Files
lmxopcua/src/ZB.MOM.WW.OtOpcUa.Driver.AbLegacy/LibplctagLegacyTagRuntime.cs
T
2026-04-25 13:41:52 -04:00

108 lines
4.5 KiB
C#

using libplctag;
namespace ZB.MOM.WW.OtOpcUa.Driver.AbLegacy;
/// <summary>
/// Default libplctag-backed <see cref="IAbLegacyTagRuntime"/>. Uses <c>ab_pccc</c> protocol
/// on top of EtherNet/IP — libplctag's PCCC layer handles the file-letter + word + bit +
/// sub-element decoding internally, so our wrapper just has to forward the atomic type to
/// the right Get/Set call.
/// </summary>
internal sealed class LibplctagLegacyTagRuntime : IAbLegacyTagRuntime
{
private readonly Tag _tag;
public LibplctagLegacyTagRuntime(AbLegacyTagCreateParams p)
{
_tag = new Tag
{
Gateway = p.Gateway,
Path = p.CipPath,
PlcType = MapPlcType(p.LibplctagPlcAttribute),
Protocol = Protocol.ab_eip, // PCCC-over-EIP; libplctag routes via the PlcType-specific PCCC layer
Name = p.TagName,
Timeout = p.Timeout,
};
}
public Task InitializeAsync(CancellationToken cancellationToken) => _tag.InitializeAsync(cancellationToken);
public Task ReadAsync(CancellationToken cancellationToken) => _tag.ReadAsync(cancellationToken);
public Task WriteAsync(CancellationToken cancellationToken) => _tag.WriteAsync(cancellationToken);
public int GetStatus() => (int)_tag.GetStatus();
public object? DecodeValue(AbLegacyDataType type, int? bitIndex) => type switch
{
AbLegacyDataType.Bit => bitIndex is int bit
? _tag.GetBit(bit)
: _tag.GetInt8(0) != 0,
AbLegacyDataType.Int or AbLegacyDataType.AnalogInt => (int)_tag.GetInt16(0),
AbLegacyDataType.Long => _tag.GetInt32(0),
AbLegacyDataType.Float => _tag.GetFloat32(0),
AbLegacyDataType.String => _tag.GetString(0),
// Timer/Counter/Control sub-elements: bitIndex is the status bit position within the
// parent control word (encoded by AbLegacyDriver from the .DN / .EN / etc. sub-element
// name). Word members (.PRE / .ACC / .LEN / .POS) come through with bitIndex=null and
// decode as Int32 like before.
AbLegacyDataType.TimerElement or AbLegacyDataType.CounterElement
or AbLegacyDataType.ControlElement => bitIndex is int statusBit
? _tag.GetBit(statusBit)
: _tag.GetInt32(0),
_ => null,
};
public void EncodeValue(AbLegacyDataType type, int? bitIndex, object? value)
{
switch (type)
{
case AbLegacyDataType.Bit:
if (bitIndex is int)
// Bit-within-word writes are routed at the driver level
// (AbLegacyDriver.WriteBitInWordAsync) via a parallel parent-word runtime —
// this branch only fires if dispatch was bypassed. Throw loudly rather than
// silently clobbering the whole word.
throw new NotSupportedException(
"Bit-with-bitIndex writes must go through AbLegacyDriver.WriteBitInWordAsync.");
_tag.SetInt8(0, Convert.ToBoolean(value) ? (sbyte)1 : (sbyte)0);
break;
case AbLegacyDataType.Int:
case AbLegacyDataType.AnalogInt:
_tag.SetInt16(0, Convert.ToInt16(value));
break;
case AbLegacyDataType.Long:
_tag.SetInt32(0, Convert.ToInt32(value));
break;
case AbLegacyDataType.Float:
_tag.SetFloat32(0, Convert.ToSingle(value));
break;
case AbLegacyDataType.String:
_tag.SetString(0, Convert.ToString(value) ?? string.Empty);
break;
case AbLegacyDataType.TimerElement:
case AbLegacyDataType.CounterElement:
case AbLegacyDataType.ControlElement:
_tag.SetInt32(0, Convert.ToInt32(value));
break;
default:
throw new NotSupportedException($"AbLegacyDataType {type} not writable.");
}
}
public void Dispose() => _tag.Dispose();
private static PlcType MapPlcType(string attribute) => attribute switch
{
"slc500" => PlcType.Slc500,
"micrologix" => PlcType.MicroLogix,
"plc5" => PlcType.Plc5,
"logixpccc" => PlcType.LogixPccc,
_ => PlcType.Slc500,
};
}
internal sealed class LibplctagLegacyTagFactory : IAbLegacyTagFactory
{
public IAbLegacyTagRuntime Create(AbLegacyTagCreateParams createParams) =>
new LibplctagLegacyTagRuntime(createParams);
}