asb: SampleInterval unit fix + F34 followup for Publish-decoder gap
Investigation triggered by "Publish returns 0 values where .NET sees real
values" against the local AVEVA install.

Three findings:

1. SampleInterval unit: the wire field is **milliseconds**, not 100-ns
   ticks. The .NET reference (MxAsbDataClient.cs:441) defaults to
   `ulong sampleInterval = 1000` and the probe passes `subscribeSampleMs`
   directly through that surface. Sending 10_000_000 (1s in 100-ns ticks)
   makes MxDataProvider schedule the next sample ~2.8 hours out; Publish
   polls always come back empty until the misinterpreted timer expires.
   Fixed in `examples/asb-subscribe.rs` (sample_interval_ticks →
   sample_interval_ms = 1000) and clarified in
   `MinimalMonitoredItem.sample_interval`'s doc comment with the live-2026-05-06
   evidence.

2. result_code=32 is `AsbErrorCode.PublishComplete`
   (`AsbResultMapping.cs:37`) — informational, not a fatal error. .NET's
   `ToResult` (cs:122-129) explicitly treats it like Success.
   `ArchestrAResult.ErrorCode` and `ResultCode` are aliases for the same
   `resultCodeField` (cs:424-434), so `publish[i]_error=0x00000020` in
   the .NET probe trace = `result_code=Some(32)` in our trace = the same
   thing. Already handled correctly via the F26 narrower-bail fix
   (commit 983f029) — no code change needed.

3. **F34 filed** for the residual gap: with both sides seeing
   result_code=32 + success=false, .NET extracts a value but we extract
   zero. Three open hypotheses (wire-shape mismatch / payload-locator
   bug / MonitoredItemValue byte-layout bug); all need a middleman
   asb-relay.rs trace between the .NET probe and MxDataProvider to
   confirm. Adjacent symptom: AddMonitoredItemsResponse Status reads as
   0 items where .NET sees 1 — likely the same root cause; one fix
   should close both.

Live re-runs to validate the new sample-interval unit were blocked by
the documented F32 InvalidConnectionId transient (the
pending-connection table on MxDataProvider fills up after many
back-to-back test cycles; clears after a 30s+ cool-down).

Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
2026-05-06 02:28:44 -04:00
..

mxaccess (Rust port)

Native Rust replacement for AVEVA / Wonderware MXAccess. See ../design/ for the architectural specification, ../src/ for the .NET reference (the executable spec), and ../CLAUDE.md for project-wide rules.

Status

M0 — Workspace skeleton. Stub types compile; nothing is implemented yet. See ../design/60-roadmap.md for the M0M6 milestone plan.

Layout

rust/
  Cargo.toml                 workspace root
  rust-toolchain.toml        1.85 stable
  crates/
    mxaccess-codec/          pure protocol codec, no I/O
    mxaccess-galaxy/         Galaxy SQL resolver (tiberius)
    mxaccess-rpc/            DCE/RPC + NTLMv2 + OXID + OBJREF
    mxaccess-callback/       INmxSvcCallback RPC server
    mxaccess-nmx/            INmxService2 client
    mxaccess-asb-nettcp/     net.tcp framing (MC-NMF + MC-NBFX/NBFS)
    mxaccess-asb/            IASBIDataV2 client
    mxaccess/                async session + Transport trait + public API
    mxaccess-compat/         LMXProxyServer-shaped facade

Build

cargo build --workspace
cargo test --workspace
cargo clippy --workspace -- -D warnings
cargo fmt --check

Live probes

. ..\tools\Setup-LiveProbeEnv.ps1
cargo test -p mxaccess --features live -- --ignored

The setup script fetches credentials from Infisical via wwtools/secrets/Get-Secret.ps1. Never inline plaintext credentials.

License

MIT — see ../LICENSE.