mbproxy/docs: retire superseded design/plan docs and dissolve DL260/
The standalone design.md, kpi.md, operations.md, and the docs/plan/ phase tree were point-in-time planning artefacts now superseded by the topic-organized docs/ tree (Architecture/, Features/, Operations/, Reference/, Testing/). The DL260/ folder mixed a device-reference doc, a test fixture, a sample test, and a screenshot; its contents now live in their natural homes (dl205.md + mbtcp_settings.JPG under docs/Reference/, dl205.json next to its launcher in tests/sim/, sample test dropped). All cross-references in the surviving docs, README, CLAUDE.md, the config template, and source comments are repointed to the new locations. Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
This commit is contained in:
@@ -0,0 +1,269 @@
|
||||
# AutomationDirect DirectLOGIC DL205 / DL260 — Modbus quirks
|
||||
|
||||
AutomationDirect's DirectLOGIC DL205 family (D2-250-1, D2-260, D2-262, D2-262M) and
|
||||
its larger DL260 sibling speak Modbus TCP (via the H2-ECOM100 / H2-EBC100 Ethernet
|
||||
coprocessors, and the DL260's built-in Ethernet port) and Modbus RTU (via the CPU
|
||||
serial ports in "Modbus" mode). They are mostly spec-compliant, but every one of
|
||||
the following categories has at least one trap that a textbook Modbus client gets
|
||||
wrong: octal V-memory to decimal Modbus translation, non-IEEE "BCD-looking" default
|
||||
numeric encoding, CDAB word order for 32-bit values, ASCII character packing that
|
||||
the user flagged as non-standard, and sub-spec maximum-register limits on the
|
||||
Ethernet modules. This document catalogues each quirk, cites primary sources, and
|
||||
names the ModbusPal integration test we'd write for it (convention from
|
||||
`docs/v2/modbus-test-plan.md`: `DL205_<behavior>`).
|
||||
|
||||
## Strings
|
||||
|
||||
DirectLOGIC does not have a first-class Modbus "string" type; strings live inside
|
||||
V-memory as consecutive 16-bit registers, and the CPU's string instructions
|
||||
(`PRINTV`, `VPRINT`, `ACON`/`NCON` in ladder) read/write them in a specific layout
|
||||
that a naive Modbus client will byte-swap [1][2].
|
||||
|
||||
- **Packing**: two ASCII characters per V-memory register (two per holding
|
||||
register). The *first* character of the pair occupies the **low byte** of the
|
||||
register, the *second* character occupies the **high byte** [2]. This is the
|
||||
opposite of the big-endian Modbus convention that Kepware / Ignition / most
|
||||
generic drivers assume by default, so strings come back with every pair of
|
||||
characters swapped (`"Hello"` reads as `"eHll o\0"`).
|
||||
- **Termination**: null-terminated (`0x00` in the character byte). There is no
|
||||
length prefix. Writes must pad the final register's unused byte with `0x00`.
|
||||
- **Byte order within the register**: little-endian for character data, even
|
||||
though the same CPU stores **numeric** V-memory values big-endian on the wire.
|
||||
This mixed-endianness is the single most common reason DL-series strings look
|
||||
corrupted in a generic HMI. Kepware's DirectLogic driver exposes a per-tag
|
||||
"String Byte Order = Low/High" toggle specifically for this [3].
|
||||
- **K-memory / KSTR**: DirectLOGIC does **not** expose a dedicated `KSTR` string
|
||||
address space — K-memory on these CPUs is scratch bit/word memory, not a string
|
||||
pool. Strings live wherever the ladder program allocates them in V-memory
|
||||
(typically user V2000-V7777 octal on DL260, V2000-V3777 on DL205 D2-260) [2].
|
||||
- **Maximum length**: bounded only by the V-memory region assigned. The `VPRINT`
|
||||
instruction allows up to 128 characters (64 registers) per call [2]; larger
|
||||
strings require multiple reads.
|
||||
- **V-memory interaction**: an "address a string at V2000 of length 20" tag is
|
||||
really "read 10 consecutive holding registers starting at the Modbus address
|
||||
that V2000 translates to (see next section), unpack each register low-byte
|
||||
then high-byte, stop at the first `0x00`."
|
||||
|
||||
Test names:
|
||||
`DL205_String_low_byte_first_within_register`,
|
||||
`DL205_String_null_terminator_stops_read`,
|
||||
`DL205_String_write_pads_final_byte_with_zero`.
|
||||
|
||||
## V-Memory Addressing
|
||||
|
||||
DirectLOGIC addresses are **octal**; Modbus addresses are **decimal**. The CPU's
|
||||
internal Modbus server performs the translation, but the formulas differ per
|
||||
CPU family and are 1-based in the "Modicon 4xxxx" form vs 0-based on the wire
|
||||
[4][5].
