address | Notes |
|
||||
|---|---|---|
|
||||
| Feed override `*FV0-*FV7` | `G12` (Byte) | **Inverted**: the byte holds the one's complement. Percent = `255 - value` for a binary-coded switch (`255` = 0%, `155` = 100%); gray-coded/ladder-converted panels differ |
|
||||
| Feed override `*FV0-*FV7` | `G12` (Byte) | **Inverted**: the byte holds the one's complement. Percent = `~value & 0xFF` for a binary-coded switch (raw `0xFF` = 0%, raw `0x9B` = 100%); gray-coded/ladder-converted panels differ |
|
||||
| Rapid override `ROV1`, `ROV2` | `G14.0`, `G14.1` (Bit) | Two bits select 100% / 50% / 25% / F0 |
|
||||
| Spindle override `SOV0-SOV7` | `G30` (Byte) | Percent, usually a direct 0-150 value |
|
||||
| Spindle override `SOV0-SOV7` | `G30` (Byte) | Percent, usually a direct 0-150 value — mask it (`value & 0xFF`): 128-150 % read negative |
|
||||
|
||||
Author them as normal PMC tags (`G12`, `G14.0`, `G30` — G is accepted on the 30i family and the 16i). To publish a
|
||||
percentage rather than the raw byte, derive it with a virtual tag (`255 - ctx.GetTag("{{equip}}/FeedOverrideRaw")`).
|
||||
Author them as normal PMC tags (`G12`, `G14.0`, `G30` — G is accepted on the 30i family and the 16i). ⚠️ A `Byte`
|
||||
tag is **signed** (`sbyte`, published as Int32), so a raw byte above `0x7F` reads negative: on the Makino Z-34184 at
|
||||
100 % feed override `G12` reads **`-101`** (raw `0x9B` = 155). `255 - value` would therefore give 356, not 100 — mask
|
||||
before inverting. To publish a percentage rather than the raw byte, derive it with a virtual tag
|
||||
(`~(int)ctx.GetTag("{{equip}}/FeedOverrideRaw").Value & 0xFF` for `G12`; `(int)… & 0xFF` for `G30`).
|
||||
|
||||
Read-only live check (hw2 gate, 2026-10-08, Makino Z-34184 idle at the panel's 100 % positions): `G12 = -101`
|
||||
(→ 100 %), `G14.0 = G14.1 = false` (→ rapid 100 %), `G30 = 100` (→ 100 %). Plausible against the standard map;
|
||||
not yet cross-checked against the switches at other positions.
|
||||
|
||||
⚠️ **The addresses above are the FANUC *standard* signal assignment; the meaning is defined by the machine
|
||||
builder's ladder.** Confirm each against the machine's own PMC signal list before trusting the number, and
|
||||
@@ -489,6 +503,12 @@ an `ALARM:` address without the `alarm` object (not a condition, and no value to
|
||||
on a non-`ALARM:` address (a condition nothing can raise). Reading an `ALARM:` tag's RawPath through the driver
|
||||
returns `BadNotSupported`; writing it, `BadNotWritable`.
|
||||
|
||||
**Live (passive, read-only) — hw2 gate 2026-10-08, Makino Z-34184.** `ALARM:*`, `ALARM:OTHER`, `ALARM:Servo` and
|
||||
`ALARM:T6` subscribed for 6 minutes at a 2 s poll: the control answered `cnc_rdalmmsg2` `rc=0` with an **empty**
|
||||
(0-byte) payload every time, no condition event of any kind was raised (no spurious Raise, no quality churn), and driver
|
||||
health stayed Healthy. With no alarm active, the 76-vs-80-byte layout and the 30i type codes remain unobserved on
|
||||
this control.
|
||||
|
||||
**Known residuals.** Whether the alarm *list* itself flickers at a CNC reset (the status word does, one poll)
|
||||
is unobserved; if the live gate shows it, a clear-debounce knob is the follow-up. Real-machine raise/clear is
|
||||
only observable passively — never induce an alarm on a production control.
