f179829ca6
- IMPORTANT: a successful probe records the PLC's ADS state; a PLC not in Run
keeps the driver Degraded with 'PLC in {state}' while LastSuccessfulRead
still advances (the device answered). RecordDeviceAnswered never restores
Healthy while any device is out of Run.
- Health is per device, rolled up worst-of: a comms fault is remembered on the
device it was seen on and only that device answering clears it (device A
answering no longer clears device B's fault).
- Refused (non-comms) dead registrations back off 30 s doubling to 10 min and
are re-armed by a symbol-version change or retried by the reconnect replay;
comms-class failures keep the every-tick retry. A retry whose failure class
changes republishes the tag's status, once.
- Bit-RMW gates are kept across generations and teardowns (never cleared).
- ShutdownAsync honours its CancellationToken: it stops waiting, finishes the
bookkeeping and throws OperationCanceledException.
- Remarks on why a superseded InitializeAsync throws OperationCanceledException.
- REAL / LREAL values (scalar or array element) outside the target range are
OverflowException -> BadOutOfRange instead of being written as Infinity.
- String / array write encoding factored into AdsTwinCATClient.PlanStringWrite
/ PlanArrayWrite; the fake runs them so a driver-level test covers the real
encode path against a fake resolved symbol.
- Timing-fragile tests use condition waits / measured probe-tick windows; the
dispose-during-shutdown test asserts ordering with a 1 s bound.
Refs #739
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
295 lines
16 KiB
C#
295 lines
16 KiB
C#
using System.Collections.Concurrent;
|
|
using System.Diagnostics;
|
|
using Shouldly;
|
|
using TwinCAT.TypeSystem;
|
|
using Xunit;
|
|
using ZB.MOM.WW.OtOpcUa.Core.Abstractions;
|
|
using ZB.MOM.WW.OtOpcUa.Driver.TwinCAT;
|
|
|
|
namespace ZB.MOM.WW.OtOpcUa.Driver.TwinCAT.Tests;
|
|
|
|
/// <summary>
|
|
/// #739 review fix round 1: the PLC-not-in-RUN health ruling, refused-registration retry backoff,
|
|
/// per-device worst-of health, RMW gates surviving teardown, a cancellable shutdown, the real
|
|
/// STRING / array encode path through the client planning helpers, and REAL range checks.
|
|
/// </summary>
|
|
[Trait("Category", "Unit")]
|
|
public sealed class TwinCATReviewFixRound1Tests
|
|
{
|
|
private const string Host = "ads://5.23.91.23.1.1:851";
|
|
private const string HostB = "ads://5.23.91.24.1.1:851";
|
|
|
|
private static TwinCATProbeOptions FastProbe => new()
|
|
{
|
|
Enabled = true,
|
|
Interval = TimeSpan.FromMilliseconds(30),
|
|
Timeout = TimeSpan.FromMilliseconds(100),
|
|
};
|
|
|
|
private static TwinCATDriver NewDriver(FakeTwinCATClientFactory factory, TwinCATProbeOptions probe, bool native,
|
|
params TwinCATTagDefinition[] tags) =>
|
|
new(new TwinCATDriverOptions
|
|
{
|
|
Devices = [.. tags.Select(t => t.DeviceHostAddress).Append(Host).Distinct().Select(h => new TwinCATDeviceOptions(h))],
|
|
RawTags = TwinCATRawTags.Entries(tags),
|
|
Probe = probe,
|
|
UseNativeNotifications = native,
|
|
}, "drv-1", factory);
|
|
|
|
private static async Task WaitForAsync(Func<bool> condition, TimeSpan timeout)
|
|
{
|
|
var deadline = DateTime.UtcNow + timeout;
|
|
while (!condition() && DateTime.UtcNow < deadline)
|
|
await Task.Delay(10);
|
|
}
|
|
|
|
// ---- IMPORTANT: a PLC not in RUN leaves the driver Degraded ----
|
|
|
|
/// <summary>
|
|
/// A probe that answers with ADS state Stop writes Degraded "PLC in Stop" and still advances
|
|
/// LastSuccessfulRead (the device answered); back in Run the driver is Healthy (positive control).
