Stand up local dev infrastructure (OPC UA, LDAP, MS SQL) with Docker Compose, Python CLI tools for service interaction, and teardown script. Fix GLAuth config mount, OPC PLC node format, and document actual DN/namespace behavior discovered during testing. Resolve Q1-Q8,Q10: .NET 10, Akka.NET 1.5.x, monorepo with slnx, appsettings JWT, Windows Server 2022 site target.
3.6 KiB
Test Infrastructure: OPC UA Server
Overview
The test OPC UA server uses Azure IoT OPC PLC, a simulated OPC UA server that generates realistic data. It is configured with custom nodes that match ScadaLink attribute patterns.
Image & Ports
- Image:
mcr.microsoft.com/iotedge/opc-plc:latest - OPC UA endpoint:
opc.tcp://localhost:50000 - Web/config UI:
http://localhost:8080
Startup Flags
--autoaccept Accept all client certificates
--unsecuretransport Enable plain (non-TLS) OPC UA connections for dev tools
--sph Show PLC heartbeat on console
--sn=5 --sr=10 --st=uint 5 slow-changing nodes (10s cycle, uint)
--fn=5 --fr=1 --ft=uint 5 fast-changing nodes (1s cycle, uint)
--gn=5 5 stepping nodes
--nf=/app/config/nodes.json Custom node definitions
--pn=50000 Listen port
Custom Nodes
The file infra/opcua/nodes.json defines a single ConfigFolder object (not an array) with a root "ScadaLink" folder containing four equipment subfolders. Tags match typical ScadaLink instance attribute patterns:
| Folder | Tags | Types |
|---|---|---|
| Motor | Speed, Temperature, Current, Running, FaultCode | Double, Boolean, UInt32 |
| Pump | FlowRate, Pressure, Running | Double, Boolean |
| Tank | Level, Temperature, HighLevel, LowLevel | Double, Boolean |
| Valve | Position, Command | Double, UInt32 |
All custom nodes hold their initial/default values (0 for numerics, false for booleans) until written. OPC PLC's custom node format does not support random value generation for these nodes.
Custom nodes live in namespace 3 (http://microsoft.com/Opc/OpcPlc/). Node IDs follow the pattern ns=3;s=<Folder>.<Tag> (e.g., ns=3;s=Motor.Speed).
The browse path from the Objects root is: OpcPlc > ScadaLink > Motor|Pump|Tank|Valve.
Verification
- Check the container is running:
docker ps --filter name=scadalink-opcua
- Verify the OPC UA endpoint using any OPC UA client (e.g., UaExpert, opcua-commander):
# Using opcua-commander (npm install -g opcua-commander)
opcua-commander -e opc.tcp://localhost:50000
- Check the web UI at
http://localhost:8080for server status and node listing.
CLI Tool
The infra/tools/opcua_tool.py script provides a convenient CLI for interacting with the OPC UA server.
Install dependencies (one-time):
pip install -r infra/tools/requirements.txt
Commands:
# Check server status, namespaces, and endpoints
python infra/tools/opcua_tool.py check
# Browse the Objects folder (top-level)
python infra/tools/opcua_tool.py browse
# Browse a specific equipment folder
python infra/tools/opcua_tool.py browse --path "3:OpcPlc.3:ScadaLink.3:Motor"
# Read a tag value
python infra/tools/opcua_tool.py read --node "ns=3;s=Motor.Speed"
# Write a value to a tag
python infra/tools/opcua_tool.py write --node "ns=3;s=Motor.Running" --value true --type Boolean
# Monitor value changes for 15 seconds
python infra/tools/opcua_tool.py monitor --nodes "ns=3;s=Motor.Speed,ns=3;s=Pump.FlowRate" --duration 15
Use --endpoint to override the default endpoint (opc.tcp://localhost:50000). Run with --help for full usage.
Relevance to ScadaLink Components
- Data Connection Layer — connect to this server to test OPC UA subscription, read/write, and reconnection behavior.
- Site Runtime / Instance Actors — deploy instances with tag mappings pointing at these nodes.
- Template Engine — design templates with attributes matching the Motor/Pump/Tank/Valve folder structure.