- Add JoeAppEngine folder to OPC UA nodes.json (BTCS, AlarmCntsBySeverity, Scheduler/ScanTime)
- Fix DataConnectionActor: capture Self in PreStart for use from non-actor threads,
preventing Self.Tell failure in Disconnected event handler
- Implement InstanceActor.HandleConnectionQualityChanged to mark attributes Bad on disconnect
- Fix LmxFakeProxy TagMapper to serialize arrays as JSON instead of "System.Int32[]"
- Allow DataType and DataSourceReference updates in TemplateService.UpdateAttributeAsync
- Update test_infra_opcua.md with JoeAppEngine documentation
Both nodes of a site cluster were sending health reports. The standby
node (without the DeploymentManager singleton) reported 0 instances and
no connections, overwriting the active node's data in the aggregator.
Added IsActiveNode flag to ISiteHealthCollector, set by
DeploymentManagerActor on PreStart/PostStop. HealthReportSender skips
sending when the node is not active. Also ensured EnsureDclConnections
is called during startup batch creation so data connections survive
container restarts.
Wired ISiteHealthCollector calls for script errors (ScriptExecutionActor),
alarm eval errors (AlarmActor), dead letters (DeadLetterMonitorActor), and
S&F buffer depth placeholder. Added instance count tracking (deployed/
enabled/disabled) to SiteHealthReport via DeploymentManagerActor. Updated
Health Dashboard UI to show instance counts per site. All metrics flow
through the existing health report pipeline via ClusterClient.