DeploymentManagerActor deserialized connection config JSON as
Dictionary<string, string>, which silently failed on non-string values
like {"publishInterval":1000}. The OPC UA adapter then fell back to
localhost:4840 (unreachable in Docker). Now uses JsonDocument to handle
any JSON value type. OPC PLC Simulator connects successfully.
Attributes bound to data connections now initialize with "Uncertain" quality,
distinguishing "never received a value" from "known good" or "connection lost."
Quality is tracked per attribute and included in GetAttributeResponse.
- Add TagValueUpdate/ConnectionQualityChanged handlers to InstanceActor
- InstanceActor subscribes to DCL on PreStart based on DataSourceReference
- DeploymentManagerActor creates DCL connections on deploy and passes DCL ref
- AkkaHostedService creates DCL Manager Actor for tag subscriptions
- Move CreateConnectionCommand to Commons for cross-project access
- Add ConnectionConfig to FlattenedConfiguration for deployment packaging
DeploymentManagerActor now handles SubscribeDebugViewRequest and
UnsubscribeDebugViewRequest by forwarding to the appropriate Instance Actor.
This completes the debug view data flow from Central UI through to the site's
Instance Actor snapshot. Reduced refresh interval to 2s for responsiveness.
Instances page gains Deploy button that triggers flattening pipeline and sends
config to site. Button shows "Redeploy" when instance is stale. Fixed actor name
collision on redeployment by scheduling deferred recreation after Context.Stop.