lmxopcua/docs/drivers/AbLegacy.md
T
Joseph Doherty e863e9f0e2 fix(ablegacy): refuse native status-bit and PLC-5 writes before creating the runtime (#593)
A first-touch native write to a T/C/R status-bit sub-element (T4:0.DN) created
and initialised the tag's runtime before the runtime's write refusal could fire;
the init is one READ, so against a device lacking the file (the ab_server
fixture has no T/C/R) it surfaced as BadCommunicationError + Degraded health
instead of BadNotSupported. The bit-RMW path was not involved: AbLegacyAddress
rejects sub-element + /N, so a status bit's BitIndex is always null.

NativeAbLegacyTagRuntime.WriteRefusal is now the single predicate (status bit
by address whatever the authored type; any PLC-5 write), asked by the driver via
IAbLegacyTagFactory.WriteRefusal (default null, so libplctag is unchanged)
before EnsureTagRuntimeAsync and ahead of the bit-RMW branch.

Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
2026-10-08 07:28:52 -04:00

17 KiB

AB Legacy Driver

In-process native-protocol driver that exposes legacy Allen-Bradley PLCs — SLC 500, MicroLogix, PLC-5, and Logix-via-PCCC — as OPC UA nodes. It runs inside the OtOpcUa server's .NET 10 AnyCPU process and speaks PCCC over EtherNet/IP through the same libplctag.NET wrapper as the AB CIP driver, but addresses data by file (data-table) rather than by symbolic tag. One driver instance can serve many devices; per-device routing is keyed on the canonical ab://gateway[:port]/cip-path host-address string. PCCC has no native push model, so subscriptions are a polling overlay on top of IReadable.

For the driver spec (capability surface, config shape, payload limits), see docs/v2/driver-specs.md §4. For the manual test client, see Driver.AbLegacy.Cli.md. For the integration fixture coverage map, see AbLegacy-Test-Fixture.md.

Project Layout

Project Role
src/Drivers/ZB.MOM.WW.OtOpcUa.Driver.AbLegacy/ The driver — AbLegacyDriver, the libplctag runtime wrapper, the PCCC file-address parser (AbLegacyAddress), the host-address parser, and the status mapper.
src/Drivers/ZB.MOM.WW.OtOpcUa.Driver.AbLegacy.Contracts/ AbLegacyDriverOptions, AbLegacyDeviceOptions, AbLegacyTagDefinition, and the AbLegacyDataType / AbLegacyPlcFamily / AbLegacyPlcFamilyProfile records bound from the driver's DriverConfig JSON.

Per family the AbLegacyPlcFamilyProfile supplies the libplctag plc attribute, default CIP path, max-payload bytes, and the SupportsStringFile / SupportsLongFile capability flags. MicroLogix uses direct EIP (empty default path); MicroLogix and PLC-5 don't ship L-files; PLC-5 predates them entirely. Tag types are validated against the device's profile at init time — declaring a Long or String tag on a family that can't support it fails fast with a clear message.

Capability Surface

AbLegacyDriver : IDriver, IReadable, IWritable, ITagDiscovery, ISubscribable, IHostConnectivityProbe, IPerCallHostResolver, IDisposable, IAsyncDisposable (Driver.AbLegacy/AbLegacyDriver.cs). There is no IAlarmSource — unlike the AB CIP driver, PCCC has no ALMD instruction to project, so alarms are out of scope.

Capability Implementation entry point Notes
ITagDiscovery DiscoverAsync Emits pre-declared tags under per-device folders. Tags are single-element today (IsArray hard-wired false); multi-element file ranges are a tracked follow-up.
IReadable ReadAsync Per-tag reads serialized per cached runtime under a lock (a libplctag Tag handle is not concurrency-safe across the server read path + poll loop).
IWritable WriteAsync Bit-within-word writes (N/L-file N7:0/3, B-file B3:0/0, and I/O image files I:0/0/O:1/2) do a per-parent-word read-modify-write under a lock. An Input-image (I) write is forwarded to the PLC and may be rejected by the device (the device drives the input image from physical inputs); the driver surfaces the device's real PCCC status in that case. Non-writable tags return BadNotWritable.
ISubscribable SubscribeAsync driven by the shared PollGroupEngine No push model — subscriptions become polling groups.
IHostConnectivityProbe ProbeLoopAsync + GetHostStatuses One probe loop per device reading Probe.ProbeAddress; transitions log Warning (down) / Information (recover).
IPerCallHostResolver ResolveHost Routes each call to the tag's DeviceHostAddress; unknown references fall back to the first device, never throwing (per the interface contract).

