# DelmiaRecipeDownload — ScadaBridge Inbound API spec (as deployed)
**Captured:** 2026-09-02 from the live **prod** management API on `wonder-app-vd03` (method id 4,
API keys, the `CvdReactor` template's `ProcessRecipeDownload` script, the `DelmiaReceiver` template,
and the inbound audit log). **QA (`vq03`/`vq04`) was NOT read** — its management API requires real
LDAP credentials (prod runs with `DisableLogin`); re-capture QA with `scadabridge api-method get --id …`
once credentials are to hand. The definition is config-as-data in the central ConfigDb (not in git), so
this file is the durable record; the legacy predecessor is documented in
[`../former-api-specs/dnc/Delmia-Integration-API.md`](../former-api-specs/dnc/Delmia-Integration-API.md)
(Surface B), and the client that calls it is the `WWNotifier.exe` drop-in
([`DelmiaNotifier`](../../src/ZB.MOM.WW.ScadaBridge.DelmiaNotifier/README.md)).
## 1. Endpoint
| Item | Value |
|---|---|
| Method / path | `POST /api/DelmiaRecipeDownload` |
| Auth | `X-API-Key: sbk_<keyId>_<secret>` **or** `Authorization: Bearer sbk_<keyId>_<secret>` (Authorization wins if both) |
| Content type | `application/json`, flat PascalCase object |
| Server timeout | **45 s** (`TimeoutSeconds` on the method); the site-side handshake wait inside it is **25 s** |
| Prod base URL | `http://wonder-app-vd03.zmr.zimmer.com:8085` (single central node) |
| QA base URLs | `http://10.220.158.2:8085` (vq03), `http://10.220.158.3:8085` (vq04) — list **both** in the notifier's `BaseUrls`; a standby central relays to the active peer |
Unauthenticated / bad-key calls return **401** `{"error":"Invalid or missing API key"}` (audit kind
`InboundAuthFailure`). General Inbound API status semantics (413 body cap, 503 `STANDBY_NODE` /
`ACTIVE_NODE_UNREACHABLE`, unknown method) are in
[`Component-InboundAPI.md`](../requirements/Component-InboundAPI.md).
## 2. Request
Deployed `ParameterDefinitions` (JSON Schema, verbatim — note `required` is **empty**; the
script itself rejects a missing/blank `MachineCode`):
```json
{"type":"object","properties":{
"MachineCode":{"type":"string"},
"DownloadPath":{"type":"string"},
"WorkOrderNumber":{"type":"string"},
"PartNumber":{"type":"string"},
"JobStepNumber":{"type":"string"},
"Username":{"type":"string"}},
"required":[]}
```
| Field | Notifier flag | Meaning | Where it lands on the site |
|---|---|---|---|
| `MachineCode` | `-m` | **Routing key** — must equal an instance `UniqueName` exactly (trimmed). Prod today: `Z28061`, `Z28062`, `Z28061Sim`. | `Route.To(MachineCode)` |
| `DownloadPath` | `-d` | Path where the recipe/NC file was placed | `DelmiaReceiver.DownloadPath` |
| `WorkOrderNumber` | `-w` | Work order | `DelmiaReceiver.WorkOrderNumber` |
| `PartNumber` | `-p` | Part / item number | `DelmiaReceiver.PartNumber` |
| `JobStepNumber` | `-s` | Job step / sequence op | `DelmiaReceiver.JobStepNumber` |
| `Username` | `-u` | Operator (audit only) | `DelmiaReceiver.Username` |
Example (a real call taken from the prod audit log):
```bash
curl -s -X POST http://wonder-app-vd03.zmr.zimmer.com:8085/api/DelmiaRecipeDownload \
-H "X-API-Key: $SCADABRIDGE_API_KEY" -H "Content-Type: application/json" \
-d '{"MachineCode":"Z28061Sim","DownloadPath":"C:\\recipes\\test.nc","WorkOrderNumber":"WO-TEST-001","PartNumber":"PN-TEST","JobStepNumber":"0100","Username":"delmia-sim-test"}'
```
## 3. Response
Deployed `ReturnDefinition`: `{"type":"object","properties":{"Result":{"type":"boolean"},"ResultText":{"type":"string"}},"required":["Result","ResultText"]}`
**HTTP 200 is returned for every business outcome** — success is `Result == true`, never the status
code. `ResultText` values the deployed scripts can produce:
| `Result` | `ResultText` | Produced by |
|---|---|---|
| `true` | echo of `DelmiaReceiver.RecipeProcessResultText` (often `""`) | Galaxy object acknowledged the download |
| `false` | `DelmiaReceiver.RecipeProcessResultText` | Galaxy object rejected the download (`RecipeProcessResult` false) |
