Joseph Doherty cb7b81a87a Phase 3 PR 30 — Modbus integration-test project scaffold. New tests/ZB.MOM.WW.OtOpcUa.Driver.Modbus.IntegrationTests project is the harness modbus-test-plan.md called for: a skip-when-unreachable fixture that TCP-probes a Modbus simulator endpoint (MODBUS_SIM_ENDPOINT, default localhost:502) once per test session, a DL205 device profile stub (single writable holding register at address 100, probe disabled to avoid racing with assertions), and one happy-path smoke test that initializes the real ModbusDriver + real ModbusTcpTransport, writes a known Int16 value, reads it back, and asserts status=0 + value round-trip. No DL205 quirk assertions yet — those land one-per-PR as the user validates each behavior in ModbusPal (word order for 32-bit, register-zero access, coil addressing base, max registers per FC03, response framing under load, exception code on protected-bit coil write).
ModbusSimulatorFixture is a collection fixture so the 2s TCP probe runs once per run, not per test; SkipReason gets a clear operator-facing message ('start ModbusPal or override MODBUS_SIM_ENDPOINT'). Tests call Assert.Skip(sim.SkipReason) rather than silently returning — matches the test-plan convention and reads cleanly in CI logs. DL205Profile.BuildOptions deliberately disables the background probe loop since integration tests drive reads explicitly and the probe would race with assertions. Tag naming uses the DL205_ prefix so filter 'DisplayName~DL205' surfaces device-specific failures at a glance.
Project references: xunit.v3 + Shouldly + Microsoft.NET.Test.Sdk + xunit.runner.visualstudio (matches the existing Driver.Modbus.Tests unit project), project ref to src/Driver.Modbus. Registered in ZB.MOM.WW.OtOpcUa.slnx under tests/. ModbusPal/README.md documents the dev loop (install ModbusPal jar, load profile, start simulator, dotnet test), explains MODBUS_SIM_ENDPOINT override for real-PLC benchwork, and flags DL205.xmpp as the first profile to add in a follow-up PR.
dotnet test run against the scaffold (no simulator running) skips cleanly: 0 failed, 0 passed, 1 skipped, with the SkipReason surfaced. dotnet build clean (0 warnings, 0 errors). Updated docs/v2/modbus-test-plan.md to mark the scaffold PR done and renumbered future PRs from 'PR 27+' to 'PR 31+' to stay in sync with the actual PR chain.

Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
2026-04-18 15:02:39 -04:00
..
Phase 3 PR 28 — Admin UI cert-trust management page. New /certificates route (FleetAdmin-only) surfaces the OPC UA server's PKI store rejected + trusted certs and gives operators Trust / Delete / Revoke actions so rejected client certs can be promoted without touching disk. CertTrustService reads $PkiStoreRoot/{rejected,trusted}/certs/*.der files directly via X509CertificateLoader — no Opc.Ua dependency in the Admin project, which keeps the Admin host runnable on a machine that doesn't have the full Server install locally (only needs the shared PKI directory reachable; typical deployment has Admin + Server side-by-side on the same box and PkiStoreRoot defaults match so a plain-vanilla install needs no override). CertTrustOptions bound from the Admin's 'CertTrust:PkiStoreRoot' section, default %ProgramData%\OtOpcUa\pki (matches OpcUaServerOptions.PkiStoreRoot default). Trust action moves the .der from rejected/certs/ to trusted/certs/ via File.Move(overwrite:true) — idempotent, tolerates a concurrent operator doing the same move. Delete wipes the file. Revoke removes from trusted/certs/ (Opc.Ua re-reads the Directory store on each new client handshake, so no explicit reload signal is needed; operators retry the rejected connection after trusting). Thumbprint matching is case-insensitive because X509Certificate2.Thumbprint is upper-case hex but operators copy-paste from logs that sometimes lowercase it. Malformed files in the store are logged + skipped — a single bad .der can't take the whole management page offline. Missing store directories produce empty lists rather than exceptions so a pristine install (Server never run yet, no rejected/trusted dirs yet) doesn't crash the page.
