docs(index): OtOpcUa #717 Warm redundancy implemented default-off (f817c77e)

Claude-Session: https://claude.ai/code/session_01GT67ACmpMR7b9LGRPLijMi
This commit is contained in:
Joseph Doherty
2026-11-13 03:45:46 -05:00
parent d5cb6ba2c0
commit ee9b403c4f
2 changed files with 26 additions and 1 deletions
@@ -606,3 +606,28 @@ Owner-approved; WinRM only for the pack's on-box steps. Pack `docs/deploy/2026-1
QA `E:\psrem-stage\otopcua-c9640f5c\rollback.ps1` per node (prev `app\..\app.bak.20261113-pre-c9640f5c`). DB `.bak`s on both SQL servers. QA `E:\psrem-stage\otopcua-c9640f5c\rollback.ps1` per node (prev `app\..\app.bak.20261113-pre-c9640f5c`). DB `.bak`s on both SQL servers.
- **ScadaBridge consumer impact: none on DEV/QA** (no OPC UA link). Elsewhere: see the pack §1. Galaxy Pending/Warning now reads Uncertain - **ScadaBridge consumer impact: none on DEV/QA** (no OPC UA link). Elsewhere: see the pack §1. Galaxy Pending/Warning now reads Uncertain
(#872), and an out-of-namespace credential ref no longer connects (#834). (#872), and an out-of-namespace credential ref no longer connects (#834).
### 2026-11-13 — #717 Warm non-transparent redundancy implemented, default-off (master `8667ce58`, `7829b937`, `f817c77e`)
Owner adopted the T0-proven first-delivery mechanism (SDK 2.0.1 clones every Publish/Republish and pools payloads, so the
object-keyed design failed T0): a decision record keyed by `(SubscriptionId, SequenceNumber)` and an `OrdinaryTagMarker`
on `MonitoredItemNotification.Message` validated by `(ClientHandle, DataValue)`; the SDK's cached copy is never mutated.
- **`OpcUa:Redundancy:Mode`**: `Unset` (default) is today's server exactly; `None` advertises `RedundancySupport=None` and
deletes the SDK's orphan `i=11314` (readable by NodeId under `Unset`, which is left as is and documented); `Warm` installs
`NonTransparentRedundancyType` + read-only `ServerUriArray [self, peers]`, boot SL 1, Standby 90/50, Active 250/200/100.
`Hot`/unknown fail start; `Warm` needs distinct peers, the effective self URI not listed, and the driver role.
- **Warm Standby**: ordinary-tag values `BadOutOfService`/null (acquisition continues), writes and Part 9 methods
`BadInvalidState`, new alarm events suppressed but stamped (refresh returns retained conditions), promotion runs a
ConditionRefresh2 on every live event item; transitions in the spec §4.7 order (Active level last, Standby level first).
- **Ordered snapshots**: `RedundancyStateChanged.Revision` (up-number via reflection — `Member.UpNumber` is internal in
Akka.NET — incarnation tick, sequence); under Warm `OpcUaPublishActor`/`DriverHostActor` drop older revisions; an
unrevisioned snapshot never makes a Warm node Active (upgrade both pair nodes before flipping).
- **Tests**: 23 Warm wire tests, 23 unit (incl. the SDK-field regression pin), 81 ControlPlane (revision + band table),
16 Runtime actor/verdict, 11 validator. Full Server/Runtime/ControlPlane/Host and both integration projects green;
12 mutations (revision ordering ×2, alarm suppression, transition order ×2, decision record ×4, write/scripted/native
refusals, read projection) all killed.
- **Not done**: T13 docker-dev pair gate (overlay `docker-dev/docker-compose.warm.yml` ready; the shared rig was not
touched); real 2-node handover test. **ScadaBridge consumer impact: none until a tier sets `Warm`** — that is gated on
ScadaBridge#138 (ServiceLevel-aware failover) being deployed, because a Warm Standby serves Bad data on a healthy session.
+1 -1
View File