perf(worker): batch frames skip per-frame TCS; stream the alarm-poll XML (mxaccessgw#177)
R21-K12: WorkerFrameWriter.WriteBatchAsync allocated a TaskCompletionSource (plus its Task) per frame on the event drain hot path. PendingFrame now holds its terminal state itself (Interlocked pending/succeeded/faulted/canceled) and only single-frame WriteAsync frames, which race their completion against the write lock, get a TCS. A batch caller reads each frame's outcome after its own drain pass: every frame a pass claims is terminal before that pass releases the lock, so nothing is left to await. First-failure-in-batch-order, tombstoning, claim/cancel interlock and flush coalescing are unchanged. R21-K13: WnWrapAlarmConsumer.ParseSnapshotXml streams the GetXmlCurrentAlarms2 payload with an XmlTextReader (same defaults XmlDocument.LoadXml uses: Normalization off, DTDs parsed, no resolver; Significant whitespace only) instead of building a full XmlDocument every 500 ms poll. Behaviour is pinned by new tests: batch first-failure ordering (own drain and drained by another lock holder), batch cancellation tombstoning, batch flush failure, and a differential test running the replaced XmlDocument parser as an oracle over a 48-payload corpus (CRLF, CDATA, entities, DTD, namespaces, nesting, malformed). Mutation checks on windev: 8 of 8 injected regressions (whitespace, normalization, DTD, namespace, CDATA, batch last-failure, batch ignored failures, ignored tombstone) fail the new tests. Claude-Session: https://claude.ai/code/session_01GT67AEHd2Acv1YPwGfXEoV
This commit is contained in:
@@ -511,7 +511,7 @@ behavior.
|
||||
| `MxGateway:Alarms:DefaultArea` | _(empty)_ | Area name used to compose a default subscription when `SubscriptionExpression` is empty. If both are empty while `Enabled` is `true`, the monitor faults with a configuration diagnostic. |
|
||||
| `MxGateway:Alarms:ReconcileIntervalSeconds` | `30` | How often the monitor re-resolves and, on material change, hot-swaps the subtag fallback watch-list, then reconciles its in-process alarm cache against the worker's authoritative active-alarm snapshot. The acknowledged watch-list fingerprint advances only after an OK worker reply. Floored at 5 seconds. |
|
||||
| `MxGateway:Alarms:PollIntervalMilliseconds` | `500` | Cadence at which the worker's STA polls the AVEVA alarm consumer (`GetXmlCurrentAlarms2`) for the active-alarm snapshot the live feed diffs. Must be between `100` and `3600000` (one hour): every poll is a COM call plus an XML parse on the same STA that serves reads and writes, so a tighter cadence starves the command path, while a value above an hour stops being a cadence and silently disables alarm polling. The gateway conveys the value to the worker via the `MXGATEWAY_ALARM_POLL_INTERVAL_MS` environment variable; a missing or out-of-range value leaves the worker on the 500 ms default rather than failing the session. |
|
||||
| `MxGateway:Alarms:MaxAlarmsPerFetch` | `1024` | Cap the worker passes to `GetXmlCurrentAlarms2`'s `maxAlmCnt`. Must be between `64` and `65536` — the worker is a 32-bit process that materializes each reply as one BSTR plus a full `XmlDocument`, so an unbounded cap faults the STA with an out-of-memory rather than merely slowing it. It doubles as the **truncation threshold**: a fetch returning exactly this many records is treated as truncated, because the COM API caps its reply with no "more available" flag. On a truncated poll the worker retains the alarms the capped reply could not mention instead of letting their absence read as a clear, and logs a rate-limited `AlarmSnapshotTruncated` warning to its stderr (identifiers and counts only). **Remediation when you see that warning: raise this value** so the steady-state active-alarm count fits inside one fetch. A galaxy permanently above the cap holds stale entries in the snapshot until a sub-cap poll, and loses clear→re-raise cycles that happen entirely out of window (see `docs/DesignDecisions.md`). Conveyed to the worker via the `MXGATEWAY_ALARM_MAX_ALARMS_PER_FETCH` environment variable; a missing or out-of-range value leaves the worker on the 1024 default. |
|
||||
| `MxGateway:Alarms:MaxAlarmsPerFetch` | `1024` | Cap the worker passes to `GetXmlCurrentAlarms2`'s `maxAlmCnt`. Must be between `64` and `65536` — the worker is a 32-bit process that materializes each reply as one BSTR (streamed into one record per alarm, not a DOM), so an unbounded cap faults the STA with an out-of-memory rather than merely slowing it. It doubles as the **truncation threshold**: a fetch returning exactly this many records is treated as truncated, because the COM API caps its reply with no "more available" flag. On a truncated poll the worker retains the alarms the capped reply could not mention instead of letting their absence read as a clear, and logs a rate-limited `AlarmSnapshotTruncated` warning to its stderr (identifiers and counts only). **Remediation when you see that warning: raise this value** so the steady-state active-alarm count fits inside one fetch. A galaxy permanently above the cap holds stale entries in the snapshot until a sub-cap poll, and loses clear→re-raise cycles that happen entirely out of window (see `docs/DesignDecisions.md`). Conveyed to the worker via the `MXGATEWAY_ALARM_MAX_ALARMS_PER_FETCH` environment variable; a missing or out-of-range value leaves the worker on the 1024 default. |
|
||||
| `MxGateway:Alarms:AckClientName` | `MxGateway` | MXAccess client name the alarm worker's ack writer registers with; the Historian records it as each acknowledgement's OperatorNode. 1-64 printable characters. Conveyed via `MXGATEWAY_ALARM_ACK_CLIENT_NAME`. |
|
||||
|
||||
The alarm monitor is independent of client sessions: `AcknowledgeAlarm` and
|
||||
|
||||