2026-04-18 14:37:55 -04:00
Phase 1 Streams B–E scaffold + Phase 2 Streams A–C scaffold — 8 new projects with ~70 new tests, all green alongside the 494 v1 IntegrationTests baseline (parity preserved: no v1 tests broken; legacy OtOpcUa.Host untouched). Phase 1 finish: Configuration project (16 entities + 10 enums + DbContext + DesignTimeDbContextFactory + InitialSchema/StoredProcedures/AuthorizationGrants migrations — 8 procs including sp_PublishGeneration with MERGE on ExternalIdReservation per decision #124, sp_RollbackToGeneration cloning rows into a new published generation, sp_ValidateDraft with cross-cluster-namespace + EquipmentUuid-immutability + ZTag/SAPID reservation pre-flight, sp_ComputeGenerationDiff with CHECKSUM-based row signature — plus OtOpcUaNode/OtOpcUaAdmin SQL roles with EXECUTE grants scoped to per-principal-class proc sets and DENY UPDATE/DELETE/INSERT/SELECT on dbo schema); managed DraftValidator covering UNS segment regex, path length, EquipmentUuid immutability across generations, same-cluster namespace binding (decision #122), reservation pre-flight, EquipmentId derivation (decision #125), driver↔namespace compatibility — returning every failing rule in one pass; LiteDB local cache with round-trip + ring pruning + corruption-fast-fail; GenerationApplier with per-entity Added/Removed/Modified diff and dependency-ordered callbacks (namespace → driver → device → equipment → poll-group → tag, Removed before Added); Core project with GenericDriverNodeManager (scaffold for the Phase 2 Galaxy port) and DriverHost lifecycle registry; Server project using Microsoft.Extensions.Hosting BackgroundService replacing TopShelf, with NodeBootstrap that falls back to LiteDB cache when the central DB is unreachable (decision #79); Admin project scaffolded as Blazor Server with Bootstrap 5 sidebar layout, cookie auth, three admin roles (ConfigViewer/ConfigEditor/FleetAdmin), Cluster + Generation services fronting the stored procs. Phase 2 scaffold: Driver.Galaxy.Shared (netstandard2.0) with full MessagePack IPC contract surface — Hello version negotiation, Open/CloseSession, Heartbeat, DiscoverHierarchy + GalaxyObjectInfo/GalaxyAttributeInfo, Read/WriteValues, Subscribe/Unsubscribe/OnDataChange, AlarmSubscribe/Event/Ack, HistoryRead, HostConnectivityStatus, Recycle — plus length-prefixed framing (decision #28) with a 16 MiB cap and thread-safe FrameWriter/FrameReader; Driver.Galaxy.Host (net48) implementing the Tier C cross-cutting protections from driver-stability.md — strict PipeAcl (allow configured server SID only, explicit deny on LocalSystem + Administrators), PipeServer with caller-SID verification via pipe.RunAsClient + WindowsIdentity.GetCurrent and per-process shared-secret Hello, Galaxy-specific MemoryWatchdog (warn at max(1.5×baseline, +200 MB), soft-recycle at max(2×baseline, +200 MB), hard ceiling 1.5 GB, slope ≥5 MB/min over 30-min rolling window), RecyclePolicy (1 soft recycle per hour cap + 03:00 local daily scheduled), PostMortemMmf (1000-entry ring buffer in %ProgramData%\OtOpcUa\driver-postmortem\galaxy.mmf, survives hard crash, readable cross-process), MxAccessHandle : SafeHandle (ReleaseHandle loops Marshal.ReleaseComObject until refcount=0 then calls optional unregister callback), StaPump with responsiveness probe (BlockingCollection dispatcher for Phase 1 — real Win32 GetMessage/DispatchMessage pump slots in with the same semantics when the Galaxy code lift happens), IsExternalInit shim for init setters on .NET 4.8; Driver.Galaxy.Proxy (net10) implementing IDriver + ITagDiscovery forwarding over the IPC channel with MX data-type and security-classification mapping, plus Supervisor pieces — Backoff (5s → 15s → 60s capped, reset-on-stable-run), CircuitBreaker (3 crashes per 5 min opens; 1h → 4h → manual cooldown escalation; sticky alert doesn't auto-clear), HeartbeatMonitor (2s cadence, 3 consecutive misses = host dead per driver-stability.md). Infrastructure: docker SQL Server remapped to host port 14330 to coexist with the native MSSQL14 Galaxy ZB DB instance on 1433; NuGetAuditSuppress applied per-project for two System.Security.Cryptography.Xml advisories that only reach via EF Core Design with PrivateAssets=all (fix ships in 11.0.0-preview); .slnx gains 14 project registrations. Deferred with explicit TODOs in docs/v2/implementation/phase-2-partial-exit-evidence.md: Phase 1 Stream E Admin UI pages (Generations listing + draft-diff-publish, Equipment CRUD with OPC 40010 fields, UNS Areas/Lines tabs, ACLs + permission simulator, Generic JSON config editor, SignalR real-time, Release-Reservation + Merge-Equipment workflows, LDAP login page, AppServer smoke test per decision #142), Phase 2 Stream D (Galaxy MXAccess code lift out of legacy OtOpcUa.Host, dual-service installer, appsettings → DriverConfig migration script, legacy Host deletion — blocked by parity), Phase 2 Stream E (v1 IntegrationTests against v2 topology, Client.CLI walkthrough diff, four 2026-04-13 stability findings regression tests, adversarial review — requires live MXAccess runtime).