|
|
/// </summary>
|
|
[Fact]
|
|
public async Task A_PLC_not_in_Run_is_Degraded_and_Run_restores_Healthy()
|
|
{
|
|
var fake = new FakeTwinCATClient { AdsStateText = "Stop" };
|
|
var drv = NewDriver(new FakeTwinCATClientFactory { Customise = () => fake }, FastProbe, native: false,
|
|
new TwinCATTagDefinition("Speed", Host, "MAIN.Speed", TwinCATDataType.DInt));
|
|
await drv.InitializeAsync("{}", TestContext.Current.CancellationToken);
|
|
var initStamp = drv.GetHealth().LastSuccessfulRead!.Value;
|
|
|
|
await WaitForAsync(() => drv.GetHealth().State == DriverState.Degraded, TimeSpan.FromSeconds(3));
|
|
var stopped = drv.GetHealth();
|
|
stopped.State.ShouldBe(DriverState.Degraded);
|
|
stopped.LastError.ShouldNotBeNull().ShouldContain("PLC in Stop");
|
|
await WaitForAsync(() => drv.GetHealth().LastSuccessfulRead > initStamp, TimeSpan.FromSeconds(3));
|
|
drv.GetHealth().LastSuccessfulRead!.Value.ShouldBeGreaterThan(initStamp);
|
|
|
|
// A Good read while the PLC is stopped must not paper over it.
|
|
_ = await drv.ReadAsync(["Speed"], TestContext.Current.CancellationToken);
|
|
drv.GetHealth().State.ShouldBe(DriverState.Degraded);
|
|
|
|
fake.AdsStateText = "Run";
|
|
await WaitForAsync(() => drv.GetHealth().State == DriverState.Healthy, TimeSpan.FromSeconds(3));
|
|
drv.GetHealth().State.ShouldBe(DriverState.Healthy);
|
|
await drv.ShutdownAsync(TestContext.Current.CancellationToken);
|
|
}
|
|
|
|
// ---- MINOR 1: refused dead registrations back off; a class change republishes ----
|
|
|
|
/// <summary>
|
|
/// A REFUSED dead registration is not re-attempted every probe tick; a comms-failed one is (positive
|
|
/// control: it recovers). A symbol-version-changed signal re-arms the refused one at once.
|
|
/// </summary>
|
|
[Fact]
|
|
public async Task Refused_registrations_back_off_while_comms_failures_retry_each_tick()
|
|
{
|
|
var fake = new FakeTwinCATClient();
|
|
fake.AddNotificationErrors["MAIN.T"] = new TwinCATTypeMismatchException("MAIN.T", "declared DInt, PLC STRING");
|
|
fake.AddNotificationErrors["MAIN.C"] = new InvalidOperationException("transient");
|
|
var drv = NewDriver(new FakeTwinCATClientFactory { Customise = () => fake }, FastProbe, native: true,
|
|
new TwinCATTagDefinition("T", Host, "MAIN.T", TwinCATDataType.DInt),
|
|
new TwinCATTagDefinition("C", Host, "MAIN.C", TwinCATDataType.DInt));
|
|
await drv.InitializeAsync("{}", TestContext.Current.CancellationToken);
|
|
_ = await drv.SubscribeAsync(["T", "C"], TimeSpan.FromMilliseconds(100), TestContext.Current.CancellationToken);
|
|
|
|
await WaitForAsync(() => fake.AttemptsFor("MAIN.C") >= 3, TimeSpan.FromSeconds(3));
|
|
fake.AttemptsFor("MAIN.C").ShouldBeGreaterThanOrEqualTo(3); // comms class: every tick
|
|
fake.AttemptsFor("MAIN.T").ShouldBe(1); // refusal: backed off
|
|
|
|
fake.AddNotificationErrors.TryRemove("MAIN.C", out _);
|
|
await WaitForAsync(() => fake.Notifications.Any(n => n.SymbolPath == "MAIN.C"), TimeSpan.FromSeconds(3));
|
|
fake.Notifications.ShouldContain(n => n.SymbolPath == "MAIN.C");
|
|
|
|
fake.FireSymbolVersionChanged();
|
|
await WaitForAsync(() => fake.AttemptsFor("MAIN.T") >= 2, TimeSpan.FromSeconds(3));
|
|
fake.AttemptsFor("MAIN.T").ShouldBe(2);
|
|
await drv.ShutdownAsync(TestContext.Current.CancellationToken);
|
|
}
|
|
|
|