|
||||
|
||||
@@ -1816,41 +1816,60 @@ public sealed class FocasDriver : IDriver, IReadable, IWritable, ITagDiscovery,
|
||||
{
|
||||
if (device.Client is { IsConnected: true } c) return c;
|
||||
|
||||
// 05/STAB-8: inside an open backoff window a data-path / per-tick-loop caller fails fast — no
|
||||
// socket create, no wire connect. The probe loop bypasses this and drives failure/success.
|
||||
if (!bypassBackoff && !device.Backoff.ShouldAttempt(DateTime.UtcNow))
|
||||
throw new ConnectionThrottledException(
|
||||
$"FOCAS connect to {device.Options.HostAddress} throttled — backoff window open after a recent connect failure.");
|
||||
|
||||
// Discard the existing client (if any) before creating a new one. A client that is
|
||||
// non-null but not connected may have been disposed by a HandleRecycle race or a prior
|
||||
// teardown — retrying ConnectAsync on a disposed FocasWireClient hits ThrowIfDisposed and
|
||||
// returns a permanent BadCommunicationError with no recovery. Replacing it unconditionally
|
||||
// ensures EnsureConnectedAsync always works with a fresh, non-disposed instance.
|
||||
if (device.Client is not null)
|
||||
{
|
||||
device.Client.Dispose();
|
||||
device.Client = null;
|
||||
}
|
||||
|
||||
// Wrap the raw wire client so every operation on the device's single FOCAS/2 socket is
|
||||
// serialized (request→response on one socket cannot interleave) and time-bounded. Without
|
||||
// this, the equipment poll, fixed-tree loop, probe, and recycle loop collide on the shared
|
||||
// socket and a stalled read blocks forever — leaving bound tags at BadWaitingForInitialData.
|
||||
device.Client = new SynchronizedFocasClient(_clientFactory.Create(), _options.Timeout);
|
||||
// Serialize the connect (hw2 Makino live gate, 2026-10-08). The alarm poll loop and the fixed-tree loop
|
||||
// both reach here right after init; unserialized, the second caller saw the first caller's still-
|
||||
// CONNECTING client as "not connected", disposed it and opened a second session, and the first caller's
|
||||
// failure path then disposed the second caller's client — two sessions to a CNC with a small handle pool,
|
||||
// a disposed client handed back, and a spurious backoff failure (observed live as the fixed-tree
|
||||
// bootstrap failing with ObjectDisposedException: FocasWireClient).
|
||||
await device.ConnectGate.WaitAsync(ct).ConfigureAwait(false);
|
||||
try
|
||||
{
|
||||
await device.Client.ConnectAsync(device.ParsedAddress, _options.Timeout, ct).ConfigureAwait(false);
|
||||
// Another caller may have connected while this one waited.
|
||||
if (device.Client is { IsConnected: true } connected) return connected;
|
||||
|
||||
// 05/STAB-8: inside an open backoff window a data-path / per-tick-loop caller fails fast — no
|
||||
// socket create, no wire connect. The probe loop bypasses this and drives failure/success.
|
||||
if (!bypassBackoff && !device.Backoff.ShouldAttempt(DateTime.UtcNow))
|
||||
throw new ConnectionThrottledException(
|
||||
$"FOCAS connect to {device.Options.HostAddress} throttled — backoff window open after a recent connect failure.");
|
||||
|
||||
// Discard the existing client (if any) before creating a new one. A client that is
|
||||
// non-null but not connected may have been disposed by a HandleRecycle race or a prior
|
||||
// teardown — retrying ConnectAsync on a disposed FocasWireClient hits ThrowIfDisposed and
|
||||
// returns a permanent BadCommunicationError with no recovery. Replacing it unconditionally
|
||||
// ensures EnsureConnectedAsync always works with a fresh, non-disposed instance.
|
||||
if (device.Client is not null)
|
||||
{
|
||||
device.Client.Dispose();
|
||||
device.Client = null;
|
||||
}
|
||||
|
||||
// Wrap the raw wire client so every operation on the device's single FOCAS/2 socket is
|
||||
// serialized (request→response on one socket cannot interleave) and time-bounded. Without
|
||||
// this, the equipment poll, fixed-tree loop, probe, and recycle loop collide on the shared
|
||||
// socket and a stalled read blocks forever — leaving bound tags at BadWaitingForInitialData.