| `false` | `MachineCode is required` | central script, blank `MachineCode` |
| `false` | `Receiver ready flag not set to true` | site script, `ReadyFlag` not true (**or unreadable — see §7**) |
| `false` | `Timeout waiting for recipe to be processed` | site script, `RecipeProcessedFlag` not true within 25 s |
| `false` | `RecipeDownload failed: <exception>` | either script — e.g. unknown instance, site unreachable, `Script 'ProcessRecipeDownload' on instance 'X' failed: …` |
## 4. Processing flow
```
Delmia ─► WWNotifier.exe ─► POST /api/DelmiaRecipeDownload (central, active node)
│ inbound method script (id 4): validate MachineCode
▼
Route.To(MachineCode).Call("ProcessRecipeDownload", {5 fields})
│ gRPC central→site, lands on the instance actor
▼
CvdReactor.ProcessRecipeDownload (site Call script) on the composed DelmiaReceiver child:
1. read ReadyFlag → must be true, else "Receiver ready flag not set to true"
2. write RecipeProcessedFlag = false
3. WriteBatchAndWaitAsync({DownloadPath, WorkOrderNumber, PartNumber, JobStepNumber, Username},
trigger RecipeDownloadFlag = true,
wait RecipeProcessedFlag == true, timeout 25 s)
4. read RecipeProcessResult / RecipeProcessResultText → {Result, ResultText}
```
Both scripts as deployed on prod (verbatim):
<details><summary>Central inbound method script (id 4, timeout 45 s)</summary>
```csharp
try {
System.Func<string, object> P = k => Parameters.ContainsKey(k) ? Parameters[k] : null;
var code = (P("MachineCode") as string ?? "").Trim();
if (string.IsNullOrEmpty(code)) return new { Result = false, ResultText = "MachineCode is required" };
var suf = code.Substring(code.Length - 1);
return await Route.To(code).Call("ProcessRecipeDownload", new {
DownloadPath = P("DownloadPath"),
WorkOrderNumber = P("WorkOrderNumber"),
PartNumber = P("PartNumber"),
JobStepNumber = P("JobStepNumber"),
Username = P("Username"),
});
} catch (Exception ex) {
return new { Result = false, ResultText = "RecipeDownload failed: " + ex.Message };
}
```
</details>
<details><summary>Site script <code>CvdReactor.ProcessRecipeDownload</code> (template 1, script id 4, trigger <code>call</code>)</summary>
```csharp
// Generic DELMIA recipe-download — performed DIRECTLY on the composed DelmiaReceiver child
// (mirrors how MesMoveIn writes the MESReceiver child) instead of delegating via CallScript.
// No side logic; the receiver's own DelmiaReceiver.Download method holds the same handshake.
var recv = Children["DelmiaRecv"];
System.Func<object,bool> IsTrue = v => { var s=v?.ToString(); return (v is bool b && b)||s=="1"||string.Equals(s,"true",System.StringComparison.OrdinalIgnoreCase); };
System.Func<string,object?> P = k => Parameters.ContainsKey(k) ? Parameters[k] : null;
if (!IsTrue(recv.Attributes["ReadyFlag"]))
return new { Result=false, ResultText="Receiver ready flag not set to true" };
try {
recv.Attributes["RecipeProcessedFlag"] = false;
var data = new System.Collections.Generic.Dictionary<string, object?> {
{ "DownloadPath", P("DownloadPath") },
{ "WorkOrderNumber", P("WorkOrderNumber") },
{ "PartNumber", P("PartNumber") },
{ "JobStepNumber", P("JobStepNumber") },
{ "Username", P("Username") },
};
if (!await recv.Attributes.WriteBatchAndWaitAsync(data, "RecipeDownloadFlag", true, "RecipeProcessedFlag", true, System.TimeSpan.FromSeconds(25)))
return new { Result=false, ResultText="Timeout waiting for recipe to be processed" };
return new {
Result = IsTrue(recv.Attributes["RecipeProcessResult"]),
ResultText = recv.Attributes["RecipeProcessResultText"]?.ToString() ?? ""
};
} catch (Exception ex) {
return new { Result=false, ResultText="RecipeDownload failed: " + ex.Message };
}
```
</details>
## 5. Galaxy-side contract — the `DelmiaReceiver` template (id 12; composed clone id 26)
All ten attributes are **data-sourced over the site `MxGateway` connection**, bound per instance to the
reactor-level Galaxy object (prod: `DelmiaReceiver_038` on Z28061, `_039` on Z28062, `_037` on
Z28061Sim; `Left_00x.DelmiaReceiver` / `Right_00x.DelmiaReceiver` back the unused side compositions).
