Review finding on ab08ecd3: each Good re-armed the watchdog from 'now', so Goods arriving faster than the floor starved the retry. Pinned by FlappingGood_DoesNotDeferTheRetry (12 Goods over 1.2 s; naive re-arm measured 1.43 s, guarded ~0.3 s).
Claude-Session: https://claude.ai/code/session_019ZxXT5sxZs5XrtdwYzJDPV
Task 4 review fix-ups: RepeatedFailures gaps[1] lower bound 600→500 (two compounding jitter draws bottom out at 512 ms); SubscribeToDcl also clears _tagPathToAttributes and its prune is documented as defensive (PreStart is the only caller).
Also from the Task 3 review: FailedSubscribeResponse_IsRetried guards the failure path again (large ceiling); HandleSubscribeTagsResponse reads state instead of get-or-create; SubscribeToDcl prunes stale retry state on re-entry; doc comments refreshed.
Claude-Session: https://claude.ai/code/session_019ZxXT5sxZs5XrtdwYzJDPV
FailedSubscribeResponse_IsRetried and LostSubscribeResponse_IsRetried_AndSuccessStopsRetrying now pin the in-flight ceiling to the retry interval: a lost reply is re-sent only once the outstanding request is presumed lost, by design.
Claude-Session: https://claude.ai/code/session_019ZxXT5sxZs5XrtdwYzJDPV
A caller addressing a standby central node directly (or hitting Traefik inside its
/health/active probe window after a failover) used to get 503 STANDBY_NODE. The
standby now relays the request verbatim to the active peer over HTTP
(IStandbyRequestForwarder / HttpStandbyRequestForwarder) and replays the response;
method scripts and Route.To() still execute only on the active node.
- ScadaBridge:InboundApi:StandbyForwardPeerEndpoints (static list of the OTHER
central node's HTTP base URL; empty = old 503 behaviour) + StandbyForwardTimeout
(60s), both startup-validated.
- Peers tried in order: peer 503 stamped X-ScadaBridge-Standby, connection failure
or timeout → next peer; all fail → 503 ACTIVE_NODE_UNREACHABLE. A 503 without
the marker is the active node's own answer and is replayed.
- One-hop loop guard via X-ScadaBridge-Forwarded; 413 body cap now runs BEFORE
the active-node check so a standby never buffers/relays an oversized body.
- AuditWriteMiddleware skips its own ApiInbound row for a relayed request so a
call is audited once, on the node that executed it.
- Rig + env2 central nodes configured; spec (Component-InboundAPI.md → Standby
forwarding), Component-Host.md options row, CLAUDE.md updated.
- 20 new tests (filter decision + relay mechanics + validator).
Claude-Session: https://claude.ai/code/session_019ZxXT5sxZs5XrtdwYzJDPV
The grouped Connection Bindings panel (77f4af0d) added a per-group
'Apply to n' button, so InstanceConfigureTests' Name = "Apply" role
locator started matching two elements and failing Playwright's strict
mode. Adds data-test="binding-bulk-apply" alongside the existing
binding-bulk-select / binding-group-apply keys and clicks that instead.
Claude-Session: https://claude.ai/code/session_01G2GHPnbbKGvyyfbr2XBRVH
Tasks 4 and 5 of the plan land together: the card's state fields are write-only
until the markup consumes them, and the project treats unused-field warnings as
errors, so neither task builds on its own.
Claude-Session: https://claude.ai/code/session_01G2GHPnbbKGvyyfbr2XBRVH
Row 104: docker/vacuum-site-localdb.sh stops both nodes of a pair together, sets
auto_vacuum=INCREMENTAL + VACUUM on each node volume with integrity_check before/after,
then starts both (DRY_RUN=1 reports). Run on all three rig pairs: six files 0 -> 2, ok,
~11% smaller; site-a replication reconnected with backlog 0 and no watermark change —
VACUUM is replication-invisible (ledger keys by declared PK, oplog seq is INTEGER PRIMARY
KEY AUTOINCREMENT). Topology guide gains the recipe.
Row 105: SiteLocalDbReplicatedTableFkGuardTests builds the real site schema via OnReady
(unreplicated config so 0.3.3's own guard cannot mask the culprit) and asserts every
SiteLocalDbSetup.ReplicatedTables entry (now internal) exists and has no inbound
CASCADE/SET NULL/SET DEFAULT foreign key, with a negative control. The constraint is
enforced at build instead of at the first replicated boot.
Row 106 (found during 104's live verification, NOT caused by it — the identical 127k-row
full snapshot also landed at the earlier deploy restart): SnapshotStreamer.SendAsync stamps
as_of_seq = MAX(seq), which is 0 once a converged sender's oplog is ack-pruned to empty;
a zero-watermark receiver (rebuilt node) is never lifted, so the empty-oplog horizon rule
re-streams a full snapshot on every reconnect. Sender-side one-line fix for LocalDb 0.3.4:
as_of_seq = max(MAX(seq), last_acked_seq).