TwinCATDriverProbe ran a first-phase TCP check against the AmsNetId's first four octets on the AMS port (801/851). An AmsNetId is not an IP and the AMS port is not a TCP port, so Test Connect timed out against every real runtime (Z35474: dialled 5.118.56.93, an unrelated public host). The probe now opens no socket of its own: it takes the driver's path, AdsClient.Connect + ReadStateAsync through the local AMS router, bounded by the probe budget (Task.Run + WaitAsync), and classifies failures as no local AMS router / no route or target unreachable / timeout / other. The degrade-to-green 'TCP reachability only' outcome is gone - with no TCP check nothing was contacted, so a missing router is reported red. Tests: the regression test listens on the AmsNetId-derived endpoint and asserts no connection arrives (fails on the old probe); classification and budget tests drive the handshake through an internal seam. Claude-Session: https://claude.ai/code/session_01GT67AD99zQQqpLCVm3p7xk
11 KiB
Test-Connect Probes — Protocol Handshakes
Each driver's Test-Connect button in the AdminUI runs a probe against the
form's current config (never the persisted row, never the live driver actor).
Before Phase 5 (shipped 2026-06-16) every probe was a bare TCP ConnectAsync
— a live-but-rejecting device showed a healthy green tick, and the operator
only discovered the truth when the driver faulted at deploy. Phase 5 replaced
each TCP-only probe with a real protocol handshake so a reachable-but-wrong
or actively-rejecting endpoint now reads RED.
The IDriverProbe / DriverProbeResult contract and DI registration are
unchanged. Probes run in a transient actor with a timeout clamp of 1–60 s
and must not mutate any state.
For the AdminUI probe flow (button → AdminOperationsActor → transient probe
actor), see
docs/plans/2026-05-28-adminui-driver-pages-design.md
§4.
Result contract
All probes return a consistent DriverProbeResult(bool Ok, string? Message, TimeSpan? Latency).
The message templates below are uniform across all 8 drivers:
| Outcome | Ok |
Message template |
|---|---|---|
| TCP connect fails | false |
"Connect failed: {SocketErrorCode}" |
| TCP ok + handshake ok | true |
driver-specific descriptive string (see table below) |
| TCP ok but handshake rejected | false |
"Reachable at {host}:{port} but {proto} handshake failed: {detail}" |
| Timeout | false |
"Probe timed out after {n}s." |
The third row is the key new behavior: a reachable device that answers on the
port but rejects the protocol-level handshake now surfaces a false result
with a human-readable explanation rather than a false-green TCP-open tick.
Per-driver handshake
| Driver | Handshake | Ok message | Dev-rig target |
|---|---|---|---|
| Modbus | FC03 (Read Holding Registers, qty 1 @ addr 0) via ModbusTcpTransport. A Modbus exception PDU still proves a real Modbus device → Ok. A non-MBAP reply → handshake fail. |
"Modbus FC03 OK" |
10.100.0.35:5020 (Modbus sim) |
| OpcUaClient | DiscoveryClient.GetEndpointsAsync — no session, no app-cert, no auth. ≥ 1 endpoint → Ok. A non-OPC-UA TCP server throws or times out → handshake fail. |
"OPC UA: N endpoint(s)" |
opc.tcp://10.100.0.35:50000 (opc-plc) |
| S7 | Plc.OpenAsync (COTP CR/CC + S7 setup-communication), check IsConnected, then Close. Wrong rack/slot or a non-S7 server causes OpenAsync to throw → handshake fail. |
"S7 connected (CPU …)" |
10.100.0.35:1102 (python-snap7 sim) |
| AbCip | libplctag Tag InitializeAsync (EIP session + CIP Forward Open). A CIP-level error such as tag-not-found still proves the controller answered CIP → Ok. A session/ForwardOpen/connect error → handshake fail. |
"CIP session OK" |
10.100.0.35:44818 (CIP sim) |
| AbLegacy | Same libplctag InitializeAsync handshake as AbCip, PCCC protocol family. |
"CIP session OK" (PCCC family) |
Deferred — no PLC5/SLC sim |
| TwinCAT | AdsClient.Connect + ReadStateAsync through the local AMS router — no TCP pre-check. See TwinCAT: no TCP pre-check below. |
