Files
lmxopcua/docs/deploy
Joseph Doherty 1862fab671
v2-ci / unit-tests (push) Failing after 14m56s
docs(deploy): QA vq03/vq04 switched to OpcUa:Redundancy:Mode=Warm; #138 live gate PASS (#907, #717)
Two service-env entries per node (Mode=Warm, PeerApplicationUris__0), pair stopped and
started together. Gates: 250/90, RedundancySupport Warm, standby BadOutOfService,
LocalDb sync, canary Good on the Primary; standby Write could only show BadNotWritable
(QA tags are read-only). ScadaBridge WarmCanary moved off the Standby by ServiceLevel in
0.1 s (connect-time preference); graceful Primary stop still took the 66 s connectivity
path (ScadaBridge#141). End state: Warm, vq04 Primary.

Claude-Session: https://claude.ai/code/session_01GT67ACmpMR7b9LGRPLijMi
2026-11-13 09:00:35 -05:00
..