2026-04-17 21:35:25 -04:00
Phase 3 PR 15 — alarm-condition contract in IAddressSpaceBuilder + wire OnAlarmEvent through GenericDriverNodeManager. IAddressSpaceBuilder.IVariableHandle gains MarkAsAlarmCondition(AlarmConditionInfo) which returns an IAlarmConditionSink. AlarmConditionInfo carries SourceName/InitialSeverity/InitialDescription. Concrete address-space builders (the upcoming PR 16 OPC UA server backend) materialize a sibling AlarmConditionState node on the first call; the sink receives every lifecycle transition the generic node manager forwards. GenericDriverNodeManager gains a CapturingBuilder wrapper that transparently wraps every Folder/Variable call — the wrapper observes MarkAsAlarmCondition calls without participating in materialization, captures the resulting IAlarmConditionSink into an internal source-node-id → sink ConcurrentDictionary keyed by IVariableHandle.FullReference. After DiscoverAsync completes, if the driver implements IAlarmSource the node manager subscribes to OnAlarmEvent and routes every AlarmEventArgs to the sink registered for args.SourceNodeId — unknown source ids are dropped silently (may belong to another driver or to a variable the builder chose not to flag). Dispose unsubscribes the forwarder to prevent dangling invocation-list references across node-manager rebuilds. GalaxyProxyDriver.DiscoverAsync now calls handle.MarkAsAlarmCondition(new AlarmConditionInfo(fullName, AlarmSeverity.Medium, null)) on every attr.IsAlarm=true variable — severity seed is Medium because the live Priority byte arrives through the subsequent GalaxyAlarmEvent stream (which PR 14's GalaxyAlarmTracker now emits); the Admin UI sees the severity update on the first transition. RecordingAddressSpaceBuilder in Driver.Galaxy.E2E gains a RecordedAlarmCondition list + a RecordingSink implementation that captures AlarmEventArgs for test assertion — the E2E parity suite can now verify alarm-condition registration shape in addition to folder/variable shape. Tests (4 new GenericDriverNodeManagerTests): Alarm_events_are_routed_to_the_sink_registered_for_the_matching_source_node_id — 2 alarms registered (Tank.HiHi + Heater.OverTemp), driver raises an event for Tank.HiHi, the Tank.HiHi sink captures the payload, the Heater.OverTemp sink does not (tag-scoped fan-out, not broadcast); Non_alarm_variables_do_not_register_sinks — plain Tank.Level in the same discover is not in TrackedAlarmSources; Unknown_source_node_id_is_dropped_silently — a transition for Unknown.Source doesn't reach any sink + no exception; Dispose_unsubscribes_from_OnAlarmEvent — post-dispose, a transition for a previously-registered tag is no-op because the forwarder detached. InternalsVisibleTo('ZB.MOM.WW.OtOpcUa.Core.Tests') added to Core csproj so TrackedAlarmSources internal property is visible to the test. Full solution: 0 errors, 152 unit tests pass (8 Core + 14 Proxy + 14 Admin + 24 Configuration + 6 Shared + 84 Galaxy.Host + 2 Server). PR 16 will implement the concrete OPC UA address-space builder that materializes AlarmConditionState from this contract.
