feat(alarms): HiLo trigger type with per-band level, hysteresis, messages, overrides

Adds a new HiLo alarm trigger type with four configurable setpoints
(LoLo / Lo / Hi / HiHi). Each setpoint carries an optional priority,
deadband (for hysteresis), and operator message. The site runtime emits
AlarmStateChanged with an AlarmLevel field so consumers can differentiate
warning vs critical bands.

Plumbing:
  - new AlarmLevel enum + AlarmStateChanged.Level/Message init properties
  - AlarmTriggerEditor (Blazor) gets a HiLo render with severity tinting
  - AlarmTriggerConfigCodec extracted from the editor for testability
  - sitestream.proto carries level + message over gRPC
  - SemanticValidator enforces numeric attribute, setpoint ordering,
    non-negative deadband
  - on-trigger scripts get an Alarm global (Name/Level/Priority/Message)
    so notification routing can branch by severity
  - per-instance InstanceAlarmOverride entity + EF migration + flattening
    step + CLI commands; HiLo overrides merge setpoint-by-setpoint, binary
    types whole-replace
  - DebugView shows a Level badge + per-band message tooltip
  - App.razor auto-reloads on permanent Blazor circuit failure
  - docker/regen-proto.sh automates the proto regen workflow (the linux/arm64
    protoc segfault means generated files are checked in for now)
This commit is contained in:
Joseph Doherty
2026-05-13 03:23:32 -04:00
parent 783da8e21a
commit 751248feb6
46 changed files with 4693 additions and 204 deletions

View File

@@ -34,6 +34,17 @@ enum AlarmStateEnum {
ALARM_STATE_ACTIVE = 2;
}
// Severity level for an active alarm. Binary trigger types (ValueMatch,
// RangeViolation, RateOfChange) always emit ALARM_LEVEL_NONE. The HiLo
// trigger type emits one of the directional values.
enum AlarmLevelEnum {
ALARM_LEVEL_NONE = 0;
ALARM_LEVEL_LOW = 1;
ALARM_LEVEL_LOW_LOW = 2;
ALARM_LEVEL_HIGH = 3;
ALARM_LEVEL_HIGH_HIGH = 4;
}
message AttributeValueUpdate {
string instance_unique_name = 1;
string attribute_path = 2;
@@ -49,4 +60,6 @@ message AlarmStateUpdate {
AlarmStateEnum state = 3;
int32 priority = 4;
google.protobuf.Timestamp timestamp = 5;
AlarmLevelEnum level = 6; // ALARM_LEVEL_NONE for binary trigger types; set by HiLo.
string message = 7; // Optional per-band operator message; empty when unset.
}