docs: revise interop fix path — wnwrapConsumer.dll is the right surface
Reflection on aaAlarmManagedClient.AlarmClient shows it implements only IDisposable (no [ComImport] interface, no class GUID) and has a single field "CwwAlarmConsumer* m_almUnmanaged". So AlarmClient is a C++/CLI managed wrapper around a native C++ class -- NOT a COM-interop class. The DateTime conversion happens INSIDE AVEVA's wrapper IL, not at the .NET-COM marshaling boundary. There's no separate COM interface to QI to. Revised approach (in docs/AlarmClientDiscovery.md): A. wnwrapConsumer.dll -- separate standalone COM library AVEVA ships at "C:\Program Files (x86)\Common Files\ArchestrA" exposing WNWRAPCONSUMERLib.wwAlarmConsumerClass with SetXmlAlarmQuery / GetXmlCurrentAlarms. XML-string output bypasses FILETIME marshaling entirely. Best fit -- real COM, self-contained, conventional production-grade approach. B. Patch aaAlarmManagedClient.dll IL -- direct but modifies a vendor binary, brittle to upgrades. C. Reflect into m_almUnmanaged and call native vtable directly -- requires reverse-engineering the C++ class layout. Picking A. Probe restored to Skip; next commit starts the wnwrapConsumer integration. Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
This commit is contained in:
@@ -250,6 +250,52 @@ public sealed class AlarmClientWmProbeTests : IDisposable
|
||||
{
|
||||
client = new AlarmClient();
|
||||
|
||||
// One-time interop introspection: dump AlarmClient's class GUID
|
||||
// (CoClass IID) and every interface it implements with their
|
||||
// GUID + InterfaceType. The IID we need to redeclare with safe
|
||||
// blittable types is the one whose vtable carries
|
||||
// GetHighPriAlarm.
|
||||
try
|
||||
{
|
||||
Type ct = client.GetType();
|
||||
Log($"=== AlarmClient interop introspection ===");
|
||||
Log($"Class FullName: {ct.FullName}");
|
||||
var classGuid = ct.GetCustomAttributes(typeof(System.Runtime.InteropServices.GuidAttribute), true)
|
||||
.Cast<System.Runtime.InteropServices.GuidAttribute>().FirstOrDefault();
|
||||
Log($"Class GUID: {classGuid?.Value ?? "(none)"}");
|
||||
foreach (var iface in ct.GetInterfaces())
|
||||
{
|
||||
var ig = iface.GetCustomAttributes(typeof(System.Runtime.InteropServices.GuidAttribute), true)
|
||||
.Cast<System.Runtime.InteropServices.GuidAttribute>().FirstOrDefault();
|
||||
var ity = iface.GetCustomAttributes(typeof(System.Runtime.InteropServices.InterfaceTypeAttribute), true)
|
||||
.Cast<System.Runtime.InteropServices.InterfaceTypeAttribute>().FirstOrDefault();
|
||||
int methodCount = iface.GetMethods().Length;
|
||||
Log($" iface {iface.FullName} | GUID={ig?.Value ?? "(none)"} | type={ity?.Value.ToString() ?? "(none)"} | methods={methodCount}");
|
||||
}
|
||||
// Dump fields (private/internal) — the COM object reference
|
||||
// is likely on a private field.
|
||||
Log($"--- AlarmClient instance fields ---");
|
||||
foreach (var f in ct.GetFields(BindingFlags.Public | BindingFlags.NonPublic | BindingFlags.Instance))
|
||||
{
|
||||
Log($" field {f.FieldType.FullName} {f.Name} (public={f.IsPublic})");
|
||||
}
|
||||
// Dump base class chain.
|
||||
Log($"--- base class chain ---");
|
||||
Type? baseT = ct.BaseType;
|
||||
int depth = 0;
|
||||
while (baseT != null && depth < 5)
|
||||
{
|
||||
Log($" base[{depth}]: {baseT.FullName}");
|
||||
baseT = baseT.BaseType;
|
||||
depth++;
|
||||
}
|
||||
Log($"=== end introspection ===");
|
||||
}
|
||||
catch (Exception ex)
|
||||
{
|
||||
Log($"Interop introspection threw: {ex.GetType().Name}: {ex.Message}");
|
||||
}
|
||||
|
||||
// Try InitializeConsumer first — separate from RegisterConsumer
|
||||
// per the discovered API surface; previous probe runs skipped
|
||||
// it. Some AVEVA managed-client patterns require Initialize
|
||||
|
||||
Reference in New Issue