2026-04-18 07:51:35 -04:00
Phase 3 PR 15 — alarm-condition contract in IAddressSpaceBuilder + wire OnAlarmEvent through GenericDriverNodeManager. IAddressSpaceBuilder.IVariableHandle gains MarkAsAlarmCondition(AlarmConditionInfo) which returns an IAlarmConditionSink. AlarmConditionInfo carries SourceName/InitialSeverity/InitialDescription. Concrete address-space builders (the upcoming PR 16 OPC UA server backend) materialize a sibling AlarmConditionState node on the first call; the sink receives every lifecycle transition the generic node manager forwards. GenericDriverNodeManager gains a CapturingBuilder wrapper that transparently wraps every Folder/Variable call — the wrapper observes MarkAsAlarmCondition calls without participating in materialization, captures the resulting IAlarmConditionSink into an internal source-node-id → sink ConcurrentDictionary keyed by IVariableHandle.FullReference. After DiscoverAsync completes, if the driver implements IAlarmSource the node manager subscribes to OnAlarmEvent and routes every AlarmEventArgs to the sink registered for args.SourceNodeId — unknown source ids are dropped silently (may belong to another driver or to a variable the builder chose not to flag). Dispose unsubscribes the forwarder to prevent dangling invocation-list references across node-manager rebuilds. GalaxyProxyDriver.DiscoverAsync now calls handle.MarkAsAlarmCondition(new AlarmConditionInfo(fullName, AlarmSeverity.Medium, null)) on every attr.IsAlarm=true variable — severity seed is Medium because the live Priority byte arrives through the subsequent GalaxyAlarmEvent stream (which PR 14's GalaxyAlarmTracker now emits); the Admin UI sees the severity update on the first transition. RecordingAddressSpaceBuilder in Driver.Galaxy.E2E gains a RecordedAlarmCondition list + a RecordingSink implementation that captures AlarmEventArgs for test assertion — the E2E parity suite can now verify alarm-condition registration shape in addition to folder/variable shape. Tests (4 new GenericDriverNodeManagerTests): Alarm_events_are_routed_to_the_sink_registered_for_the_matching_source_node_id — 2 alarms registered (Tank.HiHi + Heater.OverTemp), driver raises an event for Tank.HiHi, the Tank.HiHi sink captures the payload, the Heater.OverTemp sink does not (tag-scoped fan-out, not broadcast); Non_alarm_variables_do_not_register_sinks — plain Tank.Level in the same discover is not in TrackedAlarmSources; Unknown_source_node_id_is_dropped_silently — a transition for Unknown.Source doesn't reach any sink + no exception; Dispose_unsubscribes_from_OnAlarmEvent — post-dispose, a transition for a previously-registered tag is no-op because the forwarder detached. InternalsVisibleTo('ZB.MOM.WW.OtOpcUa.Core.Tests') added to Core csproj so TrackedAlarmSources internal property is visible to the test. Full solution: 0 errors, 152 unit tests pass (8 Core + 14 Proxy + 14 Admin + 24 Configuration + 6 Shared + 84 Galaxy.Host + 2 Server). PR 16 will implement the concrete OPC UA address-space builder that materializes AlarmConditionState from this contract.
2026-04-18 07:51:35 -04:00
Phase 2 PR 14 — alarm subsystem wire-up. Per IsAlarm=true attribute (PR 9 added the discovery flag), GalaxyAlarmTracker in Backend/Alarms/ advises the four Galaxy alarm-state attributes: .InAlarm (boolean alarm active), .Priority (int severity), .DescAttrName (human-readable description), .Acked (boolean acknowledged). Runs the OPC UA Part 9 alarm lifecycle state machine simplified for the Galaxy AlarmExtension model and raises AlarmTransition events on transitions operators must react to — Active (InAlarm false→true, default Unacknowledged), Acknowledged (Acked false→true while InAlarm still true), Inactive (InAlarm true→false). MxAccessGalaxyBackend instantiates the tracker in its constructor with delegate-based subscribe/unsubscribe/write pointers to MxAccessClient, hooks TransitionRaised to forward each transition through the existing OnAlarmEvent IPC event that PR 4 ConnectionSink wires into MessageKind.AlarmEvent frames — no new contract messages required since GalaxyAlarmEvent already exists in Shared.Contracts. Field mapping: EventId = fresh Guid.ToString('N') per transition, ObjectTagName = alarm attribute full reference, AlarmName = alarm attribute full reference, Severity = tracked Priority, StateTransition = 'Active'|'Acknowledged'|'Inactive', Message = DescAttrName or tag fallback, UtcUnixMs = transition time. DiscoverAsync caches every IsAlarm=true attribute's full reference (tag.attribute) into _discoveredAlarmTags (ConcurrentBag cleared-then-filled on every re-Discover to track Galaxy redeploys). SubscribeAlarmsAsync iterates the cache and advises each via GalaxyAlarmTracker.TrackAsync; best-effort per-alarm — a subscribe failure