|
||||
|
||||
Canonical DL260 / DL250-1 mapping (from the D2-USER-M appendix and the H2-ECOM
|
||||
manual) [4][5]:
|
||||
|
||||
```
|
||||
V-memory (octal) Modicon 4xxxx (1-based) Modbus PDU addr (0-based)
|
||||
V0 (user) 40001 0x0000
|
||||
V1 40002 0x0001
|
||||
V2000 (user) 41025 0x0400
|
||||
V7777 (user) 44096 0x0FFF
|
||||
V40400 (system) 48449 0x2100
|
||||
V41077 ~8848 (read-only status)
|
||||
```
|
||||
|
||||
Formula: `Modbus_0based = octal_to_decimal(Vaddr)`. So `V2000` octal = `1024`
|
||||
decimal = Modbus PDU address `0x0400`. The "4xxxx" Modicon view just adds 1 and
|
||||
prefixes the register bank digit.
|
||||
|
||||
- **V40400 is the Modbus starting offset for system registers on the DL260**;
|
||||
its 0-based PDU address is `0x2100` (decimal 8448), not 0. The widespread
|
||||
"V40400 = register 0" shorthand is wrong on modern firmware — that was true
|
||||
on the older DL05/DL06 when the ECOM module was configured in "relative"
|
||||
addressing mode. On the H2-ECOM100 factory default ("absolute" mode), V40400
|
||||
maps to 0x2100 [5].
|
||||
- **DL205 (D2-260) vs DL260 differences**:
|
||||
- DL205 D2-260 user V-memory: V1400-V7377 and V10000-V17777 octal.
|
||||
- DL260 user V-memory: V1400-V7377, V10000-V35777, and V40000-V77777 octal
|
||||
(much larger) [4].
|
||||
- DL205 D2-262 / D2-262M adds the same extended V-memory as DL260 but
|
||||
retains the DL205 I/O base form factor.
|
||||
- Neither DL205 sub-model changes the *formula* — only the valid range.
|
||||
- **Bit-in-V-memory (C, X, Y relays)**: control relays `C0`-`C1777` octal live
|
||||
in V40600-V40677 (DL260) as packed bits; the Modbus server exposes them *both*
|
||||
as holding-register bits (read the whole word and mask) *and* as Modbus coils
|
||||
via FC01/FC05 at coil addresses 3072-4095 (0-based) [5]. `X` inputs map to
|
||||
Modbus discrete inputs starting at FC02 address 0; `Y` outputs map to Modbus
|
||||
coils starting at FC01/FC05 address 2048 (0-based) on the DL260.
|
||||
- **Off-by-one gotcha**: the AutomationDirect manuals use the 1-based 4xxxx
|
||||
form. Kepware, libmodbus, pymodbus, and the .NET stack all take the 0-based
|
||||
PDU form. When the manual says "V2000 = 41025" you send `0x0400`, not
|
||||
`0x0401`.
|
||||
|
||||
Test names:
|
||||
`DL205_Vmem_V2000_maps_to_PDU_0x0400`,
|
||||
`DL260_Vmem_V40400_maps_to_PDU_0x2100`,
|
||||
`DL260_Crelay_C0_maps_to_coil_3072`.
|
||||
|
||||
## Word Order (Int32 / UInt32 / Float32)
|
||||
|
||||
DirectLOGIC CPUs store 32-bit values across **two consecutive V-memory words,
|
||||
low word first** — i.e., `CDAB` when viewed as a Modbus register pair [1][3].
|
||||
Within each word, bytes are big-endian (high byte of the word in the high byte
|
||||
of the Modbus register), so the full wire layout for a 32-bit value `0xAABBCCDD`
|
||||
is:
|
||||
|
||||
```
|
||||
Register N : 0xCC 0xDD (low word, big-endian bytes)
|
||||
Register N+1 : 0xAA 0xBB (high word, big-endian bytes)
|
||||
```
|
||||
|
||||
- This is the same "little-endian word / big-endian byte" layout Kepware calls
|
||||
`Double Word Swapped` and Ignition calls `CDAB` [3][6].
|
||||
- **DL205 and DL260 agree** — the convention is a CPU-level choice, not a
|
||||
module choice. The H2-ECOM100 and H2-EBC100 do **not** re-swap; they're pure
|
||||
Modbus-TCP-to-backplane bridges [5]. The DL260 built-in Ethernet port
|
||||
behaves identically.
