fix(alarms): fetch/poll ceilings; truncation-semantics docs; log-format conformance
This commit is contained in:
@@ -418,8 +418,8 @@ behavior.
|
||||
| `MxGateway:Alarms:SubscriptionExpression` | _(empty)_ | AVEVA alarm-subscription expression the monitor subscribes on startup, in canonical `\\<machine>\Galaxy!<area>` form. The literal `Galaxy` provider is correct regardless of the Galaxy database name. When empty and `Enabled` is `true`, the gateway falls back to `\\<MachineName>\Galaxy!<DefaultArea>` if `DefaultArea` is set. |
|
||||
| `MxGateway:Alarms:DefaultArea` | _(empty)_ | Area name used to compose a default subscription when `SubscriptionExpression` is empty. If both are empty while `Enabled` is `true`, the monitor faults with a configuration diagnostic. |
|
||||
| `MxGateway:Alarms:ReconcileIntervalSeconds` | `30` | How often the monitor reconciles its in-process alarm cache against the worker's authoritative active-alarm snapshot, catching transitions the live poll-and-diff feed missed. Floored at 5 seconds. |
|
||||
| `MxGateway:Alarms:PollIntervalMilliseconds` | `500` | Cadence at which the worker's STA polls the AVEVA alarm consumer (`GetXmlCurrentAlarms2`) for the active-alarm snapshot the live feed diffs. Must be `>= 100`: every poll is a COM call plus an XML parse on the same STA that serves reads and writes, so a tighter cadence starves the command path. The gateway conveys the value to the worker via the `MXGATEWAY_ALARM_POLL_INTERVAL_MS` environment variable; a missing or unusable value leaves the worker on the 500 ms default rather than failing the session. |
|
||||
| `MxGateway:Alarms:MaxAlarmsPerFetch` | `1024` | Cap the worker passes to `GetXmlCurrentAlarms2`'s `maxAlmCnt`. Must be `>= 64`. It doubles as the **truncation threshold**: a fetch returning exactly this many records is treated as truncated, because the COM API caps its reply with no "more available" flag. On a truncated poll the worker retains the alarms the capped reply could not mention instead of letting their absence read as a clear, and logs a rate-limited `AlarmSnapshotTruncated` warning (identifiers and counts only). Raise this on galaxies whose steady-state active-alarm count approaches the cap — a galaxy permanently above it holds stale entries in the snapshot until a sub-cap poll. Conveyed to the worker via the `MXGATEWAY_ALARM_MAX_ALARMS_PER_FETCH` environment variable; a missing or unusable value leaves the worker on the 1024 default. |
|
||||
| `MxGateway:Alarms:PollIntervalMilliseconds` | `500` | Cadence at which the worker's STA polls the AVEVA alarm consumer (`GetXmlCurrentAlarms2`) for the active-alarm snapshot the live feed diffs. Must be between `100` and `3600000` (one hour): every poll is a COM call plus an XML parse on the same STA that serves reads and writes, so a tighter cadence starves the command path, while a value above an hour stops being a cadence and silently disables alarm polling. The gateway conveys the value to the worker via the `MXGATEWAY_ALARM_POLL_INTERVAL_MS` environment variable; a missing or out-of-range value leaves the worker on the 500 ms default rather than failing the session. |
|
||||
| `MxGateway:Alarms:MaxAlarmsPerFetch` | `1024` | Cap the worker passes to `GetXmlCurrentAlarms2`'s `maxAlmCnt`. Must be between `64` and `65536` — the worker is a 32-bit process that materializes each reply as one BSTR plus a full `XmlDocument`, so an unbounded cap faults the STA with an out-of-memory rather than merely slowing it. It doubles as the **truncation threshold**: a fetch returning exactly this many records is treated as truncated, because the COM API caps its reply with no "more available" flag. On a truncated poll the worker retains the alarms the capped reply could not mention instead of letting their absence read as a clear, and logs a rate-limited `AlarmSnapshotTruncated` warning to its stderr (identifiers and counts only). **Remediation when you see that warning: raise this value** so the steady-state active-alarm count fits inside one fetch. A galaxy permanently above the cap holds stale entries in the snapshot until a sub-cap poll, and loses clear→re-raise cycles that happen entirely out of window (see `docs/DesignDecisions.md`). Conveyed to the worker via the `MXGATEWAY_ALARM_MAX_ALARMS_PER_FETCH` environment variable; a missing or out-of-range value leaves the worker on the 1024 default. |
|
||||
|
||||
The alarm monitor is independent of client sessions: `AcknowledgeAlarm` and
|
||||
`StreamAlarms` are session-less RPCs served by the monitor.
|
||||
|
||||