on one alarm doesn't abort the whole call since operators prefer partial alarm coverage to none. Tracker is internally idempotent on repeat Track calls (second invocation for same alarm tag is a no-op; already-subscribed check short-circuits before the 4 MXAccess sub calls). Subscribe-failure rollback inside TrackAsync removes the alarm state + unadvises any of the 4 that did succeed so a partial advise can't leak a phantom tracking entry. AcknowledgeAlarmAsync routes to tracker.AcknowledgeAsync which writes the operator comment to <tag>.AckMsg via MxAccessClient.WriteAsync — writes use the existing MXAccess OnWriteComplete TCS-by-handle path (PR 4 Medium 4) so a runtime-refused ack bubbles up as Success=false rather than false-positive. State-machine quirks preserved from v1: (1) initial Acked=true on subscribe does NOT fire Acknowledged (alarm at rest, pre-acknowledged — default state is Acked=true so the first subscribe callback is a no-op transition), (2) Acked false→true only fires Acknowledged when InAlarm is currently true (acking a latched-inactive alarm is not a user-visible transition), (3) Active transition clears the Acked flag in-state so the next Acked callback correctly fires Acknowledged (v1 had this buried in the ConditionState logic; we track it on the AlarmState struct directly). Priority value handled as int/short/long via type pattern match with int.MaxValue guard — Galaxy attribute category returns varying CLR types (Int32 is canonical but some older templates use Int16), and a long overflow cast to int would silently corrupt the severity. Dispose cascade in MxAccessGalaxyBackend.Dispose: alarm-tracker unsubscribe→dispose, probe-manager unsubscribe→dispose, mx.ConnectionStateChanged detach, historian dispose — same discipline PR 6 / PR 8 / PR 13 established so dangling invocation-list refs don't survive a backend recycle. #pragma warning disable CS0067 around OnAlarmEvent removed since the event is now raised. Tests (9 new, GalaxyAlarmTrackerTests): four-attribute subscribe per alarm, idempotent repeat-track, InAlarm false→true fires Active with Priority + Desc, InAlarm true→false fires Inactive, Acked false→true while InAlarm fires Acknowledged, Acked transition while InAlarm=false does not fire, AckMsg write path carries the comment, snapshot reports latest four fields, foreign probe callback for a non-tracked tag is silently dropped. Full Galaxy.Host.Tests Unit suite 84 pass / 0 fail (9 new alarm + 12 PR 13 probe + 21 PR 12 quality + 42 pre-existing). Galaxy.Host builds clean (0/0). Branches off phase-2-pr13-runtime-probe so the MxAccessGalaxyBackend constructor/Dispose chain gets the probe-manager + alarm-tracker wire-up in a coherent order; fast-forwards if PR 13 merges first.
2026-04-18 07:34:13 -04:00
Phase 2 PR 7 — wire IHistoryProvider.ReadProcessedAsync end-to-end. PR 5 ported HistorianDataSource.ReadAggregateAsync into Galaxy.Host but left it internal — GalaxyProxyDriver.ReadProcessedAsync still threw NotSupportedException, so OPC UA clients issuing HistoryReadProcessed requests against the v2 topology got rejected at the driver boundary. This PR closes that gap by adding two new Shared.Contracts messages (HistoryReadProcessedRequest/Response, MessageKind 0x62/0x63), routing them through GalaxyFrameHandler, implementing HistoryReadProcessedAsync on all three IGalaxyBackend implementations (Stub/DbBacked return the canonical "pending" Success=false, MxAccessGalaxyBackend delegates to _historian.ReadAggregateAsync), mapping HistorianAggregateSample → GalaxyDataValue at the IPC boundary (null bucket Value → BadNoData 0x800E0000u, otherwise Good 0u), and flipping GalaxyProxyDriver.ReadProcessedAsync from the NotSupported throw to a real IPC call with OPC UA HistoryAggregateType enum mapped to Wonderware AnalogSummary column name on the Proxy side (Average → "Average", Minimum → "Minimum", Maximum → "Maximum", Count → "ValueCount", Total → NotSupported since there's no direct SDK column for sum). Decision #13 IPC data-shape stays intact — HistoryReadProcessedResponse carries GalaxyDataValue[] with the same MessagePack value + OPC UA StatusCode + timestamps shape as the other history responses, so the Proxy's existing ToSnapshot helper handles the conversion without a new code path. MxAccessGalaxyBackend.HistoryReadProcessedAsync guards: null historian → "Historian disabled" (symmetric with HistoryReadAsync); IntervalMs <= 0 → "HistoryReadProcessed requires IntervalMs > 0" (prevents division-by-zero inside the SDK's Resolution parameter); exception during SDK call → Success=false Values=[] with the message so the Proxy surfaces it as InvalidOperationException with a clean error chain. Tests — HistoryReadProcessedTests (new, 4 cases): disabled-error when historian null, rejects