Addressing Model

Per-device host addresses are the canonical ab://gateway[:port]/cip-path form parsed by AbLegacyHostAddress.TryParse. When the parsed CIP path is empty the family profile's default path is used (e.g. SLC 500 gets 1,0; MicroLogix stays empty for direct EIP).

Tags carry a PCCC file address parsed by AbLegacyAddress (AbLegacyAddress.cs) — file letter + file number + word number, with an optional bit index (/N) or structured sub-element (.ACC, .PRE, …). The string is passed straight through to libplctag's name= attribute; the parser validates shape and surfaces the pieces for driver-side routing (e.g. deciding a bit needs read-modify-write):

Form Meaning
N7:0 Integer file 7, word 0 (signed 16-bit)
F8:0 Float file 8, word 0 (32-bit IEEE-754)
B3:0/0 Bit file 3, word 0, bit 0
L9:0 Long-integer file (SLC 5/05+, 32-bit)
ST9:0 String file (82-byte fixed-length)
T4:0.ACC / C5:0.PRE Timer / counter sub-element
I:0/0 / O:1/2 / S:1 Input / output / status system files (no file number)

AbLegacyDataType covers the corresponding PCCC types: Bit, Int (N), Long (L), Float (F), AnalogInt (A), String (ST), and the TimerElement / CounterElement / ControlElement sub-element families. The parser enforces PCCC structural rules — bit-addressing only on 16/32-bit element files, sub-elements only on T/C/R files, no file number on I/O/S — rejecting malformed addresses before they reach libplctag.

Bit-within-word writes — B-file (B3:0/0), I/O image (I:0/0, O:1/2), N-file (N7:0/3), and L-file bit addresses all use the same parent-word read-modify-write (RMW) path: the driver reads the parent word, flips the target bit, and writes the word back, under a per-parent lock. The lock serialises the driver's own concurrent bit-writers against the same word, but cannot guard against the PLC program writing that word between the driver's read and write — this is an inherent limitation of any software-level RMW. Input-image (I) bit writes are forwarded to the PLC as-is; the device drives the input image from physical inputs and may reject the write.

Configuration

AbLegacyDriverOptions (Driver.AbLegacy.Contracts/AbLegacyDriverOptions.cs) binds from the driver's DriverConfig JSON:

  • Devices — one AbLegacyDeviceOptions per PLC (HostAddress, PlcFamily, optional DeviceName).
  • Tags — pre-declared AbLegacyTagDefinition list (Name, DeviceHostAddress, Address, DataType, Writable, WriteIdempotent).
  • Probe — connectivity-probe Enabled / Interval / Timeout / ProbeAddress.
  • Transport — absent (default ⇒ Libplctag), Native (opt-in), or Libplctag; see Transport.

Full per-field descriptions live in the contracts assembly. The JSON skeleton is reproduced in docs/v2/driver-specs.md §4.

Transport (transport option)

Same switch as AB CIP: transport = absent | Native | Libplctag, a string (case-insensitive on read, written as "Libplctag" / "Native"; "use the default" is encoded by omitting the key). Native is a managed PCCC-over-EtherNet/IP client (Driver.Ab.Transport).

Default resolution (one place, AbLegacyTransportResolver, used by the driver, the Test Connect probe and the CLI): an absent key resolves to Libplctag for every PLC family — unchanged from before the native transport existed. Native is opt-in (final review I3: on a wire it is proven only for N-file reads and writes and one F8 read — see Wire evidence). An explicit value always wins: explicit Native with a PLC-5 / LogixPccc device is allowed (an operator choice) and logs one Warning per driver instance naming the limitation. (AbCip's node-level Drivers:AbCip:DefaultTransport has no AbLegacy counterpart — the AbLegacy default is libplctag and is not node-configurable.)