/// <summary>When a retry fails with a different failure class the tag's status is republished, once.</summary>
|
|
[Fact]
|
|
public async Task A_retry_whose_failure_class_changes_republishes_the_status()
|
|
{
|
|
var fake = new FakeTwinCATClient();
|
|
fake.AddNotificationErrors["MAIN.X"] = new InvalidOperationException("router hiccup");
|
|
var drv = NewDriver(new FakeTwinCATClientFactory { Customise = () => fake }, FastProbe, native: true,
|
|
new TwinCATTagDefinition("X", Host, "MAIN.X", TwinCATDataType.DInt));
|
|
await drv.InitializeAsync("{}", TestContext.Current.CancellationToken);
|
|
var events = new ConcurrentQueue<DataChangeEventArgs>();
|
|
drv.OnDataChange += (_, e) => events.Enqueue(e);
|
|
_ = await drv.SubscribeAsync(["X"], TimeSpan.FromMilliseconds(100), TestContext.Current.CancellationToken);
|
|
events.ShouldHaveSingleItem().Snapshot.StatusCode.ShouldBe(TwinCATStatusMapper.BadCommunicationError);
|
|
await WaitForAsync(() => fake.AttemptsFor("MAIN.X") >= 3, TimeSpan.FromSeconds(3));
|
|
events.Count.ShouldBe(1, "a repeat of the same failure class publishes nothing");
|
|
|
|
fake.AddNotificationErrors["MAIN.X"] = new TwinCATNotificationRefusedException(
|
|
"MAIN.X", "symbol gone", TwinCATStatusMapper.BadNodeIdUnknown);
|
|
await WaitForAsync(() => events.Count >= 2, TimeSpan.FromSeconds(3));
|
|
events.Last().Snapshot.StatusCode.ShouldBe(TwinCATStatusMapper.BadNodeIdUnknown);
|
|
await drv.ShutdownAsync(TestContext.Current.CancellationToken);
|
|
}
|
|
|
|
// ---- MINOR 2: per-device worst-of health ----
|
|
|
|
/// <summary>
|
|
/// A comms fault on device B is not cleared by device A answering; B answering clears it
|
|
/// (positive control).
|
|
/// </summary>
|
|
[Fact]
|
|
public async Task One_devices_answer_does_not_clear_another_devices_comms_fault()
|
|
{
|
|
var clients = new ConcurrentDictionary<int, FakeTwinCATClient>();
|
|
var build = 0;
|
|
var factory = new FakeTwinCATClientFactory
|
|
{
|
|
Customise = () =>
|
|
{
|
|
var c = new FakeTwinCATClient();
|
|
clients[Interlocked.Increment(ref build)] = c;
|
|
return c;
|
|
},
|
|
};
|
|
var drv = NewDriver(factory, new TwinCATProbeOptions { Enabled = false }, native: false,
|
|
new TwinCATTagDefinition("A", Host, "MAIN.A", TwinCATDataType.DInt),
|
|
new TwinCATTagDefinition("B", HostB, "MAIN.B", TwinCATDataType.DInt));
|
|
await drv.InitializeAsync("{}", TestContext.Current.CancellationToken);
|
|
_ = await drv.ReadAsync(["A"], TestContext.Current.CancellationToken); // client 1 = device A
|
|
_ = await drv.ReadAsync(["B"], TestContext.Current.CancellationToken); // client 2 = device B
|
|
clients[2].ReadStatuses["MAIN.B"] = TwinCATStatusMapper.BadTimeout;
|
|
|
|
_ = await drv.ReadAsync(["B"], TestContext.Current.CancellationToken);
|
|
drv.GetHealth().State.ShouldBe(DriverState.Degraded);
|
|
|
|
_ = await drv.ReadAsync(["A"], TestContext.Current.CancellationToken);
|
|
drv.GetHealth().State.ShouldBe(DriverState.Degraded, "device A answering says nothing about device B");
|
|
|
|
clients[2].ReadStatuses.Remove("MAIN.B");
|
|
_ = await drv.ReadAsync(["B"], TestContext.Current.CancellationToken);
|
|
drv.GetHealth().State.ShouldBe(DriverState.Healthy);
|
|
}
|
|
|
|
// ---- MINOR 3: RMW gates are kept across generations ----
|
|
|
|
/// <summary>The per-parent RMW gate survives a teardown (a write still in flight keeps the same gate).</summary>