|
||||
var client = new SynchronizedFocasClient(_clientFactory.Create(), _options.Timeout);
|
||||
device.Client = client;
|
||||
try
|
||||
{
|
||||
await client.ConnectAsync(device.ParsedAddress, _options.Timeout, ct).ConfigureAwait(false);
|
||||
}
|
||||
catch (Exception ex)
|
||||
{
|
||||
// Dispose only OUR client — never one another path installed meanwhile (recycle/teardown).
|
||||
client.Dispose();
|
||||
if (ReferenceEquals(device.Client, client)) device.Client = null;
|
||||
// The caller's OWN cancellation says nothing about the CNC: do not open the backoff window, or
|
||||
// every caller queued on ConnectGate behind it would be throttled for ~1 s for nothing.
|
||||
if (!(ex is OperationCanceledException && ct.IsCancellationRequested))
|
||||
device.Backoff.RecordFailure(DateTime.UtcNow); // 05/STAB-8: open the backoff window
|
||||
throw;
|
||||
}
|
||||
device.Backoff.RecordSuccess(); // 05/STAB-8: recovery resets the window immediately
|
||||
return client;
|
||||
}
|
||||
catch
|
||||
{
|
||||
device.Client.Dispose();
|
||||
device.Client = null;
|
||||
device.Backoff.RecordFailure(DateTime.UtcNow); // 05/STAB-8: open the backoff window
|
||||
throw;
|
||||
}
|
||||
device.Backoff.RecordSuccess(); // 05/STAB-8: recovery resets the window immediately
|
||||
return device.Client;
|
||||
finally { device.ConnectGate.Release(); }
|
||||
}
|
||||
|
||||
/// <summary>Disposes the driver and releases all resources synchronously.</summary>
|
||||
@@ -1919,13 +1938,17 @@ public sealed class FocasDriver : IDriver, IReadable, IWritable, ITagDiscovery,
|
||||
/// Per-device connect-attempt throttle (05/STAB-8). A dead CNC fails fast inside the
|
||||
/// backoff window instead of paying a full two-socket reconnect on every tick of each of
|
||||
/// the read / write / probe / fixed-tree / recycle loops; the probe loop bypasses it and a
|
||||
/// successful connect resets it. FOCAS's <c>EnsureConnectedAsync</c> is not gate-serialized
|
||||
/// (the loops already race the client swap by design), so this is best-effort — atomic
|
||||
/// enough on 64-bit for the int/DateTime state, and a benign extra/skipped attempt is the
|
||||
/// worst outcome of a race.
|
||||
/// successful connect resets it. The connect itself is serialized by
|
||||
/// <see cref="ConnectGate"/>; the backoff is consulted inside it.
|
||||
/// </summary>
|
||||
public ConnectionBackoff Backoff { get; } = new(TimeSpan.FromSeconds(1), TimeSpan.FromSeconds(30));
|
||||
|
||||
/// <summary>
|
||||
/// Serializes <c>EnsureConnectedAsync</c> per device, so concurrent loops (alarm poll, fixed tree, data
|
||||
/// path) share ONE connect instead of racing two sessions and disposing each other's client.
|
||||
/// </summary>
|
||||
public SemaphoreSlim ConnectGate { get; } = new(1, 1);
|
||||
|
||||
/// <summary>Gets the lock object for probe synchronization.</summary>
|
||||
public object ProbeLock { get; } = new();
|
||||
/// <summary>Gets or sets the current host connectivity state.</summary>
|
||||
|
||||
@@ -0,0 +1,132 @@
|
||||
using Shouldly;
|
||||
using Xunit;
|
||||
using ZB.MOM.WW.OtOpcUa.Core.Abstractions;
|
||||
using ZB.MOM.WW.OtOpcUa.Driver.FOCAS;
|
||||
|
||||
namespace ZB.MOM.WW.OtOpcUa.Driver.FOCAS.Tests;
|
||||
|
||||
/// <summary>
|
||||
/// Two callers reaching <c>EnsureConnectedAsync</c> while the device has no live session (the alarm poll loop
|
||||
/// and the fixed-tree loop both start right after init) must open ONE session between them. Found live on the
|
||||
/// Makino Z-34184 (hw2 gate, 2026-10-08): the fixed-tree bootstrap failed with
|
||||
/// <c>ObjectDisposedException: FocasWireClient</c>, because the second caller saw the first caller's
|
||||
/// still-connecting client as "not connected", disposed it, and opened a second one — and the first caller's
|
||||
/// failure path then disposed the SECOND caller's client. Two TCP sessions to a production CNC with a small
|
||||
/// handle pool, a disposed client handed back to a caller, and a spurious connect-backoff failure.
