The standalone design.md, kpi.md, operations.md, and the docs/plan/ phase tree were point-in-time planning artefacts now superseded by the topic-organized docs/ tree (Architecture/, Features/, Operations/, Reference/, Testing/). The DL260/ folder mixed a device-reference doc, a test fixture, a sample test, and a screenshot; its contents now live in their natural homes (dl205.md + mbtcp_settings.JPG under docs/Reference/, dl205.json next to its launcher in tests/sim/, sample test dropped). All cross-references in the surviving docs, README, CLAUDE.md, the config template, and source comments are repointed to the new locations. Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
13 KiB
CLAUDE.md
This file provides guidance to Claude Code (claude.ai/code) when working with code in this repository.
What this is
mbproxy is a C# .NET 10 background service (Windows Service) that sits inline as a Modbus TCP proxy in front of a fleet of ~54 AutomationDirect DirectLOGIC DL205 / DL260 equipment controllers. It is pre-configured with two pieces of static data:
- A list of BCD tags — the holding/input registers (by Modbus address and bit width) that the controllers store in DirectLOGIC's native BCD encoding (
V2000 = 1234is stored on the wire as0x1234, not0x04D2). - A list of equipment controller IP addresses (~54 entries) for the DL205/DL260 fleet. Each controller speaks Modbus TCP on port 502 via either the built-in DL260 Ethernet port or an H2-ECOM100 / H2-EBC100 coprocessor.
Purpose: bidirectional BCD rewrite inline on the MBTCP stream
The service is a transparent-by-default Modbus TCP proxy whose job is to rewrite the configured BCD tags in real time, in both directions, while proxying every other byte of the MBTCP connection untouched. Since Phase 11 the proxy also exposes an opt-in per-tag response cache (default OFF, opt-in by setting BcdTagOptions.CacheTtlMs > 0); with caching enabled the proxy is no longer purely transparent — upstream reads may return a value up to CacheTtlMs milliseconds old.
- Upstream read path (client → PLC → client). When a client reads a register on the BCD tag list, the proxy intercepts the PLC's response and rewrites the raw BCD nibbles (
0x1234) into the binary integer the client expects (0x04D2= decimal 1234) before forwarding. 32-bit BCD values that span the CDAB word pair are rewritten as a unit. - Downstream write path (client → PLC). When a client writes a register on the BCD tag list, the proxy intercepts the request and re-encodes the client's binary integer (
0x04D2) into BCD nibbles (0x1234) before forwarding to the PLC, so the value the operator sees in ladder matches what the client wrote. - Everything else passes through unchanged. Non-BCD registers, coils, discrete inputs, function codes the service doesn't touch (diagnostics, exception responses, etc.) are forwarded byte-for-byte. MBAP transaction IDs and unit IDs are preserved end-to-end so the proxy is invisible to both sides.
The integration win is that upstream consumers (Wonderware / Historian / OPC UA gateways / generic Modbus clients) can read and write the configured BCD tags as if they were plain Int16/Int32, and the proxy is the only place that has to know which registers are BCD.
