feat(contracts): carry operator credentials on alarm acknowledgement

Claude-Session: https://claude.ai/code/session_016J6isfcgqy4SB2RK3ZvFvT
This commit is contained in:
Joseph Doherty
2026-10-19 19:16:39 -04:00
parent bf4b9c6c09
commit a94b502ce6
6 changed files with 651 additions and 403 deletions
+30 -13
View File
@@ -391,10 +391,13 @@ message AlarmFailoverConfig {
int32 failback_stable_probes = 3; // clean probes before switching back (>=1)
}
// Acknowledge a single alarm by its GUID. Operator identity fields are
// recorded atomically with the ack transition in the alarm-history log.
// The reply's hresult / native_status surfaces AVEVA's
// AlarmAckByGUID return code.
// Acknowledge a single alarm by its GUID. The worker resolves the GUID to the
// alarm's Galaxy reference from its active-alarm snapshot and acknowledges it
// by writing `comment` to `<TAGNAME>.AckMsg` over MXAccess after
// AuthenticateUser as the operator, so the alarm history records the real
// operator. The reply's hresult / native_status is 0 when the write was
// applied (or sent but unconfirmed), otherwise the AuthenticateUser HRESULT or
// the OnWriteComplete status detail.
message AcknowledgeAlarmCommand {
// Canonical 8-4-4-4-12 GUID string (e.g. "BCC47053-9542-4D65-BDAA-BCDEA6A32A73").
string alarm_guid = 1;
@@ -403,6 +406,10 @@ message AcknowledgeAlarmCommand {
string operator_node = 4;
string operator_domain = 5;
string operator_full_name = 6;
// Operator credential used for AuthenticateUser before the AckMsg write.
// Implementations must keep this field out of logs, metrics labels, command
// lines, and diagnostics.
string operator_password = 7;
}
// Snapshot the currently-active alarm set. Optional filter prefix scopes
@@ -414,9 +421,7 @@ message QueryActiveAlarmsCommand {
// Acknowledge a single alarm by its (name, provider, group) tuple. Used
// when the public RPC's AlarmFullReference (Provider!Group.Tag) cannot
// be resolved to a GUID directly. The worker invokes
// wwAlarmConsumerClass.AlarmAckByName which reaches the same alarm
// history path as AlarmAckByGUID.
// be resolved to a GUID directly. The worker acknowledges by writing `comment` to `<alarm_name>.AckMsg` (Galaxy provider only) after AuthenticateUser as the operator.
message AcknowledgeAlarmByNameCommand {
// Tag/alarm name (e.g. "TestMachine_001.TestAlarm001"). Tag itself
// may contain dots; the gateway-side parser splits on the first dot
@@ -431,6 +436,10 @@ message AcknowledgeAlarmByNameCommand {
string operator_node = 6;
string operator_domain = 7;
string operator_full_name = 8;
// Operator credential used for AuthenticateUser before the AckMsg write.
// Implementations must keep this field out of logs, metrics labels, command
// lines, and diagnostics.
string operator_password = 9;
}
message UnsubscribeBulkCommand {
@@ -725,11 +734,11 @@ message DrainEventsReply {
// Reply payload for AcknowledgeAlarmCommand AND
// AcknowledgeAlarmByNameCommand — both ack command kinds reuse this
// payload case (`MxCommandReply.acknowledge_alarm`); there is no
// dedicated by-name reply case. Surfaces AVEVA's native ack return
// code (AlarmAckByGUID for the GUID arm, AlarmAckByName for the
// by-name arm); 0 means success. The MxCommandReply's hresult field
// dedicated by-name reply case. Surfaces the ack outcome: 0 when the
// AckMsg write was applied or sent but unconfirmed; otherwise the
// AuthenticateUser HRESULT or the OnWriteComplete status detail. The MxCommandReply's hresult field
// carries the same value and is preferred for protocol consumers —
// this payload exists so the gateway-side WorkerAlarmRpcDispatcher
// this payload exists so GatewayAlarmMonitor
// can echo native_status into AcknowledgeAlarmReply.hresult without
// unpacking the outer envelope.
message AcknowledgeAlarmReplyPayload {
@@ -987,6 +996,15 @@ message AcknowledgeAlarmRequest {
// Operator principal performing the acknowledgement. The lmxopcua side
// resolves this from the OPC UA session prior to invoking the RPC.
string operator_user = 5;
// Operator's Galaxy (or OS) password. The gateway authenticates as
// operator_user with it before writing the acknowledgement so the alarm
// history records the real operator. May be empty for accounts without a
// password. Credential-sensitive: implementations must keep this field out
// of logs, metrics labels, command lines, and diagnostics.
string operator_password = 6;
// Optional domain for OS-authenticated galaxies. When set the gateway
// authenticates as "<operator_domain>\<operator_user>".
string operator_domain = 7;
}
message AcknowledgeAlarmReply {
@@ -997,8 +1015,7 @@ message AcknowledgeAlarmReply {
ProtocolStatus protocol_status = 3;
// Native ack return code echoed from the worker. The worker carries the
// ack outcome as a single int32 (AcknowledgeAlarmReplyPayload.native_status,
// = AlarmAckByName / AlarmAckByGUID return code; 0 = success); the gateway's
// WorkerAlarmRpcDispatcher copies that value here. This is the authoritative
// 0 = applied or sent; otherwise the AuthenticateUser HRESULT or OnWriteComplete detail); GatewayAlarmMonitor copies that value here. This is the authoritative
// ack-outcome field for the public RPC. Absent only when the worker reply
// omitted the value entirely (a protocol violation).
optional int32 hresult = 4;