zero interval, maps Good sample with Value=12.34 and the Proxy-supplied AggregateColumn + IntervalMs flow unchanged through to the fake IHistorianDataSource, maps null Value bucket to 0x800E0000u BadNoData with null ValueBytes. AggregateColumnMappingTests (new, 5 cases in Proxy.Tests): theory covers all 4 supported HistoryAggregateType enum values → correct column string, and asserts Total throws NotSupportedException with a message that steers callers to Average/Minimum/Maximum/Count (the SDK's AnalogSummaryQueryResult doesn't expose a sum column — the closest is Average × ValueCount which is the responsibility of a caller-side aggregation rather than an extra IPC round-trip). InternalsVisibleTo added to Galaxy.Proxy csproj so Proxy.Tests can reach the internal MapAggregateToColumn static. Builds — Galaxy.Host (net48 x86) + Galaxy.Proxy (net10) both 0 errors, full solution 201 warnings (pre-existing) / 0 errors. Test counts — Host.Tests Unit suite: 28 pass (4 new processed + 9 PR5 historian + 15 pre-existing); Proxy.Tests Unit suite: 14 pass (5 new column-mapping + 9 pre-existing). Deferred to a later PR — ReadAtTime + ReadEvents + Health IPC surfaces (HistorianDataSource has them ported in PR 5 but they need additional contract messages and would push this PR past a comfortable review size); the alarm subsystem wire-up (OnAlarmEvent raising from MxAccessGalaxyBackend) which overlaps the ReadEventsAsync IPC work since both pull from HistorianAccess.CreateEventQuery on the SDK side; the Proxy-side quality-byte refinement where HistorianDataSource's per-sample raw quality byte gets decoded through the existing QualityMapper instead of the category-only mapping in ToWire(HistorianSample) — doesn't change correctness today since Good/Uncertain/Bad categories are all the Admin UI and OPC UA clients surface, but richer OPC DA status codes (BadNotConnected, UncertainSubNormal, etc.) are available on the wire and the Proxy could promote them before handing DataValueSnapshot to ISubscribable consumers. This PR branches off phase-2-pr5-historian because it directly extends the Historian IPC surface added there; if PR 5 merges first PR 7 fast-forwards, otherwise it needs a rebase after PR 5 lands.
2026-04-18 05:53:01 -04:00
Phase 1 Streams B–E scaffold + Phase 2 Streams A–C scaffold — 8 new projects with ~70 new tests, all green alongside the 494 v1 IntegrationTests baseline (parity preserved: no v1 tests broken; legacy OtOpcUa.Host untouched). Phase 1 finish: Configuration project (16 entities + 10 enums + DbContext + DesignTimeDbContextFactory + InitialSchema/StoredProcedures/AuthorizationGrants migrations — 8 procs including sp_PublishGeneration with MERGE on ExternalIdReservation per decision #124, sp_RollbackToGeneration cloning rows into a new published generation, sp_ValidateDraft with cross-cluster-namespace + EquipmentUuid-immutability + ZTag/SAPID reservation pre-flight, sp_ComputeGenerationDiff with CHECKSUM-based row signature — plus OtOpcUaNode/OtOpcUaAdmin SQL roles with EXECUTE grants scoped to per-principal-class proc sets and DENY UPDATE/DELETE/INSERT/SELECT on dbo schema); managed DraftValidator covering UNS segment regex, path length, EquipmentUuid immutability across generations, same-cluster namespace binding (decision #122), reservation pre-flight, EquipmentId derivation (decision #125), driver↔namespace compatibility — returning every failing rule in one pass; LiteDB local cache with round-trip + ring pruning + corruption-fast-fail; GenerationApplier with per-entity Added/Removed/Modified diff and dependency-ordered callbacks (namespace → driver → device → equipment → poll-group → tag, Removed before Added); Core project with GenericDriverNodeManager (scaffold for the Phase 2 Galaxy port) and DriverHost lifecycle registry; Server project using Microsoft.Extensions.Hosting BackgroundService replacing TopShelf, with NodeBootstrap that falls back to LiteDB cache when the central DB is unreachable (decision #79); Admin project scaffolded as Blazor Server with Bootstrap 5 sidebar layout, cookie auth, three admin roles (ConfigViewer/ConfigEditor/FleetAdmin), Cluster + Generation services fronting the stored procs. Phase 2 scaffold: Driver.Galaxy.Shared (netstandard2.0) with full MessagePack IPC contract surface — Hello version negotiation, Open/CloseSession, Heartbeat, DiscoverHierarchy + GalaxyObjectInfo/GalaxyAttributeInfo, Read/WriteValues, Subscribe/Unsubscribe/OnDataChange, AlarmSubscribe/Event/Ack, HistoryRead, HostConnectivityStatus, Recycle — plus length-prefixed framing (decision #28) with a 16 MiB cap and thread-safe FrameWriter/FrameReader; Driver.Galaxy.Host (net48) implementing the Tier C cross-cutting protections from driver-stability.md — strict PipeAcl (allow configured server