Architecture
The full architecture is documented under docs/ — see the Architecture/, Features/, Operations/, Reference/, and Testing/ pages. Headline choices the agent should keep in mind without opening those files:
- One
TcpListenerper PLC (54 distinct ports). Each PLC has one shared backend socket owned by aPlcMultiplexer; many upstream clients are multiplexed onto that single backend via MBAP TxId rewriting (Phase 9). The H2-ECOM100's 4-client cap no longer caps upstream connections. - Transparent by default; opt-in cached (Phase 11). Every byte passes through unchanged except the MBAP TxId field (rewritten by the multiplexer on each request and restored on each response) and FC03/FC04 response payloads + FC06/FC16 request payloads at configured BCD addresses (re-encoded between BCD nibbles and binary integers). With Phase 11, FC03/FC04 reads for tags whose
CacheTtlMs > 0may be served from a per-PLC in-process cache without backend traffic; the cache is OFF by default per tag. - In-flight FC03/FC04 read coalescing (Phase 10): same-key reads arriving while a peer is in flight attach to the existing
InFlightRequest.InterestedPartieslist; the single backend response fans out to every attached client with original TxIds restored. Zero post-response staleness — coalescing entries die when the response arrives. Hot-reload viaMbproxy.Resilience.ReadCoalescing.Enabled. - Optional response cache (Phase 11) with per-tag TTL (default 0 = off). Lookup order is cache → coalesce → backend: a cache hit short-circuits Phase 10's coalescing path entirely. Multi-tag read range: effective TTL =
min(TTLs); any tag withCacheTtlMs = 0in the range disables caching for the whole read. Successful FC06/FC16 write responses invalidate cached FC03/FC04 entries whose address range overlaps the write. Cache stores POST-rewriter bytes (hits never re-invoke the rewriter). No persistence — process restart wipes the cache.Cache.AllowLongTtl = trueis required for anyCacheTtlMs > 60_000. - Polly-backed listener supervisor auto-recovers any listener that fails to bind at startup or faults at runtime; the same code path also brings up newly-added PLCs from hot-reload and tears down removed ones.
appsettings.jsonis hot-reloadable viaIOptionsMonitor<MbproxyOptions>; tag-list changes propagate per-PDU, PLC add/remove flows through the supervisor. A tag-list reload flushes the affected PLC's response cache (per-tag granularity intentionally not done in v1).- Polly bounded retries on backend connect (3 attempts at 100ms / 500ms / 2000ms). No retries on mid-request failures (FC06/FC16 are non-idempotent on BCD tags). A per-request watchdog in the multiplexer surfaces Modbus exception 0x0B to the upstream client if a backend response never arrives within
BackendRequestTimeoutMs. - Backend disconnect cascades upstream: when the shared backend socket dies, every attached upstream pipe is closed in the same cycle (counter
BackendDisconnectCascades); clients reconnect on their next request. - Read-only Kestrel admin port (default 8080) exposes
GET /(auto-refreshing HTML) andGET /status.jsonwith service-wide and per-PLC counters (including Phase-9 mux fields, Phase-10 coalescing fields, and Phase-11 cache fieldscacheHitCount,cacheMissCount,cacheInvalidations,cacheEntryCount,cacheBytes).
Anything beyond this short list lives in the docs/ tree: the appsettings.json schema in docs/Operations/Configuration.md, config propagation in docs/Features/HotReload.md, stable log event names in docs/Reference/LogEvents.md, the status counter catalog in docs/Operations/StatusPage.md, and the simulator-backed test fixture in docs/Testing/Simulator.md. Open the relevant page before writing code; keep it in sync when decisions change.
Current state
Implementation complete through Phase 11. Phases 00–08 shipped the production-ready 1:1-model service; Phase 9 swapped the connection layer for the TxId-multiplexed model; Phase 10 added in-flight read coalescing on top; Phase 11 added an opt-in per-tag response cache (bounded staleness, OFF by default — see docs/Architecture/ResponseCache.md). The service is production-ready as a Windows Service:
- Test count grew through Phase 11 (see
tests/Mbproxy.Tests/for the current suite; previous baseline was 325 = 282 unit + 43 E2E). - Single-file self-contained publish (
dotnet publish -c Release -r win-x64). - PowerShell install/uninstall scripts under
install/. - Graceful shutdown with configurable drain timeout (
Connection.GracefulShutdownTimeoutMs, default 10 s). - Windows Event Log integration (Error+ events when running as a service).
- Read-only HTTP status page at
AdminPort(default 8080) — surfaces Phase-9 mux fields alongside Phase-7 counters. connectsSuccess/connectsFailedcounters wired inPlcMultiplexer.- Phase 9 per-request watchdog defends against any backend that drops or mis-echoes a response (real-world packet loss; pymodbus 3.13 simulator's concurrent-multiplexed-request bug).
AssemblyInformationalVersionset to1.0.0(CI can override via/p:InformationalVersion=...).
The human-facing entry point is README.md. All design decisions live in the docs/ tree.