A change takes effect when the driver instance is constructed: on a deploy that changes DriverConfig (which recreates it) and on every process start, including the restart that installs this build (see the release note). The AdminUI form's Transport dropdown offers "Default (libplctag)" (omits the key on save), "Native (managed, opt-in)" and "libplctag". The driver logs transport=<effective> (default|configured) on every init, e.g. transport=Libplctag (default). CLI: --transport default|native|libplctag (default default = libplctag for every --plc-type). See AbCip.md §Transport for the shared behaviour (one pooled connection per device, Forward Open throttle, routing).

Native routing: SLC500/MicroLogix/PLC-5 are direct; logixpccc uses UnconnectedSend and its SLC framing is unverified.

Release note — native PCCC transport, opt-in (final review I3)

  • The default is unchanged: libplctag. A driver config with no transport key runs Libplctag, for every PLC family, exactly as before this release. The upgrade restart moves nothing. (An interim build on this branch defaulted SLC 500 / MicroLogix to Native; that was reverted before merge.)
  • "transport": "Native" opts a driver into the managed PCCC-over-EtherNet/IP client (Driver.Ab.Transport). It takes effect when the driver is constructed — a deploy that changes DriverConfig, or a process start — not on ReinitializeAsync. The AdminUI Transport dropdown authors it; remove the key (or pick "Default (libplctag)") to go back.
  • Known limits of Native (why it is opt-in):
    • ⚠️ Wire evidence is narrow and simulator-only — see Wire evidence. Only N-file reads and writes and one F8 read have touched a wire (ab_server). The default probe address S:0 and the B, T, C, R, S, L, ST, A, O and I file types — and the T/C/R sub-element offsets (.PRE/.ACC/.LEN/.POS) — are encoded from the PCCC file-type table and are unverified natively. No real SLC, MicroLogix or PLC-5 has been exercised. Opt in per driver after checking it against the real controller.
    • ⚠️ Status-bit writes are refused — T4:0.DN, T4:0.TT, T4:0.EN, C5:0.CU, C5:0.DN, R6:0.EN and the rest return BadNotSupported whatever the tag's authored data type (the refusal keys on the address); nothing is written to the PLC; health is unchanged. The driver answers the refusal before it creates the tag's runtime, so a first-touch write sends nothing at all — not even the init read, which against a controller without that file used to surface as BadCommunicationError + Degraded health (#593 follow-up). PLC-5 writes are refused the same way. libplctag performs a masked bit write here; a native read-modify-write of the control word would race the PLC updating TT/DN. Reads of status bits are unaffected.
    • ⚠️ On libplctag (the default) a status-bit write is NOT refused — it goes to the controller as a write to the timer/counter/control element (libplctag's bit-tag write; not exercised on a wire — ab_server has no T/C/R files). Nothing in authoring prevents it: the address is free text, any dataType may be chosen (a status bit is naturally authored Bit), and writable defaults to true. Author status-bit tags with "writable": false unless writing them is genuinely intended.
    • PLC-5 native is N-file reads only; every other PLC-5 operation is refused with BadNotSupported. LogixPccc framing is unverified. Explicit Native on either logs a Warning at init.
    • ST (string) byte order is unverified (no capture); string values may be byte-swapped.
    • Unlike AbCip, the native AbLegacy runtime has no element-type check, so a mis-authored same-width type reads as reinterpreted data (as on libplctag), not BadTypeMismatch.
    • Releasing a native tag (evict, reinitialize, shutdown) never blocks on the connection close: the lease is released in the background (ConnectionLease.ReleaseInBackground), the same shape as native AbCip (#579). A re-create cannot overlap the close, because the pool holds the successor connection behind it.

Wire evidence (native PCCC)

Everything below is against the ab_server simulator; no real PCCC controller has been exercised.