|
|
[Fact]
|
|
public async Task Bit_RMW_gates_survive_a_shutdown()
|
|
{
|
|
var fake = new FakeTwinCATClient { ParentWords = { ["MAIN.Flags"] = [0, 0] } };
|
|
var drv = NewDriver(new FakeTwinCATClientFactory { Customise = () => fake },
|
|
new TwinCATProbeOptions { Enabled = false }, native: false,
|
|
new TwinCATTagDefinition("Bit", Host, "MAIN.Flags.1", TwinCATDataType.Bool));
|
|
await drv.InitializeAsync("{}", TestContext.Current.CancellationToken);
|
|
_ = await drv.WriteAsync([new WriteRequest("Bit", true)], TestContext.Current.CancellationToken);
|
|
var gate = drv.BitRmwGateForTest(Host, "MAIN.Flags").ShouldNotBeNull();
|
|
|
|
await drv.ShutdownAsync(TestContext.Current.CancellationToken);
|
|
await drv.InitializeAsync("{}", TestContext.Current.CancellationToken);
|
|
_ = await drv.WriteAsync([new WriteRequest("Bit", false)], TestContext.Current.CancellationToken);
|
|
|
|
drv.BitRmwGateForTest(Host, "MAIN.Flags").ShouldBeSameAs(gate);
|
|
}
|
|
|
|
// ---- MINOR 4: ShutdownAsync honours its token ----
|
|
|
|
/// <summary>
|
|
/// A cancelled ShutdownAsync stops waiting on a probe wedged in connect and throws
|
|
/// OperationCanceledException; the teardown itself still happened (tables emptied).
|
|
/// </summary>
|
|
[Fact]
|
|
public async Task Shutdown_honours_its_cancellation_token()
|
|
{
|
|
var wedge = new TaskCompletionSource(TaskCreationOptions.RunContinuationsAsynchronously);
|
|
var factory = new FakeTwinCATClientFactory { Customise = () => new FakeTwinCATClient { BlockConnect = wedge } };
|
|
var drv = NewDriver(factory, FastProbe, native: false);
|
|
await drv.InitializeAsync("{}", TestContext.Current.CancellationToken);
|
|
await WaitForAsync(() => factory.Clients.Count == 1, TimeSpan.FromSeconds(2));
|
|
|
|
using var cts = new CancellationTokenSource(TimeSpan.FromMilliseconds(100));
|
|
var sw = Stopwatch.StartNew();
|
|
await Should.ThrowAsync<OperationCanceledException>(() => drv.ShutdownAsync(cts.Token));
|
|
sw.Elapsed.ShouldBeLessThan(TwinCATDriver.ProbeJoinTimeout, "the wait ended on the token, not the join bound");
|
|
drv.DeviceCount.ShouldBe(0);
|
|
wedge.SetResult();
|
|
}
|
|
|
|
// ---- MINOR 7: the real STRING / array encode path through the client planning helpers ----
|
|
|
|
/// <summary>
|
|
/// A STRING write through the driver lands as NUL-padded Windows-1252 bytes at the PLC symbol's width;
|
|
/// an over-long value is BadOutOfRange and a WSTRING symbol under a String tag BadTypeMismatch.
|
|
/// </summary>
|
|
[Fact]
|
|
public async Task String_writes_go_through_the_client_encode_plan()
|
|
{
|
|
var fake = new FakeTwinCATClient();
|
|
fake.SymbolShapes["MAIN.Name"] = TwinCATPlcSymbolShape.Classify("STRING(4)", DataTypeCategory.String, 5);
|
|
fake.SymbolShapes["MAIN.Wide"] = TwinCATPlcSymbolShape.Classify("WSTRING(4)", DataTypeCategory.String, 10);
|
|
var drv = NewDriver(new FakeTwinCATClientFactory { Customise = () => fake },
|
|
new TwinCATProbeOptions { Enabled = false }, native: false,
|
|
new TwinCATTagDefinition("Name", Host, "MAIN.Name", TwinCATDataType.String),
|
|
new TwinCATTagDefinition("Wide", Host, "MAIN.Wide", TwinCATDataType.String));
|
|
await drv.InitializeAsync("{}", TestContext.Current.CancellationToken);
|
|
|
|
var results = await drv.WriteAsync(