Constraints that still apply to this codebase (do not change without updating the relevant docs/ page):
- The csproj targets .NET 10 (
net10.0). This is the only tool inwwtools/not pinned to .NET Framework 4.8 / x86.
Device quirks (read before writing Modbus code)
The DL205/DL260 family is almost Modbus-spec-compliant, but every category below has at least one trap. The authoritative reference is docs/Reference/dl205.md — read it end-to-end before touching the wire protocol. Highlights that bear directly on this proxy:
- BCD-by-default numeric encoding.
V2000 = 1234stores0x1234on the wire, not0x04D2. This is the entire reason this service exists. - CDAB word order for 32-bit values. Low word first, big-endian bytes within each word.
0xAABBCCDDlands as[0xCC 0xDD][0xAA 0xBB]. - Octal V-memory ↔ decimal Modbus translation.
V2000octal = decimal 1024 = Modbus PDU0x0400. Config addresses are PDU-decimal, not octal V-memory and not 1-based 4xxxx. - FC03/FC04 max qty = 128 (above spec's 125). FC16 max qty = 100 (below spec's 123). The proxy passes these through; the PLC enforces the cap with exception 03.
- Max 4 concurrent TCP clients per ECOM100. This is why the proxy uses a single TxId-multiplexed backend socket per PLC — see
docs/Architecture/ConnectionModel.mdfor how the connection model lifts this cap. - No TCP keepalive from the device. Middleboxes typically drop idle sockets at 2–5 min. With the 1:1 model, backend liveness tracks upstream client liveness; if both are idle long enough, the path dies on its own and the next request reconnects.
- Register 0 is valid on DL205/DL260 in factory "absolute" addressing mode — don't probe-skip it.
- As-deployed PLC parameters (captured in
docs/Reference/mbtcp_settings.JPG): port 502, "Use Concept data structures (Longs/Reals)" enabled, "Swap bytes" enabled, "Use Zero Based Addressing" unchecked, Register type = Binary, max coil read 1976 / coil write 800 / register read 122 / register write 100. The proxy must speak Modbus as-is; these settings describe the wire it'll see.
Resource index
| Task | Go to |
|---|---|
| Architecture — listener topology, request flow, per-PLC isolation | docs/Architecture/Overview.md |
| Connection model — single backend socket per PLC, TxId multiplexing, request-timeout watchdog, disconnect cascade | docs/Architecture/ConnectionModel.md |
| In-flight read coalescing / opt-in response cache | docs/Architecture/ReadCoalescing.md, docs/Architecture/ResponseCache.md |
| BCD rewriting (codec, CDAB word order, FC03/04/06/16 scope) and config hot-reload | docs/Features/BcdRewriting.md, docs/Features/HotReload.md |
| Operations — full appsettings.json reference, status page / JSON fields, troubleshooting playbook | docs/Operations/Configuration.md, docs/Operations/StatusPage.md, docs/Operations/Troubleshooting.md |
Stable mbproxy.* log event-name catalog |
docs/Reference/LogEvents.md |
| DL205/DL260 Modbus quirks (BCD, CDAB, octal V-memory, FC limits, exception codes, oddities) | docs/Reference/dl205.md |
| pymodbus simulator profile that models those quirks as concrete register values | tests/sim/dl205.json |
| As-deployed PLC Modbus parameters screenshot | docs/Reference/mbtcp_settings.JPG |
Maintenance
Documentation doctrine for wwtools/ lives in ../DOCS-GUIDE.md. The three-layer rules apply:
README.mdis the canonical human entry point (Layer-2 per DOCS-GUIDE). It routes to deep docs; it does not duplicate them. Update it when the service's public surface or install steps change.- This
CLAUDE.mdstays a router for LLM coding agents. Deep design decisions live in thedocs/tree; device quirks live indocs/Reference/dl205.md. When you change a design decision, update the relevant page underdocs/first (it's the source of truth) and only mirror the change into the Architecture summary above if it shifts one of the headline bullets. - When the service's task→tool mapping changes in the root index, update
../CLAUDE.mdtoo. - Any further design changes belong in the relevant
docs/page (Architecture/,Features/,Operations/,Reference/, orTesting/).