"ADS state: {state}" |
Z35474 (production TC3 press, read-only, via an in-process TcpRouter) |
| FOCAS | cnc_allclibhndl3 via a direct DllImport("fwlib32") in the probe. See degrade semantics below. |
"FOCAS handle OK" |
Deferred — no CNC + FWLIB |
| Galaxy | gRPC unary call to GalaxyRepository.TestConnection on the configured mxaccessgw endpoint. See auth-rejection rule below. |
"gateway gRPC OK" |
http://10.100.0.48:5120 (mxaccessgw) |
| Heidenhain | LSV2 A_LG INSPECT (password resolved from its secret:/env: reference) + R_VR, through the same read-only allowlist as the driver; a refusal or malformed version record → fail. No logout — the socket close ends the session. |
"LSV2 INSPECT session OK at host:port: <model> NC <version>" |
Deferred — no LSV2 control; simulator-proven |
| MQTT | One MQTT CONNECT (no SUBSCRIBE, no publish) under a -probe--suffixed client id, then disconnect. A rejected CONNACK is a returned result code, not an exception — MQTTnet 5 does not throw — so the probe inspects ResultCode and reuses the driver's own DescribeConnackRejection, making the button and the running driver word a rejection identically. |
"MQTT CONNECT OK" |
10.100.0.35:8883 (Mosquitto TLS+auth fixture) |
Historian.Wonderware had a TCP Hello→HelloAck handshake probe before Phase 5, but the
Wonderware historian backend (and its driver-type / probe) has since been retired — the historian
backend is now the external HistorianGateway (a gRPC client package, not a probed IDriver). See
Historian.Wonderware.md (retired stub) and ../Historian.md.
Degrade semantics
Some drivers have environmental constraints that can prevent the handshake from running on certain hosts. The degradation principle is: the probe must never produce a result worse than today's TCP-only probe. A genuine protocol rejection from a reachable device is a correct RED; an inability to run the handshake at all (no FWLIB) degrades to the existing TCP-reachability message — still a green tick but annotated. TwinCAT no longer degrades (see below).
TwinCAT: no TCP pre-check
TwinCAT is the exception to the "TCP connect fails" row above: it opens no socket of its own
(#863). The driver has no IP field — an AMS Net ID is a Beckhoff identifier the AMS router maps to a
host through its route table, and the AMS port (801/851) is not a TCP port. The probe therefore takes
exactly the driver's path (AdsTwinCATClient.ConnectAsync): AdsClient.Connect(netId, port) through
the local AMS router (TwinCAT XAR, or Beckhoff.TwinCAT.Ads.TcpRouter hosted in-process), then one
read-only ReadStateAsync, all inside the probe budget. Until #863 a first-phase check dialled the Net
ID's first four octets as an IPv4 address on the AMS port — for Z35474 (5.118.56.93.1.1) an
unrelated public host — so Test Connect timed out against every real runtime.
| Outcome | Ok |
Message |
|---|---|---|
| ReadState succeeds | true |
"ADS state: {state}" (Run / Config / Stop) |
No local AMS router (Beckhoff "Check for a running TwinCAT router instance!", ClientPortNotOpen, router not active, ADS client cannot load) |
false |
"No local AMS router on this host — start TwinCAT XAR or host the Beckhoff TcpRouter; the target was not contacted (…)" |
Router answered but cannot reach the target (TargetMachineNotFound, TargetPortNotFound, port/access refused, host unreachable) |
false |
"No route to {netId}:{port} or target unreachable: {code} — check the local AMS router has a route …" |
| Sync/device timeout code, or the budget expired | false |
"Probe timed out after {n}s waiting for ADS state from {netId}:{port} …" |
| Any other ADS error | false |
"ADS handshake with {netId}:{port} failed: {code}" |
There is no degrade-to-green any more: with no TCP check, a host that cannot run the handshake has contacted nothing, so it reports the missing router rather than a green tick. A stock admin node has no AMS router, so TwinCAT Test Connect is red there by design — the driver needs the same router.
