fix(modbus): review r1 - resolved address keys win only when the editor pinned them
N1: the m2 precedence trusted region/address whenever the keys were present,
but the AdminUI model stamps defaulted HoldingRegisters/0 on every save, so a
string-only tag (CSV import, or any editor toggle) silently became HR[0] -
reads AND writes. The resolved keys are now authoritative only when the editor
marked them ("addressResolved": true, written by Resolve); an unmarked
addressString is always resolved through the parser with the driver's family.
The model no longer stamps address fields for a string-only tag, CSV export
leaves its address cells blank, and the editor hint distinguishes string-only
from pinned tags. Tests: CSV import and editor save of a string-only tag, a
stamped-default blob, and the pinned positive control across families.
n1: docs/v2/modbus-addressing.md updated (FC23 opt-in, maxReadGap semantics,
coalescing scope, addressString/family rules, coil coercion, refusals).
n2: form round-trip tests for UseFC23ForMultiRegisterWrites /
DisableReadCoalescing. n4: the editor keeps unresolved address text when the
parent echoes back its own emit. n3: noted, no change.
Refs #741
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
This commit is contained in:
@@ -22,6 +22,23 @@ public sealed class ModbusDriverFormModelTests
|
||||
Converters = { new JsonStringEnumConverter() },
|
||||
};
|
||||
|
||||
/// <summary>Review r1 n2: the lane's new form keys survive FromOptions → ToOptions, and their defaults keep
|
||||
/// the historical wire (FC16, coalescing on at gap 8 only when the key is absent).</summary>
|
||||
[Fact]
|
||||
public void Form_round_trips_the_FC23_opt_in_and_coalescing_keys()
|
||||
{
|
||||
var form = new ModbusDriverForm.FormModel { UseFC23ForMultiRegisterWrites = true, DisableFC23 = true, DisableReadCoalescing = true, MaxReadGap = 0 };
|
||||
var back = ModbusDriverForm.FormModel.FromOptions(form.ToOptions());
|
||||
back.UseFC23ForMultiRegisterWrites.ShouldBeTrue();
|
||||
back.DisableFC23.ShouldBeTrue();
|
||||
back.DisableReadCoalescing.ShouldBeTrue();
|
||||
back.MaxReadGap.ShouldBe(0);
|
||||
|
||||
var defaults = new ModbusDriverForm.FormModel().ToOptions();
|
||||
defaults.UseFC23ForMultiRegisterWrites.ShouldBeFalse();
|
||||
defaults.MaxReadGap.ShouldBe((ushort)8);
|
||||
}
|
||||
|
||||