Per-CLI runbooks (Driver.{Modbus,AbCip,AbLegacy,S7,TwinCAT}.Cli.md) shipped
with #249-#251 but docs/README.md's Client tooling table never grew entries
for them and there was no parent doc pulling the suite together.
Adds:
- docs/DriverClis.md — short parent. Index table, shared-commands callout
(probe / read / write / subscribe), Driver.Cli.Common infrastructure
note (what's shared, marginal cost of adding a sixth CLI), typical
cross-CLI workflows (commissioning, bug reproduction, recipe-write
validation, byte-order debugging), known gaps that cross-ref the
per-CLI docs (AB Legacy ab_server upstream gap, S7 PUT/GET enable,
TwinCAT AMS router, UDT-write refusal), tracking pointer to #249-251.
- docs/README.md — Client tooling table grows 6 rows (DriverClis parent
+ 5 per-CLI). Also corrects the Client.CLI.md row: it's otopcua-cli,
not lmxopcua-cli (renamed in #208).
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
4.4 KiB
Driver test-client CLIs
Five shell-level ad-hoc validation tools, one per native-protocol driver family.
Each mirrors the v1 otopcua-cli shape (probe / read / write / subscribe) against
the same driver the OtOpcUa server uses — so "does the CLI see it?" and
"does the server see it?" are the same question.
| CLI | Protocol | Docs |
|---|---|---|
otopcua-modbus-cli |
Modbus-TCP | Driver.Modbus.Cli.md |
otopcua-abcip-cli |
CIP / EtherNet-IP (Logix symbolic) | Driver.AbCip.Cli.md |
otopcua-ablegacy-cli |
PCCC (SLC / MicroLogix / PLC-5) | Driver.AbLegacy.Cli.md |
otopcua-s7-cli |
S7comm / ISO-on-TCP | Driver.S7.Cli.md |
otopcua-twincat-cli |
Beckhoff ADS | Driver.TwinCAT.Cli.md |
The OPC UA client CLI lives separately and predates this suite —
see Client.CLI.md for otopcua-cli.
Shared commands
Every driver CLI exposes the same four verbs:
probe— open a session, read one sentinel tag, print driver health. Fastest "is the device talking?" check.read— synthesise a one-tag driver config from--type/--address(or--tag/--symbol) flags, read once, print the snapshot. No extra config file needed.write— same shape plus--value. Values parse per--typeusing invariant culture. Booleans accepttrue/false/1/0/yes/no/on/off. Writes are non-idempotent by default — a timeout after the device already applied the write will not auto-retry (plan decisions #44, #45).subscribe— long-running data-change stream until Ctrl+C. Uses native push where available (TwinCAT ADS notifications) and falls back to polling (PollGroupEngine) where the protocol has no push (Modbus, AB, S7).
Shared infrastructure
All five CLIs depend on src/ZB.MOM.WW.OtOpcUa.Driver.Cli.Common/:
DriverCommandBase—--verbose+ Serilog configuration + the abstractTimeoutsurface every protocol-specific base overrides with its own default.SnapshotFormatter— consistent output across every CLI: tag / value / status / source-time / server-time for single reads, a 4-column table for batches,Write <tag>: 0x... (Name)for writes, and one line per change event for subscriptions. OPC UA status codes render as0xXXXXXXXX (Name)with a shortlist forGood/Bad*/Uncertain; unknown codes fall back to hex.
Writing a sixth CLI (hypothetical Galaxy / FOCAS) costs roughly 150 lines:
a {Family}CommandBase + four thin command classes that hand their flag
values to the already-shipped driver.
Typical cross-CLI workflows
- Commissioning a new device —
probefirst, thenreada known-good tag. If the device is up + talking the protocol, both pass; if the tag is wrong you'll see the read fail with a protocol-specific error. - Reproducing a production bug —
subscribeto the tag the bug report names, then have the operator run the scenario. You get an HH:mm:ss.fff timeline of exactly when each value changed. - Validating a recipe write —
write+readback. If the server's write path would have done anything different, the CLI would have too. - Byte-order / word-swap debugging —
readwith one--byte-order, then the other. The plausible result identifies the correct setting for that device family. (Modbus, S7.)
Known gaps
- AB Legacy PCCC wire-level against the ab_server Docker simulator is upstream-broken — see the "Known limitations" section in Driver.AbLegacy.Cli.md. Pointing the CLI at real SLC / MicroLogix / PLC-5 hardware or a RSEmulate 500 golden-box works as expected.
- S7 PUT/GET communication must be enabled in TIA Portal for any S7-1200/1500. See Driver.S7.Cli.md.
- TwinCAT AMS router must be reachable (local XAR, standalone Router NuGet, or authorised remote route). See Driver.TwinCAT.Cli.md.
- Structure / UDT writes are refused by the AB CIP + TwinCAT CLIs — whole-UDT writes need a declared member layout that belongs in a real driver config, not a one-shot flag.
Tracking
Tasks #249 / #250 / #251 shipped the suite. 122 unit tests cumulative
(16 shared-lib + 106 across the five CLIs) — run
dotnet test tests/ZB.MOM.WW.OtOpcUa.Driver.Cli.Common.Tests +
tests/ZB.MOM.WW.OtOpcUa.Driver.*.Cli.Tests to re-verify.