Files
lmxopcua/src/Core/ZB.MOM.WW.OtOpcUa.Core.ScriptedAlarms/ScriptedAlarmDefinition.cs
T
Joseph Doherty 9cad9ed0fc
v2-ci / build (push) Failing after 41s
v2-ci / unit-tests (tests/Core/ZB.MOM.WW.OtOpcUa.Cluster.Tests) (push) Has been skipped
v2-ci / unit-tests (tests/Server/ZB.MOM.WW.OtOpcUa.ControlPlane.Tests) (push) Has been skipped
v2-ci / unit-tests (tests/Server/ZB.MOM.WW.OtOpcUa.OpcUaServer.Tests) (push) Has been skipped
v2-ci / unit-tests (tests/Server/ZB.MOM.WW.OtOpcUa.Runtime.Tests) (push) Has been skipped
v2-ci / unit-tests (tests/Server/ZB.MOM.WW.OtOpcUa.Security.Tests) (push) Has been skipped
v2-ci / integration (tests/Server/ZB.MOM.WW.OtOpcUa.Host.IntegrationTests) (push) Has been skipped
v2-ci / integration (tests/Server/ZB.MOM.WW.OtOpcUa.OpcUaServer.IntegrationTests) (push) Has been skipped
docs(xmldoc): fill missing XML docs + strip tracking-ID comments across src
Adds <summary>/<param>/<returns>/<inheritdoc> where missing and removes
project bookkeeping IDs (task/tracking refs) from shipped code comments,
so the docs read cleanly and CommentChecker is quiet except for known
false positives (PLC/protocol terms, event/IEqualityComparer inheritdoc).
Doc/comment-only; no logic changed; solution builds clean.
2026-07-07 12:38:39 -04:00

51 lines
2.3 KiB
C#

using ZB.MOM.WW.OtOpcUa.Core.Abstractions;
namespace ZB.MOM.WW.OtOpcUa.Core.ScriptedAlarms;
/// <summary>
/// Operator-authored scripted-alarm configuration. Phase 7 Stream E (config DB schema)
/// materializes these from the <c>ScriptedAlarm</c> + <c>Script</c> tables on publish.
/// </summary>
/// <param name="AlarmId">
/// Stable identity for the alarm — used as the OPC UA ConditionId + the key in the
/// state store. Should be globally unique within the cluster; convention is
/// <c>{EquipmentPath}::{AlarmName}</c>.
/// </param>
/// <param name="EquipmentPath">
/// UNS path of the Equipment node the alarm hangs under. Alarm browse lives here;
/// ACL binding inherits this equipment's scope per Phase 6.2.
/// </param>
/// <param name="AlarmName">Human-readable alarm name — used in the browse tree + Admin UI.</param>
/// <param name="Kind">Concrete OPC UA Part 9 subtype the alarm materializes as.</param>
/// <param name="Severity">Static severity; not currently computed by the predicate.</param>
/// <param name="MessageTemplate">
/// Message text with <c>{TagPath}</c> tokens resolved at event-emission time.
/// Unresolvable tokens emit <c>{?}</c> + a structured
/// error so operators can spot stale references.
/// </param>
/// <param name="PredicateScriptSource">
/// Roslyn C# script returning <c>bool</c>. <c>true</c> = alarm condition currently holds (active);
/// <c>false</c> = condition has cleared. Same sandbox rules as virtual tags.
/// </param>
/// <param name="HistorizeToAveva">
/// When true, every transition emission of this alarm flows to the Historian alarm
/// sink (Stream D). Defaults to true — plant alarm history is usually the
/// operator's primary diagnostic. Galaxy-native alarms default false since Galaxy
/// historises them directly.
/// </param>
/// <param name="Retain">
/// Part 9 retain flag — when true, the condition node remains visible after the
/// predicate clears as long as it has un-acknowledged or un-confirmed transitions.
/// Default true.
/// </param>
public sealed record ScriptedAlarmDefinition(
string AlarmId,
string EquipmentPath,
string AlarmName,
AlarmKind Kind,
AlarmSeverity Severity,
string MessageTemplate,
string PredicateScriptSource,
bool HistorizeToAveva = true,
bool Retain = true);