Joseph Doherty 3b6a239ed6 fix(GWC-26): attach the alarm monitor's lease before SubscribeAlarms
RunMonitorAsync issued SubscribeAlarms and the first reconcile before the
internal distributor subscriber was attached (via ISessionManager
.ReadAlarmEventsAsync). The pump has been running since MarkReady started the
dashboard mirror and only fans to subscribers registered at fan-out time, so
every transition raised in that two-round-trip window bypassed the alarm feed —
and a missed Acknowledge was never repaired, because ApplyReconcile broadcast
presence deltas only.

- The monitor now takes the internal lease directly from its session BEFORE
  SubscribeAlarms and drains it after the first reconcile; window transitions
  buffer in the lease's bounded channel. Processing them after ApplyReconcile is
  order-safe (ApplyTransition handles alarms the snapshot already placed).
- ISessionManager.ReadAlarmEventsAsync removed — zero remaining callers.
- ApplyReconcile broadcasts an Acknowledge feed transition when a both-present
  alarm's state advanced to ActiveAcked. This is a feed-level repair on the
  AlarmFeedMessage/StreamAlarms surface rebuilt from the worker's own snapshot,
  not MxEvent emission, so the "never synthesize events" rule is untouched;
  the reasoning is recorded on ApplyReconcile.

The alarm-monitor test fakes now hand the monitor a real Ready GatewaySession
with a dashboard mirror, which is what makes the window reproducible.

Docs: docs/Sessions.md and gateway.md alarm-monitor ordering notes.

Refs: archreview/2026-07-12/remediation/10-gateway-core.md GWC-26