Probe 'failover <primary> <backup> <mode> <dir>' drives ScadaBridge's own DataConnectionActor (production primary/backup machine, real DataConnectionFactory, default DataConnectionOptions, FailoverRetryCount 3) against two servers; run.py loses the primary (SIGKILL or SIGSTOP) once the probe reports a steady primary, and the probe requires Bad quality on loss, "Connected to backup", the backup's own value, a fresh ConditionRefresh replaying the native condition, and a write via the backup. rig-failover.sh runs the same probe against the local docker-dev central pair. Matrix legs gain a UNS subscription case and a Server-object alarm subscription on the reconnected session whose ConditionRefresh must replay the active condition (11 cases). run.py gains --versions, --suites, --failover-modes and --failover-loss. Claude-Session: https://claude.ai/code/session_01GT67ACmpMR7b9LGRPLijMi