| Attribute | Type | Direction | Role in the handshake |
|---|---|---|---|
| `ReadyFlag` | Boolean | Galaxy → SB | Precondition; must be true or the call is refused |
| `RecipeDownloadFlag` | Boolean | SB → Galaxy | **Trigger** — set true after the five data fields are written |
| `RecipeProcessedFlag` | Boolean | both | SB clears to false first; Galaxy sets true when done (waited ≤ 25 s) |
| `RecipeProcessResult` | Boolean | Galaxy → SB | Outcome → `Result` |
| `RecipeProcessResultText` | String | Galaxy → SB | Outcome text → `ResultText` |
| `DownloadPath`, `WorkOrderNumber`, `PartNumber`, `JobStepNumber`, `Username` | String | SB → Galaxy | Payload, written as one batch before the trigger |
## 6. API keys scoped to this method (prod, names only — secrets are shown once at creation)
`mes`, `mes api key`, `delmia-mes-receivers`, `TestKey`, `JOE_TEST_KEY` — all enabled, all also
scoped to the MES methods (`MesMoveIn`, `MesMoveOut`, `MesSampleData`, `SimpleAlarmStatusRequest`,
most also `IpsenMESMoveIn`). `delmia-mes-receivers` is the one whose name says it is the Delmia
caller's key; the audit `actor` column shows which key served each call.
## 7. Observed behaviour and open issues (from the prod audit log, 2026-06-17 → 2026-06-26)
Nine calls total, all test traffic (actors `delmia-mes-receivers`, `delmia-sim-test`), none since
2026-06-26 — **no production Delmia traffic has hit this method yet.** Every 200 answered
`Result=false`: mostly `Receiver ready flag not set to true`, one
`Script 'ProcessRecipeDownload' … The given key 'side' was not present` from an earlier script
revision, and one `MachineCode must end with A (Left) or B (Right)` from a retired left/right variant
(the current script routes on the whole `MachineCode`; the leftover `suf` variable is unused).
1. **Likely broken since the 2026-06-27 rename — verify before go-live.** The site script still
addresses the child as `Children["DelmiaRecv"]`, but the `CvdReactor` composition was renamed
`DelmiaRecv` → `DelmiaReceiver` that day (`../deployment/deployment-records/2026-06-27-wonder-app-vd03.md`
§2b), so the flattened paths are `DelmiaReceiver.*`. `ChildrenAccessor` just concatenates the
name into a path and `GetAttribute` on an unknown path logs a warning and yields null, so
`IsTrue(null)` is false and **every call will answer `Receiver ready flag not set to true`
regardless of the real flag**. No call has been made since the rename, so this is inferred from
the code, not observed. Fix = change that one line to `Children["DelmiaReceiver"]` on the
template (`scadabridge template script update`) and redeploy the three CvdReactor instances;
check QA's copy of the script for the same string.
2. **Not idempotent.** The design requires idempotency on `(MachineCode, DownloadPath, WorkOrderNumber)`
because the notifier retries on timeout/connect failure (at-least-once). The deployed script
re-runs the full handshake on a duplicate, so a retry after a slow first attempt will trigger a
second download on the Galaxy object.
3. `required` is empty in the parameter schema; only `MachineCode` is enforced, in script. Missing
payload fields are written to the receiver as null/empty.
4. QA definitions unread (credentials) — assumed identical (same build lineage), not verified.