FOCAS degrade
On a Windows host with the FANUC FWLIB shared library present:
cnc_allclibhndl3is called via a directDllImport("fwlib32")declared in the probe (the productionWire.WireFocasClientis a pure-managed FOCAS/2 TCP client, not an FWLIB P/Invoke, so the probe carries its own native binding). A successful handle allocation →Ok=true,"FOCAS handle OK".- A CNC-level rejection → handshake fail.
On dev, Linux, or macOS (no native FWLIB — UnimplementedFocasClientFactory
gates the driver):
DllNotFoundException/NotSupportedExceptionis caught and the probe degrades to TCP-reachability:Ok=true,"(FOCAS handshake unavailable on this host — FWLIB absent, TCP reachability only)".
Galaxy auth-rejection rule
The probe builds the gRPC channel from the form's config and issues one
lightweight unary call. It does not resolve secretref: secrets — the
key string in the transient config (possibly empty or unresolved) is used as-is.
Unavailable/ transport failure →Ok=false(gateway is down or unreachable).Unauthenticated/PermissionDenied→Ok=true,"gateway reachable & speaking gRPC (auth not checked)"— an auth rejection proves a live mxaccessgw gRPC server. This is the correct result: the driver's own session-layer will handle auth; the probe is testing reachability only.
The mxaccessgw client surfaces a rejected key as a typed
MxGatewayAuthenticationException / MxGatewayAuthorizationException, not a
raw RpcException — the probe catches both and maps them to the reachable result
above. (Live verification on 10.100.0.48:5120 with no key returns
MxGatewayAuthenticationException("Missing or invalid API key.") → Ok=true.)
Config note:
UseTlsmust match the endpoint scheme —UseTls:falsefor anhttp://(h2c) gateway,UseTls:trueforhttps://. A mismatch fails the client's own validation (the same constraint the Galaxy driver enforces).
Live-verify scope
| Driver | Live-verify status | Notes |
|---|---|---|
| Modbus | Verified | Dev-rig sim 10.100.0.35:5020; green vs sim, RED vs wrong port / non-Modbus server, timeout vs black-hole IP |
| OpcUaClient | Verified | opc-plc 10.100.0.35:50000; same three-scenario matrix |
| S7 | Verified | python-snap7 10.100.0.35:1102 |
| AbCip | Verified | CIP sim 10.100.0.35:44818 |
| Galaxy | Verified | mxaccessgw 10.100.0.48:5120; Unauthenticated reply counts as Ok |
| MQTT | Verified | Mosquitto 10.100.0.35:8883; live suite covers TLS+auth Ok, foreign-CA rejection, and wrong-password rejection surfacing rather than reporting healthy |
| AbLegacy | Deferred | No PLC5/SLC sim; unit-proven + code path identical to AbCip |
| TwinCAT | Deferred | No ADS target; unit-proven + degrade guard tested |
| FOCAS | Deferred | No CNC + FWLIB on dev host; degrade guard is the CI-observable path |
| Heidenhain | Deferred | No LSV2 control; probe path shared with the simulator-tested driver (#803) |
Implementation references
- Phase 5 design:
docs/plans/2026-06-16-stillpending-phase-5-probes-design.md - Parent roadmap:
docs/plans/2026-06-15-stillpending-backlog-design.md§Phase 5 - AdminUI probe flow:
docs/plans/2026-05-28-adminui-driver-pages-design.md§4 - Per-driver probe implementations:
src/Drivers/ZB.MOM.WW.OtOpcUa.Driver.<Type>/<Type>DriverProbe.cs IDriverProbecontract:src/Core/ZB.MOM.WW.OtOpcUa.Core.Abstractions/IDriverProbe.cs- Probe dispatch + timeout clamp:
src/Server/ZB.MOM.WW.OtOpcUa.Host/Actors/AdminOperationsActor.cs(around line 284)