Conditional and Expression script triggers gain an optional `mode` field in their TriggerConfiguration JSON: - OnTrue (default): unchanged edge/per-change firing. An absent mode field parses as OnTrue, so every existing trigger config behaves identically. - WhileTrue: fires on the false->true edge, then re-fires on a periodic timer while the condition holds; stops on the true->false edge. The re-fire cadence is the script's MinTimeBetweenRuns; with none configured the trigger degrades to a single edge fire and logs a warning. ScriptActor tracks condition truth state and manages a dedicated "whiletrue-trigger" timer. ScriptTriggerConfigCodec and ScriptTriggerEditor round-trip the mode and expose an OnTrue/WhileTrue selector for the two trigger kinds. Design: docs/plans/2026-05-18-whiletrue-trigger-mode-design.md Tests: 7 ScriptActor runtime tests (edge fire, timer re-fire, stop, re-arm, no-MinTimeBetweenRuns degrade, OnTrue regressions) + 14 codec / editor tests. SiteRuntime suite 206 green, CentralUI suite 295 green.