Claude-Session: https://claude.ai/code/session_01GT67ACmpMR7b9LGRPLijMi
9.3 KiB
lmxopcua#780: ScriptedAlarm seam on QA vq03/vq04 and the runner flip on DEV vd03 (2026-11-13)
Status: Part 1 (QA seam) applied, ScriptedAlarm drill PENDING. Part 2 (vd03 flip) DONE. All three nodes run
c9640f5c(see2026-11-13-vd03-qa-to-c9640f5c.md). The owner approved this on 2026-11-13, with WinRM limited to the deploy-type steps: env change,.regbackups, restarts,-Verify, and the temporary AdminUI role-mapping row.
- Health, OPC UA,
/metricsand ConfigDb checks ran from the Mac over HTTP, opc.tcp and SQL (vd03).- Logs were read over SMB.
- No other service was touched.
- No Galaxy writes, no historian writes.
Part 1: QA, Scripting__Runner__Seams__2=ScriptedAlarm
Stage E:\psrem-stage\otopcua-780-scriptedalarm\ on each node:
seam780.ps1 -Mode plan|apply|rollback;restart780.ps1, which restarts the service, waits for/health/ready, then runs-Verifyfrom thec9640f5cstage'sinstall\;sql780.ps1 -Action show|addrole|delrole, which uses the service's own ConfigDb connection, with the password inSQLCMDPASSWORDand never printed;envdigest.ps1.
The backup folder backup\ has a protected DACL (SYSTEM + Administrators).
Before:
- ServiceLevel vq03 240, vq04 250: Primary vq04, as left by this morning's deploy.
- Both nodes:
/health/ready200,Out-of-process script runner ready., shards 0 and 1 up. - Canary Good on both nodes.
- ConfigDb (QA): 2 scripts (the canary), 1 VT, 0 scripted alarms, 0 role mappings. Current deployment
5905003erev82dd0598c37f41f8…, the canary-only revision.
| Step | vq03 | vq04 |
|---|---|---|
.reg export |
backup\OtOpcUaHost-pre-780-seam2.reg (31,002 B) |
same name (30,244 B) |
| Env before (names + SHA only) | 48 entries, ordered a04ca3f1fecb / sorted 78e6acfab539 (= this morning's post-deploy digest) |
47 entries, c6adaf68ef48 / 5df6eacf7152 (= this morning's) |
| Flags before | Scripting__Runner=OutOfProcess, Seams__0=Calculation, Seams__1=VirtualTag, Seams__2 absent, Scripting__Worker__* present |
same |
| Change | Scripting__Runner__Seams__2=ScriptedAlarm inserted right after Seams__1, so the installer's two Scripting__Worker__* entries stay last |
same |
| Env after | 49 entries, 5750bbeb4734 / 4263c3ac5a46; diff = exactly the one added entry, 0 removed |
48 entries, ef146b2681b4 / d19e968212f3; same diff |
| Restart (one at a time, Secondary first) | 08:06:30.9Z → ready 08:06:41.1Z (10.2 s). SL after: vq03 240, vq04 250 | 08:07:21.2Z → ready 08:08:00.4Z (39.2 s; the stop alone took ~30 s, see the deviation below) |
-Verify after the restart |
VERIFY OK 21/21 | VERIFY OK 21/21 |
Failover (vq03 sampled every ~4 s while vq04 restarted):
- vq03 stayed 240 /
/health/active503 from 08:07:19Z to 08:07:48Z. - From 08:07:52Z it read 250 / 200 on every sample.
- After vq04 was back: vq03 250 (Primary), vq04 240, with no failback.
After both restarts:
- Both nodes:
/health/ready200, 5/5 components,Out-of-process script runner ready., akka 2 members / 0 unreachable. /health/active200 on vq03 and 503 on vq04.- Canary
canary-calc-secondsandcanary-vt-secondGood and advancing on both endpoints.
There is no startup log line that lists the selected seams (ScriptRunnerSelection logs only warnings), so the env entry
is the evidence until a scripted alarm runs. The drill's proof that the seam is live is
otopcua_script_ipc_roundtrip{kind="alarm"} counting on both nodes.
Deviation: a planned stop of the Primary takes ~30 s (filed as lmxopcua#906)
vq04 logged Application is shutting down... at 03:07:21.289 EST. It then logged nothing but DbCommand lines until 03:07:51.292:
The request stream was aborted;HTTP POST /localdb_sync.v1.LocalDbSync/Sync responded 200 in 76909 ms.
Only after that did it run Akka CoordinatedShutdown → Leaving → OldestChanged to vq03.
The host waits on the peer's open LocalDb sync stream until Kestrel's 30 s shutdown timeout. Throughout that wait the stopping Primary keeps vq03 at 240. The sync client (vq03) stops in about 1 s, so the earlier failover gates, which stopped vq03, never showed this.
ScriptedAlarm drill: PENDING
Prepared, not run. The QA AdminUI needs a signed-in session: QA has no Security:DeployApiKey, and authoring and deploying
go through the AdminUI. The temporary LdapGroupRoleMapping row (SCADA-Admins → Administrator, system-wide, Notes
lmxopcua#780 drill temp) was added with sql780.ps1 -Action addrole, and the local forwarder localhost:19003 →
wonder-app-vq03:9000 was started. The agent does not type the LDAP password itself, so the drill waits for an operator
sign-in.