|
||||
/// </summary>
|
||||
[Trait("Category", "Unit")]
|
||||
public sealed class FocasConcurrentConnectTests
|
||||
{
|
||||
/// <summary>A fake whose connect parks until released, and which — like the real wire client — refuses to
|
||||
/// finish connecting once disposed.</summary>
|
||||
private sealed class GatedConnectClient(Task release, TaskCompletionSource? entered = null) : FakeFocasClient
|
||||
{
|
||||
private bool _disposed;
|
||||
|
||||
public override async Task ConnectAsync(FocasHostAddress address, TimeSpan timeout, CancellationToken ct)
|
||||
{
|
||||
entered?.TrySetResult();
|
||||
await release.WaitAsync(ct);
|
||||
if (_disposed) throw new ObjectDisposedException("FocasWireClient");
|
||||
await base.ConnectAsync(address, timeout, ct);
|
||||
}
|
||||
|
||||
public override void Dispose()
|
||||
{
|
||||
_disposed = true;
|
||||
base.Dispose();
|
||||
}
|
||||
}
|
||||
|
||||
/// <summary>Concurrent first reads share one connect; nobody's client is disposed under them.</summary>
|
||||
[Fact]
|
||||
public async Task Concurrent_first_reads_open_one_session_and_both_succeed()
|
||||
{
|
||||
var release = new TaskCompletionSource(TaskCreationOptions.RunContinuationsAsynchronously);
|
||||
var entered = new TaskCompletionSource(TaskCreationOptions.RunContinuationsAsynchronously);
|
||||
var factory = new FakeFocasClientFactory { Customise = () => new GatedConnectClient(release.Task, entered) };
|
||||
await using var drv = new FocasDriver(new FocasDriverOptions
|
||||
{
|
||||
Devices = [new FocasDeviceOptions("focas://10.0.0.5:8193")],
|
||||
RawTags = FocasRawTags.Entries([
|
||||
new FocasTagDefinition("A", "focas://10.0.0.5:8193", "R100", FocasDataType.Byte),
|
||||
new FocasTagDefinition("B", "focas://10.0.0.5:8193", "R200", FocasDataType.Byte)]),
|
||||
Probe = new FocasProbeOptions { Enabled = false },
|
||||
Timeout = TimeSpan.FromSeconds(5),
|
||||
}, "drv-1", factory);
|
||||
await drv.InitializeAsync("{}", CancellationToken.None);
|
||||
|
||||
var first = drv.ReadAsync(["A"], CancellationToken.None);
|
||||
// Deterministic: the first caller is now parked INSIDE its connect (client created, not yet connected) —
|
||||
// the exact window the race needs. The second caller then runs synchronously up to its first real await:
|
||||
// pre-fix that is "dispose the first client, Create() a second"; with the gate it parks on ConnectGate.
