feat(worker): add opt-in managed GUID alarm-ack path
ci / nightly-windev (push) Has been skipped
ci / windows-x86 (push) Successful in 1m19s
ci / java (push) Successful in 2m8s
ci / portable (push) Failing after 2m23s
ci / nightly-windev (pull_request) Has been skipped
ci / windows-x86 (pull_request) Successful in 1m18s
ci / java (pull_request) Successful in 2m3s
ci / portable (pull_request) Failing after 2m17s
ci / nightly-windev (push) Has been skipped
ci / windows-x86 (push) Successful in 1m19s
ci / java (push) Successful in 2m8s
ci / portable (push) Failing after 2m23s
ci / nightly-windev (pull_request) Has been skipped
ci / windows-x86 (pull_request) Successful in 1m18s
ci / java (pull_request) Successful in 2m3s
ci / portable (pull_request) Failing after 2m17s
Adds a managed acknowledge path over AVEVA's modern alarm client so GUID acks carry full operator identity (domain + full name) and work on builds where the wnwrap COM AlarmAckByGUID is E_NOTIMPL. Default off; opt in with MXGATEWAY_USE_MANAGED_ALARM_ACK=1 (wnwrap behavior unchanged otherwise). - AaManagedAlarmAckConsumer: reflection wrapper over aaAlarmManagedClient.AlarmClient (InitializeConsumer/RegisterConsumer/ Subscribe/AlarmAckByGUID); EnvGatedFactory degrades to null (wnwrap) if the DLL can't load, so alarm reads never break. - IManagedAlarmAckClient seam. AlarmDispatcher takes an optional client and routes GUID acks to it (subscribing + disposing it alongside the reader). - AlarmCommandHandler gains an optional managedAckFactory; WorkerPipeSession wires AaManagedAlarmAckConsumer.EnvGatedFactory at the production sites. - WnalNativeAckConsumer: confirmed native alarmlst.dll WNAL submit layer (WNALalarmReqSetText / WNALUserRequest / WNALUserRequestEx + lpAlmAck layout). List acquisition is intentionally not hand-rolled: the alarm-record layout and selection semantics are provider-defined and not recoverable from alarmlst.dll, so inferring them risks acking the wrong alarm. - AlarmManagedGuidAckLiveSmokeTests: skip-gated live smoke that pulls a real (non-degraded) alarm GUID and asserts the ack APPLIES (Acknowledge transition / acked snapshot), not merely rc=0. By-name acks stay on wnwrap (AlarmClient has no AlarmAckByName). Grounded in static RE of alarmlst.dll, aaAlarmManagedClient.dll and alarmmgr.exe. Co-Authored-By: Claude Opus 4.8 <noreply@anthropic.com>
This commit is contained in:
@@ -76,7 +76,7 @@ public sealed class WorkerPipeSession
|
||||
options,
|
||||
() => Process.GetCurrentProcess().Id,
|
||||
new WorkerPipeSessionOptions(),
|
||||
() => new MxAccessStaSession((eq, affinity, comFactory) => new AlarmCommandHandler(eq, () => new WnWrapAlarmConsumer(), affinity, comFactory, standbyFactory: null)),
|
||||
() => new MxAccessStaSession((eq, affinity, comFactory) => new AlarmCommandHandler(eq, () => new WnWrapAlarmConsumer(), affinity, comFactory, standbyFactory: null, managedAckFactory: AaManagedAlarmAckConsumer.EnvGatedFactory)),
|
||||
logger,
|
||||
stream)
|
||||
{
|
||||
@@ -98,7 +98,7 @@ public sealed class WorkerPipeSession
|
||||
options,
|
||||
processIdProvider,
|
||||
new WorkerPipeSessionOptions(),
|
||||
() => new MxAccessStaSession((eq, affinity, comFactory) => new AlarmCommandHandler(eq, () => new WnWrapAlarmConsumer(), affinity, comFactory, standbyFactory: null)),
|
||||
() => new MxAccessStaSession((eq, affinity, comFactory) => new AlarmCommandHandler(eq, () => new WnWrapAlarmConsumer(), affinity, comFactory, standbyFactory: null, managedAckFactory: AaManagedAlarmAckConsumer.EnvGatedFactory)),
|
||||
logger: null)
|
||||
{
|
||||
}
|
||||
@@ -1585,7 +1585,7 @@ public sealed class WorkerPipeSession
|
||||
// parameterless CompleteStartupHandshakeAsync is used without a
|
||||
// prior factory call.
|
||||
_runtimeSession ??= new MxAccessStaSession(
|
||||
(eq, affinity, comFactory) => new AlarmCommandHandler(eq, () => new WnWrapAlarmConsumer(), affinity, comFactory, standbyFactory: null));
|
||||
(eq, affinity, comFactory) => new AlarmCommandHandler(eq, () => new WnWrapAlarmConsumer(), affinity, comFactory, standbyFactory: null, managedAckFactory: AaManagedAlarmAckConsumer.EnvGatedFactory));
|
||||
IWorkerRuntimeSession session = _runtimeSession;
|
||||
try
|
||||
{
|
||||
|
||||
Reference in New Issue
Block a user