Planned content (all on the canary equipment EQ-ec3979550d90; HistorizeToAveva off on every alarm, so no historian write):
| Object | Value |
|---|---|
Script ScriptRunnerCanary-AlarmPred |
return ((int)ctx.GetTag("script-runner-canary/Device1/canary-calc-seconds").Value) % 20 >= 10; (input changes every second; active for 10 s, inactive for 10 s) |
Alarm canary-alarm-cycle |
AlarmCondition, severity 100, predicate above, Retain on, HistorizeToAveva off |
Script ScriptRunnerCanary-AlarmRunaway |
var v = ctx.GetTag("script-runner-canary/Device1/canary-calc-seconds").Value; while (true) { } |
Alarm canary-alarm-runaway |
AlarmCondition, severity 100, HistorizeToAveva off, deployed only after the normal alarm has fired and cleared and ipc_roundtrip{kind="alarm"} counts on both nodes |
Cleanup: delete both alarms and both scripts, deploy, and expect the revision back at 82dd0598…. Delete the role row
(sql780.ps1 -Action delrole) and stop the forwarder.
Part 2: DEV vd03, runner flip to OutOfProcess
ConfigDb (read-only SQL from the Mac):
- 0 scripts, 0 virtual tags, 0 scripted alarms. The only driver is FOCAS.
- Current deployment
595cb909revfa9a2e28…. The draft still drifts from it because of this morning's #903 edit-and-revert.
Seams. All three seams were set, the same as QA, even though vd03 has no scripts of any kind. The seam list only decides where a future script runs, and DEV should match QA. Dropping every seam for kinds with no scripts would have left the flip with no effect.
No canary on vd03. Any deploy would seal the drifted draft as a new revision, so fa9a2e28… could not be restored
afterwards. The worker start is therefore not observable on DEV: shards stay not started until a first script.
Stage E:\ApiInstall\_stage-otopcua-780-flip\ (flip780vd03.ps1 -Mode plan|apply|rollback, restart780vd03.ps1, envdigest.ps1).
| Step | Result |
|---|---|
| Plan | Env 28 entries, 05db5d058fee / e3f876a407a8 (= this morning's). No Scripting__*. #901 record: InstallRoot E:\ApiInstall\OtOpcUa, LocalSystem, PeCacheDir C:\ProgramData\OtOpcUa\script-pe-cache, ConfigureHostService 0, 5 DenyPaths. Installer hashes 7D4078CB… / AE9D84FD… (= the pack). |
| Backup | E:\ApiInstall\OtOpcUa-backups\pre-20261113-780-runner-flip\{OtOpcUaHost.reg, OtOpcUaScriptWorker.reg} (protected) |
| Installer, supported path | Full recorded arguments plus -ConfigureHostService, service up. 14 steps: SettingsRecord changed (now records ConfigureHostService=1) and HostServiceEnv changed (added Scripting__Worker__Identity=NT SERVICE\OtOpcUaScriptWorker, Scripting__Worker__PeCacheDir=C:\ProgramData\OtOpcUa\script-pe-cache). The other 12 steps were unchanged. 0 env entries removed. |
| Runner entries | Scripting__Runner=OutOfProcess, Seams__0=Calculation, Seams__1=VirtualTag, Seams__2=ScriptedAlarm, inserted ahead of the Worker entries |
| Env after | 34 entries, 69a493345099 / caa047aaaf42; diff = exactly those 6 added, 0 removed |
| Restart | 08:11:53.2Z → ready 08:12:02.3Z (9.1 s) |
-Verify |
VERIFY OK 14/14 (13 before + HostServiceEnv) |
vd03 gates
| Gate | Result |
|---|---|
| Health | /health/ready 200, 5/5 components; script-runner: Out-of-process script runner ready. (state=Ready, peCache=true, shards not started); /health/active 200 |
| ServiceLevel | 250 on three fresh-session reads (opc.tcp://10.220.157.247:4840) |
| Runner metrics | otopcua_script_runner_state 0; otopcua_script_worker_up 0 for every shard (idle, no scripts) |
| FOCAS | 22 raw variables: 21 Good, Program/BlockCount BadNoData (as before) |
| Boot log | roles=[admin,driver]; raw subtree materialised (containers=10, tags=22, … failed=0); credential-reference preflight clean; no FTL, no ScriptWorker line. ERR lines were only the certificate-domain noise from the gate's own reads by IP. |
Rollback
- QA seam:
- Run
E:\psrem-stage\otopcua-780-scriptedalarm\seam780.ps1 -Mode rollbackon each node. It removes onlySeams__2. - Restart the Secondary, then the Primary (
restart780.ps1). - Alternatively, import
backup\OtOpcUaHost-pre-780-seam2.reg.
- Run
- vd03 flip:
- Run
E:\ApiInstall\_stage-otopcua-780-flip\flip780vd03.ps1 -Mode rollback. It removes the fourScripting__Runner*entries and keeps the Worker entries, which are harmless under InProcess. - Restart.
- For the full pre-flip state, import both
.regfiles fromE:\ApiInstall\OtOpcUa-backups\pre-20261113-780-runner-flip\. They restore the host env and the #901 record with ConfigureHostService=0.
- Run