What Evidence
N-file read (N7:0) libplctag captures slc500-read-n7, micrologix-read-n7, plc5-read-n7 (codec byte parity) + native AbLegacyReadSmokeTests read on all three profiles
N-file write (N7:5) capture slc500-write-n7 + native AbLegacyReadSmokeTests write/read round trip (SLC 500)
F-file read (F8) one capture, slc500-read-f8 (codec parity only; no native F write on a wire)
S (incl. the default probe S:0), B, T, C, R, L, ST, A, O, I none — encoded from the PCCC file-type table
T/C/R sub-elements (.PRE/.ACC/.LEN/.POS), 6-byte T/C/R element layout none

Native known gaps

  • ⚠️ Simulator-only, and narrow. Only N-file reads/writes and one F8 read are on a wire (ab_server); see Wire evidence. No real SLC/MicroLogix/PLC-5 has been exercised; the real-press gate (Task 21) was read-only and AbCip-only.
  • PLC-5 native is N-file reads only. Every other file type and all PLC-5 writes are refused before the wire and reach the client as BadNotSupported (handle kept, health unchanged; #571 closed). Native is opt-in for every family; an explicit Native on PLC-5 / logixpccc logs a Warning at init.
  • Status-bit sub-element writes (e.g. T4:0.DN, C5:0.DN) are Unsupported natively (they would clobber the control word); nothing goes on the wire — the driver refuses before creating the tag's runtime, so not even an init read is sent (NativeAbLegacyTagRuntime.WriteRefusal is the single predicate, asked through IAbLegacyTagFactory.WriteRefusal). Pinned offline by NativeAbLegacyRefusedWriteTests and on ab_server by AbLegacyUnsupportedPathTests (whose SLC500 fixture has no T/C/R files, which is what makes it discriminating). Sub-element arrays are Unsupported natively. L-file bit indexes above 15 are allowed.
  • ST (string) file layout is uncaptured, so the string byte order is unverified natively.
  • Capture recipe for golden frames: scripts/ab-capture/capture.sh (see AbLegacy-Test-Fixture.md). Follow-up issues: #564 to #577.

Testing

  • Unit tests — tests/Drivers/ZB.MOM.WW.OtOpcUa.Driver.AbLegacy.Tests/ cover the driver, the PCCC address parser, and the host-address parser via fake tag runtimes.
  • Integration tests — tests/Drivers/ZB.MOM.WW.OtOpcUa.Driver.AbLegacy.IntegrationTests/ run against the AB Legacy Docker fixture. See AbLegacy-Test-Fixture.md for the coverage map.
  • Manual client — Driver.AbLegacy.Cli.md.

1-D array support

An AB Legacy tag becomes a 1-D OPC UA array node when its TagConfig JSON carries "isArray": true and "arrayLength": N (N ≥ 1, capped at 256). The canonical rule: isArray: true + arrayLength >= 1 → array; isArray: false (any length) → scalar.

Read mechanism — the driver issues a PCCC multi-element file read (libplctag by default; the opt-in native transport issues the same typed read, chunked under the PCCC payload limit). The tag's file address (e.g. N7:0) is extended by N element count so the transport fetches N consecutive PCCC file elements in one EIP/PCCC request. The response is decoded into N values of the declared AbLegacyDataType. Maximum element count is 256 (PCCC payload limit).

This closes the previously-noted limitation ("single-element addressing today") for the array read path. The opt-in native transport also writes multi-element arrays (chunked); on libplctag array writes remain a follow-up.

Unit test coverage — tests/Drivers/ZB.MOM.WW.OtOpcUa.Driver.AbLegacy.Tests/ covers the multi-element read path via the fake tag runtime. The AB Legacy integration fixture is down during normal dev.

Live-verify — integration-fixture-gated (requires the AB Legacy Docker fixture).

Deferrals — array writes on libplctag (the opt-in native transport writes them), multi-dimensional arrays, per-element historization. arrayLength > 256 is rejected at init with an explicit error (PCCC payload cap).

See Uns.md §Array tags for the cross-driver coverage matrix and the UI authoring flow.

Operational Notes

  • Native heap is invisible to the GC. As with AB CIP, libplctag's native heap does not show up in CLR allocation figures; watch whole-process RSS and use ReinitializeAsync to recycle libplctag handles. (IDriver.GetMemoryFootprint() was deleted as unconsumed in Gitea #525.)
  • PCCC reconnect is more expensive than CIP — legacy PLCs have no connection multiplexing, so the resilience pipeline should use longer backoff than for AB CIP (see docs/v2/driver-specs.md §4).
  • Single-element addressing today — a PCCC file is inherently an array (an N7 file is up to 256 words), but the current tag surface addresses one element per tag; range-spanning tags must be enumerated element-by-element until multi-element addressing lands.