feat(alarms): HiLo trigger type with per-band level, hysteresis, messages, overrides
Adds a new HiLo alarm trigger type with four configurable setpoints
(LoLo / Lo / Hi / HiHi). Each setpoint carries an optional priority,
deadband (for hysteresis), and operator message. The site runtime emits
AlarmStateChanged with an AlarmLevel field so consumers can differentiate
warning vs critical bands.
Plumbing:
- new AlarmLevel enum + AlarmStateChanged.Level/Message init properties
- AlarmTriggerEditor (Blazor) gets a HiLo render with severity tinting
- AlarmTriggerConfigCodec extracted from the editor for testability
- sitestream.proto carries level + message over gRPC
- SemanticValidator enforces numeric attribute, setpoint ordering,
non-negative deadband
- on-trigger scripts get an Alarm global (Name/Level/Priority/Message)
so notification routing can branch by severity
- per-instance InstanceAlarmOverride entity + EF migration + flattening
step + CLI commands; HiLo overrides merge setpoint-by-setpoint, binary
types whole-replace
- DebugView shows a Level badge + per-band message tooltip
- App.razor auto-reloads on permanent Blazor circuit failure
- docker/regen-proto.sh automates the proto regen workflow (the linux/arm64
protoc segfault means generated files are checked in for now)
This commit is contained in:
@@ -34,6 +34,17 @@ enum AlarmStateEnum {
|
||||
ALARM_STATE_ACTIVE = 2;
|
||||
}
|
||||
|
||||
// Severity level for an active alarm. Binary trigger types (ValueMatch,
|
||||
// RangeViolation, RateOfChange) always emit ALARM_LEVEL_NONE. The HiLo
|
||||
// trigger type emits one of the directional values.
|
||||
enum AlarmLevelEnum {
|
||||
ALARM_LEVEL_NONE = 0;
|
||||
ALARM_LEVEL_LOW = 1;
|
||||
ALARM_LEVEL_LOW_LOW = 2;
|
||||
ALARM_LEVEL_HIGH = 3;
|
||||
ALARM_LEVEL_HIGH_HIGH = 4;
|
||||
}
|
||||
|
||||
message AttributeValueUpdate {
|
||||
string instance_unique_name = 1;
|
||||
string attribute_path = 2;
|
||||
@@ -49,4 +60,6 @@ message AlarmStateUpdate {
|
||||
AlarmStateEnum state = 3;
|
||||
int32 priority = 4;
|
||||
google.protobuf.Timestamp timestamp = 5;
|
||||
AlarmLevelEnum level = 6; // ALARM_LEVEL_NONE for binary trigger types; set by HiLo.
|
||||
string message = 7; // Optional per-band operator message; empty when unset.
|
||||
}
|
||||
|
||||
Reference in New Issue
Block a user