|
||||
- **Float32**: IEEE 754 single-precision, but only when the ladder explicitly
|
||||
uses the `R` (real) data type. DirectLOGIC's default numeric storage is
|
||||
**BCD** — `V2000 = 1234` in ladder stores `0x1234` on the wire, not `0x04D2`.
|
||||
A Modbus client reading what the operator sees as "1234" gets back a raw
|
||||
register value of `0x1234` and must BCD-decode it. Float32 values are only
|
||||
IEEE 754 if the ladder programmer used `LDR`/`OUTR` instructions [1].
|
||||
- **Operator-reported**: on very old D2-240 firmware (predecessor, not in our
|
||||
target set) the word order was `ABCD`, but every DL205/DL260 firmware
|
||||
released since 2004 is `CDAB` [3]. _Unconfirmed_ whether any field-deployed
|
||||
DL205 still runs pre-2004 firmware.
|
||||
|
||||
Test names:
|
||||
`DL205_Int32_word_order_is_CDAB`,
|
||||
`DL205_Float32_IEEE754_roundtrip_when_ladder_uses_R_type`,
|
||||
`DL205_BCD_register_decodes_as_hex_nibbles`.
|
||||
|
||||
## Function Code Support
|
||||
|
||||
The Hx-ECOM / Hx-EBC modules and the DL260 built-in Ethernet port implement the
|
||||
following Modbus function codes [5][7]:
|
||||
|
||||
| FC | Name | Supported | Max qty / request |
|
||||
|----|-----------------------------|-----------|-------------------|
|
||||
| 01 | Read Coils | Yes | 2000 bits |
|
||||
| 02 | Read Discrete Inputs | Yes | 2000 bits |
|
||||
| 03 | Read Holding Registers | Yes | **128** (not 125) |
|
||||
| 04 | Read Input Registers | Yes | 128 |
|
||||
| 05 | Write Single Coil | Yes | 1 |
|
||||
| 06 | Write Single Register | Yes | 1 |
|
||||
| 15 | Write Multiple Coils | Yes | 800 bits |
|
||||
| 16 | Write Multiple Registers | Yes | **100** |
|
||||
| 07 | Read Exception Status | Yes (RTU) | — |
|
||||
| 17 | Report Server ID | No | — |
|
||||
|
||||
- **FC03/FC04 limit is 128**, which is above the Modbus spec's 125. Requesting
|
||||
129+ returns exception code `03` (Illegal Data Value) [5].
|
||||
- **FC16 limit is 100**, below the spec's 123. This is the most common source of
|
||||
"works in test, fails in bulk-write production" bugs — our driver should cap
|
||||
at 100 when the device profile is DL205/DL260.
|
||||
- **No custom function codes** are exposed on the Modbus port. AutomationDirect's
|
||||
native "K-sequence" protocol runs on the serial port when the CPU is set to
|
||||
`K-sequence` mode, *not* `Modbus` mode, and over TCP only via the H2-EBC100's
|
||||
proprietary Ethernet/IP-like protocol — not Modbus [7].
|
||||
|
||||
Test names:
|
||||
`DL205_FC03_129_registers_returns_IllegalDataValue`,
|
||||
`DL205_FC16_101_registers_returns_IllegalDataValue`,
|
||||
`DL205_FC17_ReportServerId_returns_IllegalFunction`.
|
||||
|
||||
## Coils and Discrete Inputs
|
||||
|
||||
DL260 mapping (0-based Modbus addresses) [5]:
|
||||
|
||||
| DL memory | Octal range | Modbus table | Modbus addr (0-based) |
|
||||
|-----------|-----------------|-------------------|-----------------------|
|
||||
| X inputs | X0-X777 | Discrete Input | 0 - 511 |
|
||||
| Y outputs | Y0-Y777 | Coil | 2048 - 2559 |
|
||||
| C relays | C0-C1777 | Coil | 3072 - 4095 |
|
||||
| SP specials | SP0-SP777 | Discrete Input | 1024 - 1535 (RO) |
|
||||
|
||||
- **C0 → coil address 3072 (0-based) = 13073 (1-based Modicon)**. Y0 → coil
|
||||
2048 = 12049. These offsets are wired into the CPU and cannot be remapped.
|
||||
- **Reading a non-populated X input** (no physical module in that slot) returns
|
||||
**zero**, not an exception. The CPU sizes the discrete-input table to the
|
||||
configured I/O, not the installed hardware. Confirmed in the DL260 user
|
||||
manual's I/O configuration chapter [4].
|
||||
- **Writing Y outputs on an output point that's forced in ladder**: the CPU
|
||||
accepts the write and silently ignores it (the force wins). No exception is
|
||||
returned. _Operator-reported_, matches Kepware driver release notes [3].
|
||||
|
||||
Test names:
|
||||
`DL205_C0_maps_to_coil_3072`,
|
||||
`DL205_Y0_maps_to_coil_2048`,
|
||||
`DL205_Xinput_unpopulated_reads_as_zero`.
