Fixes every finding from the codereviews/2026-05-16 multi-agent review
(2 Critical, 20 Major, 38 Minor) and adds that review to the repo.
Highlights: dashboard XSS escape; response cache invalidated on the
write request (not just the response); ReloadValidator now runs at
startup so port collisions / duplicate names / malformed Resilience
profiles fail fast; AdminPort 0 genuinely disables the admin endpoint;
PlcListener accept-loop faults propagate to the supervisor's faulted
path; reconciler Restart builds before removing; Resilience pipelines
are restart-only from a frozen snapshot; multiplexer connect-race leak,
watchdog party-list snapshot, backend-response and FC16 framing
validation; frontend reconnect retry and util.js load guard; plus the
log-event/doc drift sweep and test-port hygiene.
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
Comments described the *history* of how the code arrived (phase numbers,
wave IDs, review IDs, dated TODOs) instead of what it does today. That
scaffolding rotted as the codebase evolved. Cleaned 60 source files +
.gitignore; behaviour unchanged (387/387 tests still pass).
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
Adds the mbproxy service end-to-end. Phases 00-08 implement the
production-ready single-listener / 1:1-backend transparent Modbus TCP
proxy with bidirectional BCD rewriting for the ~54-PLC DL205/DL260
fleet. Phase 9 replaces the connection layer with a single backend
socket per PLC plus MBAP TxId rewriting, lifting the H2-ECOM100's
4-concurrent-client cap as an operational ceiling.
Phase 9 additions of note:
- PlcMultiplexer + UpstreamPipe + TxIdAllocator + CorrelationMap
- InFlightRequest with IReadOnlyList<InterestedParty> (load-bearing
for Phase 10 read coalescing — do not collapse to a single field)
- Per-request watchdog: surfaces Modbus exception 0x0B to upstream
on BackendRequestTimeoutMs, defending against lost responses,
dead-PLC paths, and pymodbus 3.13.0's concurrent-multiplexed-
request bug (its ServerRequestHandler.last_pdu state race)
- Status DTO + HTML gain inFlight / maxInFlight / txIdWraps /
disconnectCascades / queueDepth (Tier 1.6 in docs/kpi.md)
Tests: 263 unit + 38 E2E. Multiplexer correctness under truly
concurrent backend traffic is proved against a stub backend in
PlcMultiplexerTests; MultiplexerE2ETests paces requests so pymodbus
3.13's single-PDU framer stays in known-good mode.