|
||||
await entered.Task.WaitAsync(TimeSpan.FromSeconds(5));
|
||||
var second = drv.ReadAsync(["B"], CancellationToken.None);
|
||||
release.SetResult();
|
||||
var results = await Task.WhenAll(first, second);
|
||||
|
||||
factory.Clients.Count.ShouldBe(1, "two concurrent callers must share one FOCAS session, not race two");
|
||||
factory.Clients[0].DisposeCount.ShouldBe(0, "no caller may dispose a client another caller is using");
|
||||
results[0].Single().StatusCode.ShouldBe(FocasStatusMapper.Good);
|
||||
results[1].Single().StatusCode.ShouldBe(FocasStatusMapper.Good);
|
||||
}
|
||||
|
||||
/// <summary>A failed connect does not poison a later one — the gate is released on failure.</summary>
|
||||
[Fact]
|
||||
public async Task A_failed_connect_releases_the_gate_for_the_next_caller()
|
||||
{
|
||||
var factory = new FakeFocasClientFactory();
|
||||
var attempt = 0;
|
||||
factory.Customise = () => new FakeFocasClient { ThrowOnConnect = Interlocked.Increment(ref attempt) == 1 };
|
||||
await using var drv = new FocasDriver(new FocasDriverOptions
|
||||
{
|
||||
Devices = [new FocasDeviceOptions("focas://10.0.0.5:8193")],
|
||||
RawTags = FocasRawTags.Entries([new FocasTagDefinition("A", "focas://10.0.0.5:8193", "R100", FocasDataType.Byte)]),
|
||||
Probe = new FocasProbeOptions { Enabled = false },
|
||||
}, "drv-1", factory);
|
||||
await drv.InitializeAsync("{}", CancellationToken.None);
|
||||
|
||||
(await drv.ReadAsync(["A"], CancellationToken.None)).Single().StatusCode
|
||||
.ShouldNotBe(FocasStatusMapper.Good);
|
||||
// Past the 1 s initial connect backoff window, the next caller must be able to connect.
|
||||
await Task.Delay(TimeSpan.FromMilliseconds(1100));
|
||||
var read = drv.ReadAsync(["A"], CancellationToken.None);
|
||||
(await read.WaitAsync(TimeSpan.FromSeconds(5))).Single().StatusCode.ShouldBe(FocasStatusMapper.Good);
|
||||
}
|
||||
|
||||
/// <summary>
|
||||
/// A caller cancelled during its connect must not open the backoff window: the cancellation is the caller's,
|
||||
/// not the CNC's, and a recorded failure would throttle every caller queued behind it on the gate.
|
||||
/// </summary>
|
||||
[Fact]
|
||||
public async Task A_caller_cancelled_during_connect_does_not_throttle_the_next_caller()
|
||||
{
|
||||
var never = new TaskCompletionSource(TaskCreationOptions.RunContinuationsAsynchronously);
|
||||
var entered = new TaskCompletionSource(TaskCreationOptions.RunContinuationsAsynchronously);
|
||||
var factory = new FakeFocasClientFactory();
|
||||
var created = 0;
|
||||
// First client parks in connect until cancelled; every later client connects immediately.
|
||||
factory.Customise = () => Interlocked.Increment(ref created) == 1
|
||||
? new GatedConnectClient(never.Task, entered)
|
||||
: new FakeFocasClient();
|
||||
await using var drv = new FocasDriver(new FocasDriverOptions
|
||||
{
|
||||
Devices = [new FocasDeviceOptions("focas://10.0.0.5:8193")],
|
||||
RawTags = FocasRawTags.Entries([new FocasTagDefinition("A", "focas://10.0.0.5:8193", "R100", FocasDataType.Byte)]),
|
||||
Probe = new FocasProbeOptions { Enabled = false },
|
||||
Timeout = TimeSpan.FromSeconds(5),
|
||||
}, "drv-1", factory);
|
||||
await drv.InitializeAsync("{}", CancellationToken.None);
|
||||
|
||||
using var cts = new CancellationTokenSource();
|
||||
var cancelled = drv.ReadAsync(["A"], cts.Token);
|
||||
await entered.Task.WaitAsync(TimeSpan.FromSeconds(5));
|
||||
cts.Cancel();
|
||||
try { await cancelled; } catch (OperationCanceledException) { /* either surfaced or mapped — both fine */ }
|
||||
|
||||
// Immediately — well inside the 1 s initial backoff window a recorded failure would have opened.
|
||||
var next = await drv.ReadAsync(["A"], CancellationToken.None).WaitAsync(TimeSpan.FromSeconds(5));
|
||||
next.Single().StatusCode.ShouldBe(FocasStatusMapper.Good, "a caller's own cancellation must not throttle the next connect");
|
||||
factory.Clients.Count.ShouldBe(2);
|
||||
}
|
||||
}
|
||||