|
|
[
|
|
new WriteRequest("Name", "äb"),
|
|
new WriteRequest("Name", "toolong"),
|
|
new WriteRequest("Wide", "x"),
|
|
], TestContext.Current.CancellationToken);
|
|
|
|
results.Select(r => r.StatusCode).ShouldBe(
|
|
[TwinCATStatusMapper.Good, TwinCATStatusMapper.BadOutOfRange, TwinCATStatusMapper.BadTypeMismatch]);
|
|
fake.RawWrites["MAIN.Name"].ShouldBe(new byte[] { 0xE4, (byte)'b', 0, 0, 0 });
|
|
fake.RawWrites.ShouldNotContainKey("MAIN.Wide");
|
|
drv.GetHealth().State.ShouldBe(DriverState.Healthy);
|
|
}
|
|
|
|
/// <summary>An array write through the driver lands as the codec's bytes at the PLC element stride.</summary>
|
|
[Fact]
|
|
public async Task Array_writes_go_through_the_client_encode_plan()
|
|
{
|
|
var fake = new FakeTwinCATClient();
|
|
var element = TwinCATPlcSymbolShape.Classify("INT", DataTypeCategory.Primitive, 2);
|
|
fake.SymbolShapes["MAIN.Buf"] = TwinCATPlcSymbolShape.Classify("ARRAY [0..3] OF INT", DataTypeCategory.Array, 8);
|
|
fake.ArrayShapes["MAIN.Buf"] = new TwinCATPlcArrayShape([4], 8, element);
|
|
var drv = NewDriver(new FakeTwinCATClientFactory { Customise = () => fake },
|
|
new TwinCATProbeOptions { Enabled = false }, native: false,
|
|
new TwinCATTagDefinition("Buf", Host, "MAIN.Buf", TwinCATDataType.Int, ArrayLength: 2),
|
|
new TwinCATTagDefinition("BufAsReal", Host, "MAIN.Buf", TwinCATDataType.Real, ArrayLength: 2));
|
|
await drv.InitializeAsync("{}", TestContext.Current.CancellationToken);
|
|
|
|
var results = await drv.WriteAsync(
|
|
[
|
|
new WriteRequest("Buf", new[] { 1, -2 }),
|
|
new WriteRequest("BufAsReal", new[] { 1.0, 2.0 }),
|
|
], TestContext.Current.CancellationToken);
|
|
|
|
results[0].StatusCode.ShouldBe(TwinCATStatusMapper.Good);
|
|
fake.RawWrites["MAIN.Buf"].ShouldBe(new byte[] { 0x01, 0x00, 0xFE, 0xFF }); // leading sub-range only
|
|
results[1].StatusCode.ShouldBe(TwinCATStatusMapper.BadTypeMismatch);
|
|
}
|
|
|
|
// ---- MINOR 8: REAL / LREAL range ----
|
|
|
|
/// <summary>A REAL (scalar or array element) beyond float range is BadOutOfRange, never written as Infinity.</summary>
|
|
[Fact]
|
|
public async Task Out_of_range_REAL_values_are_BadOutOfRange()
|
|
{
|
|
Should.Throw<OverflowException>(() => AdsTwinCATClient.ConvertForWrite(TwinCATDataType.Real, 1e300));
|
|
Should.Throw<OverflowException>(() => AdsTwinCATClient.ConvertForWrite(TwinCATDataType.LReal, "1e400"));
|
|
AdsTwinCATClient.ConvertForWrite(TwinCATDataType.Real, 3.5).ShouldBe(3.5f);
|
|
AdsTwinCATClient.ConvertForWrite(TwinCATDataType.Real, float.PositiveInfinity).ShouldBe(float.PositiveInfinity);
|
|
float.IsNaN((float)AdsTwinCATClient.ConvertForWrite(TwinCATDataType.Real, double.NaN)).ShouldBeTrue();
|
|
|
|
var fake = new FakeTwinCATClient();
|
|
var drv = NewDriver(new FakeTwinCATClientFactory { Customise = () => fake },
|
|
new TwinCATProbeOptions { Enabled = false }, native: false,
|
|
new TwinCATTagDefinition("Arr", Host, "MAIN.Arr", TwinCATDataType.Real, ArrayLength: 2));
|
|
await drv.InitializeAsync("{}", TestContext.Current.CancellationToken);
|
|
var result = await drv.WriteAsync([new WriteRequest("Arr", new[] { 1.0, 1e300 })], TestContext.Current.CancellationToken);
|
|
result.Single().StatusCode.ShouldBe(TwinCATStatusMapper.BadOutOfRange);
|
|
fake.ArrayWriteLog.ShouldBeEmpty();
|
|
}
|
|
}
|