SID only, explicit deny on LocalSystem + Administrators), PipeServer with caller-SID verification via pipe.RunAsClient + WindowsIdentity.GetCurrent and per-process shared-secret Hello, Galaxy-specific MemoryWatchdog (warn at max(1.5×baseline, +200 MB), soft-recycle at max(2×baseline, +200 MB), hard ceiling 1.5 GB, slope ≥5 MB/min over 30-min rolling window), RecyclePolicy (1 soft recycle per hour cap + 03:00 local daily scheduled), PostMortemMmf (1000-entry ring buffer in %ProgramData%\OtOpcUa\driver-postmortem\galaxy.mmf, survives hard crash, readable cross-process), MxAccessHandle : SafeHandle (ReleaseHandle loops Marshal.ReleaseComObject until refcount=0 then calls optional unregister callback), StaPump with responsiveness probe (BlockingCollection dispatcher for Phase 1 — real Win32 GetMessage/DispatchMessage pump slots in with the same semantics when the Galaxy code lift happens), IsExternalInit shim for init setters on .NET 4.8; Driver.Galaxy.Proxy (net10) implementing IDriver + ITagDiscovery forwarding over the IPC channel with MX data-type and security-classification mapping, plus Supervisor pieces — Backoff (5s → 15s → 60s capped, reset-on-stable-run), CircuitBreaker (3 crashes per 5 min opens; 1h → 4h → manual cooldown escalation; sticky alert doesn't auto-clear), HeartbeatMonitor (2s cadence, 3 consecutive misses = host dead per driver-stability.md). Infrastructure: docker SQL Server remapped to host port 14330 to coexist with the native MSSQL14 Galaxy ZB DB instance on 1433; NuGetAuditSuppress applied per-project for two System.Security.Cryptography.Xml advisories that only reach via EF Core Design with PrivateAssets=all (fix ships in 11.0.0-preview); .slnx gains 14 project registrations. Deferred with explicit TODOs in docs/v2/implementation/phase-2-partial-exit-evidence.md: Phase 1 Stream E Admin UI pages (Generations listing + draft-diff-publish, Equipment CRUD with OPC 40010 fields, UNS Areas/Lines tabs, ACLs + permission simulator, Generic JSON config editor, SignalR real-time, Release-Reservation + Merge-Equipment workflows, LDAP login page, AppServer smoke test per decision #142), Phase 2 Stream D (Galaxy MXAccess code lift out of legacy OtOpcUa.Host, dual-service installer, appsettings → DriverConfig migration script, legacy Host deletion — blocked by parity), Phase 2 Stream E (v1 IntegrationTests against v2 topology, Client.CLI walkthrough diff, four 2026-04-13 stability findings regression tests, adversarial review — requires live MXAccess runtime).
2026-04-17 21:35:25 -04:00
Phase 3 PR 24 — Modbus PLC data type extensions. Extends ModbusDataType beyond the textbook Int16/UInt16/Int32/UInt32/Float32 set with Int64/UInt64/Float64 (4-register types), BitInRegister (single bit within a holding register, BitIndex 0-15 LSB-first), and String (ASCII packed 2 chars per register with StringLength-driven sizing). Adds ModbusByteOrder enum on ModbusTagDefinition covering the two word-orderings that matter in the real PLC population: BigEndian (ABCD — Modbus TCP standard, Schneider PLCs that follow it strictly) and WordSwap (CDAB — Siemens S7 family, several Allen-Bradley series, some Modicon families). NormalizeWordOrder helper reverses word pairs in-place for 32-bit values and reverses all four words for 64-bit values (keeps bytes big-endian within each register, which is universal; swaps only the word positions). Internal codec surface switched from (bytes, ModbusDataType) pairs to (bytes, ModbusTagDefinition) because the tag carries the ByteOrder + BitIndex + StringLength context the codec needs; RegisterCount similarly takes the tag so strings can compute ceil(StringLength/2). DriverDataType mapping in MapDataType extended to cover the new logical types — Int64/UInt64 widen to Int32 (PR 25 follow-up: extend DriverDataType enum with Int64 to avoid precision loss), Float64 maps to DriverDataType.Float64, String maps to DriverDataType.String, BitInRegister surfaces as Boolean, all other mappings preserved. BitInRegister writes throw a deliberate InvalidOperationException with a 'read-modify-write' hint — to atomically flip a single bit the driver needs to FC03 the register, OR/AND in the bit, then FC06 it back; that's a separate PR because the bit-modify atomicity story needs a per-register mutex and optional compare-and-write semantics. Everything else (decoder paths for both byte orders, Int64/UInt64/Float64 encode + decode, bit-index extraction across both register halves, String nul-truncation on decode, String nul-padding on encode) ships here. Tests (21 new ModbusDataTypeTests): RegisterCount_returns_correct_register_count_per_type theory (10 rows covering every numeric type); RegisterCount_for_String_rounds_up_to_register_pair theory (5 rows including the 0-char edge case that