Document the central alarm monitor and fan-out reversal
gateway.md describes the always-on GatewayAlarmMonitor, the session-less StreamAlarms feed, and session-less AcknowledgeAlarm. DesignDecisions.md records that the v1 "one subscriber per session / no fan-out" rule is superseded for the alarm subsystem: alarm state is gateway-wide, so the gateway monitors it centrally and fans it out to all clients. Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
This commit is contained in:
+16
-5
@@ -120,13 +120,24 @@ snapshot interval without mutating session or worker state. The dashboard uses
|
||||
local Bootstrap CSS and JavaScript plus a small local stylesheet; it does not
|
||||
use a Blazor UI component library.
|
||||
|
||||
`/dashboard/browse` and `/dashboard/alarms` go beyond read-only snapshots: they
|
||||
read live MXAccess data through `IDashboardLiveDataService`, which owns one
|
||||
shared, lazily-opened gateway session (and therefore one worker) for the whole
|
||||
dashboard. Browse walks the `IGalaxyHierarchyCache` tree and reads subscribed
|
||||
tag values; Alarms lists the worker's currently-active alarm set. See
|
||||
`/dashboard/browse` walks the `IGalaxyHierarchyCache` tree and reads subscribed
|
||||
tag values live through `IDashboardLiveDataService`, which owns one shared,
|
||||
lazily-opened gateway session for the whole dashboard. `/dashboard/alarms`
|
||||
reads the central alarm monitor's in-process cache directly. See
|
||||
`docs/GatewayDashboardDesign.md`.
|
||||
|
||||
The gateway runs an always-on central alarm monitor (`GatewayAlarmMonitor`):
|
||||
one gateway-owned worker session subscribes the configured AVEVA alarm
|
||||
provider, caches the active-alarm set (reconciled periodically against the
|
||||
worker's snapshot), and fans it out to every client through the session-less
|
||||
`StreamAlarms` RPC — the stream opens with the current active-alarm snapshot,
|
||||
then streams live transitions. `AcknowledgeAlarm` is session-less and routes
|
||||
through the monitor. Clients never open a worker session to see alarms, and
|
||||
alarm monitoring is independent of client lifecycle; the monitor re-opens its
|
||||
session if the worker faults. Gated by `MxGateway:Alarms:Enabled` — see
|
||||
`docs/DesignDecisions.md` for why this reverses the v1 single-subscriber rule
|
||||
for the alarm subsystem.
|
||||
|
||||
Dashboard routes use the same API-key verifier as gRPC. `/dashboard/login`
|
||||
accepts the API key in a form body, validates the configured `admin` scope,
|
||||
and issues an HTTP-only secure cookie for subsequent dashboard requests.
|
||||
|
||||
Reference in New Issue
Block a user