|
||||
|
||||
## Register Zero
|
||||
|
||||
The DL260's H2-ECOM100 **accepts FC03 at register 0** and returns the contents
|
||||
of `V0`. This contradicts a widespread internet claim that "DirectLOGIC rejects
|
||||
register 0" — that rumour stems from older DL05/DL06 CPUs in *relative*
|
||||
addressing mode, where V40400 was mapped to register 0 and registers below
|
||||
40400 were invalid [5][3]. On DL205/DL260 with the ECOM module in its factory
|
||||
*absolute* mode, register 0 is valid user V-memory.
|
||||
|
||||
- Our driver's `ModbusProbeOptions.ProbeAddress` default of 0 is therefore
|
||||
**safe** for DL205/DL260; operators don't need to override it.
|
||||
- If the module is reconfigured to "relative" addressing (a historical
|
||||
compatibility mode), register 0 then maps to V40400 and is still valid but
|
||||
means something different. The probe will still succeed.
|
||||
|
||||
Test name: `DL205_FC03_register_0_returns_V0_contents`.
|
||||
|
||||
## Exception Codes
|
||||
|
||||
DL205/DL260 returns only the standard Modbus exception codes [5]:
|
||||
|
||||
| Code | Name | When |
|
||||
|------|------------------------|-------------------------------------------------|
|
||||
| 01 | Illegal Function | FC not in supported list (e.g., FC17) |
|
||||
| 02 | Illegal Data Address | Register outside mapped V-memory / coil range |
|
||||
| 03 | Illegal Data Value | Quantity > 128 (FC03/04), > 100 (FC16), > 2000 (FC01/02), > 800 (FC15) |
|
||||
| 04 | Server Failure | CPU in PROGRAM mode during a protected write |
|
||||
|
||||
- **No proprietary exception codes** (06/07/0A/0B are not used).
|
||||
- **Write to a write-protected bit** (CPU password-locked or bit in a force
|
||||
list): returns `02` (Illegal Data Address) on newer firmware, `04` on older
|
||||
firmware [3]. _Unconfirmed_ which firmware revision the transition happened
|
||||
at; treat both as "not writable" in the driver's status-code mapping.
|
||||
- **Read of a write-only register**: there are no write-only registers in the
|
||||
DL-series Modbus map. Every writable register is also readable.
|
||||
|
||||
Test names:
|
||||
`DL205_FC03_unmapped_register_returns_IllegalDataAddress`,
|
||||
`DL205_FC06_in_ProgramMode_returns_ServerFailure`.
|
||||
|
||||
## Behavioral Oddities
|
||||
|
||||
- **Transaction ID echo**: the H2-ECOM100 and DL260 built-in port reliably
|
||||
echo the MBAP TxId on every response, across firmware revisions from 2010+.
|
||||
The rumour that "DL260 drops TxId under load" appears on the AutomationDirect
|
||||
support forum but is _unconfirmed_ and has not reproduced on our bench; it
|
||||
may be a user-software issue rather than firmware [8]. Our driver's
|
||||
single-flight + TxId-match guard handles it either way.
|
||||
- **Concurrency**: the ECOM serializes requests internally. Opening multiple
|
||||
TCP sockets from the same client does not parallelize — the CPU scans the
|
||||
Ethernet mailbox once per PLC scan (typically 2-10 ms) and processes one
|
||||
request per scan [5]. High-frequency polling from multiple clients
|
||||
multiplies scan overhead linearly; keep poll rates conservative.
|
||||
- **Partial-frame disconnect recovery**: the ECOM's TCP stack closes the
|
||||
socket on any malformed MBAP header or any frame that exceeds the declared
|
||||
PDU length. It does not resynchronize mid-stream. The driver must detect
|
||||
the half-close, reconnect, and replay the last request [5].
|
||||
- **Keepalive**: the ECOM does **not** send TCP keepalives. An idle socket
|
||||
stays open on the PLC side indefinitely, but intermediate NAT/firewall
|
||||
devices often drop it after 2-5 minutes. Driver-side keepalive or
|
||||
periodic-probe is required for reliable long-lived subscriptions.
|
||||
- **Maximum concurrent TCP clients**: H2-ECOM100 accepts up to **4 simultaneous
|
||||
TCP connections**; the 5th is refused at TCP accept [5]. This matters when
|
||||
an HMI + historian + engineering workstation + our OPC UA gateway all want
|
||||
to talk to the same PLC.
|
||||
|
||||
Test names:
|
||||
`DL205_TxId_preserved_across_burst_of_50_requests`,
|
||||
`DL205_5th_TCP_connection_refused`,
|
||||
`DL205_socket_closes_on_malformed_MBAP`.
|
||||
|
||||