returns 0 registers); Int32_BigEndian_decodes_ABCD_layout + Int32_WordSwap_decodes_CDAB_layout + Float32_WordSwap_encode_decode_roundtrips (covers the two most-common 32-bit orderings); Int64_BigEndian_roundtrips + UInt64_WordSwap_reverses_four_words (word-swap on 64-bit reverses the four-word layout explicitly, with the test computing the expected wire shape by hand rather than trusting the implementation) + Float64_roundtrips_under_word_swap (3.14159265358979 survives the round-trip with 1e-12 tolerance); BitInRegister_extracts_bit_at_index theory (6 rows including LSB, MSB, and arbitrary bits in a multi-bit mask); BitInRegister_write_is_not_supported_in_PR24 (asserts the exception message steers the reader to the 'read-modify-write' follow-up); String_decodes_ASCII_packed_two_chars_per_register (decodes 'HELLO!' from 3 packed registers with the 'HELLO!'u8 test-only UTF-8 literal which happens to equal the ASCII bytes for this ASCII input); String_decode_truncates_at_first_nul ('Hi' padded with nuls reads back as 'Hi'); String_encode_nul_pads_remaining_bytes (short input writes remaining bytes as 0). Full solution: 0 errors, 217 unit + integration tests pass (22 + 30 new Modbus = 52 Modbus total, 165 pre-existing). ModbusDriver capability footprint now matches the most common industrial PLC workloads — Siemens S7 + Allen-Bradley + Modicon all supported via ByteOrder config without driver forks.
2026-04-18 12:27:12 -04:00
Phase 3 PR 26 — server-layer write authorization gating by role. Per the user's ACL-at-server-layer directive (saved as feedback_acl_at_server_layer.md in memory), write authorization is enforced in DriverNodeManager.OnWriteValue and never delegated to the driver or to driver-specific auth (the v1 Galaxy-provided security path is explicitly not part of v2 — drivers report SecurityClassification as discovery metadata only). New WriteAuthzPolicy static class in Server/Security/ maps SecurityClassification → required role per the table documented in docs/Configuration.md: FreeAccess = no role required (anonymous sessions can write), Operate + SecuredWrite = WriteOperate, Tune = WriteTune, VerifiedWrite + Configure = WriteConfigure, ViewOnly = deny regardless of roles. Role matching is case-insensitive and role requirements do NOT cascade — a session with WriteConfigure can write Configure attributes but needs WriteOperate separately to write Operate attributes; this is deliberate so escalation is an explicit LDAP group assignment, not a hierarchy the policy silently grants. DriverNodeManager gains a _securityByFullRef Dictionary populated during Variable() registration (parallel to the existing _variablesByFullRef) so OnWriteValue can look up the classification in O(1) on the hot path. OnWriteValue casts the session's context.UserIdentity to the new IRoleBearer interface (implemented by OtOpcUaServer.RoleBasedIdentity from PR 19) — empty Roles collection when the session is anonymous; the same WriteAuthzPolicy.IsAllowed check then either short-circuits true (FreeAccess), false (ViewOnly), or walks the roles list looking for the required one. On deny, OnWriteValue logs 'Write denied for {FullRef}: classification=X userRoles=[...]' at Information level (readable trail for operator complaints) and returns BadUserAccessDenied without touching IWritable.WriteAsync — drivers never see a request we'd have refused. IRoleBearer kept as a minimal server-side interface rather than reusing some abstraction from Core.Abstractions because the concept is OPC-UA-session-scoped and doesn't generalize (the driver side has no notion of a user session). Tests — WriteAuthzPolicyTests (17 new cases): FreeAccess allows write with empty role set + arbitrary roles; ViewOnly denies write even with every role; Operate requires WriteOperate; role match is case-insensitive; Operate denies empty role set + wrong role; SecuredWrite shares Operate's requirement; Tune requires WriteTune; Tune denies WriteOperate-only (asserts roles don't cascade — this is the test that catches a future regression where someone 'helpfully' adds a role-escalation table); Configure requires WriteConfigure; VerifiedWrite shares Configure's requirement; multi-role session allowed when any role matches; unrelated roles denied; RequiredRole theory covering all 5 classified-and-mapped rows + null for FreeAccess/ViewOnly special cases. lmx-followups.md follow-up #2 marked DONE with a back-reference to this PR and the memory note. Full Server.Tests Unit suite: 38 pass / 0 fail (17 new WriteAuthz + 14 SecurityConfiguration from PR 19 + 2 NodeBootstrap + 5 others). Server.Tests Integration (Category=Integration) 2 pass — existing PR 17 anonymous-endpoint smoke tests stay green since the read path doesn't hit OnWriteValue.
2026-04-18 13:01:01 -04:00