Joseph Doherty f3850f8914 Phase 6.1 Stream A.5/A.6 — WriteIdempotent flag on DriverAttributeInfo + Modbus/S7 tag records + FlakeyDriver integration tests
Per-tag opt-in for write-retry per docs/v2/plan.md decisions #44, #45, #143.
Default is false — writes never auto-retry unless the driver author has marked
the tag as safe to replay.

Core.Abstractions:
- DriverAttributeInfo gains `bool WriteIdempotent = false` at the end of the
  positional record (back-compatible; every existing call site uses the default).

Driver.Modbus:
- ModbusTagDefinition gains `bool WriteIdempotent = false`. Safe candidates
  documented in the param XML: holding-register set-points, configuration
  registers. Unsafe: edge-triggered coils, counter-increment addresses.
- ModbusDriver.DiscoverAsync propagates t.WriteIdempotent into
  DriverAttributeInfo.WriteIdempotent.

Driver.S7:
- S7TagDefinition gains `bool WriteIdempotent = false`. Safe candidates:
  DB word/dword set-points, configuration DBs. Unsafe: M/Q bits that drive
  edge-triggered program routines.
- S7Driver.DiscoverAsync propagates the flag.

Stream A.5 integration tests (FlakeyDriverIntegrationTests, 4 new) exercise
the invoker + flaky-driver contract the plan enumerates:
- Read with 5 transient failures succeeds on the 6th attempt (RetryCount=10).
- Non-idempotent write with RetryCount=5 configured still fails on the first
  failure — no replay (decision #44 guard at the ExecuteWriteAsync surface).
- Idempotent write with 2 transient failures succeeds on the 3rd attempt.
- Two hosts on the same driver have independent breakers — dead-host trips
  its breaker but live-host's first call still succeeds.

Propagation tests:
- ModbusDriverTests: SetPoint WriteIdempotent=true flows into
  DriverAttributeInfo; PulseCoil default=false.
- S7DiscoveryAndSubscribeTests: same pattern for DBx SetPoint vs M-bit.

Full solution dotnet test: 947 passing (baseline 906, +41 net across Stream A
so far). Pre-existing Client.CLI Subscribe flake unchanged.

Stream A's remaining work (wiring CapabilityInvoker into DriverNodeManager's
OnReadValue / OnWriteValue / History / Subscribe dispatch paths) is the
server-side integration piece + needs DI wiring for the pipeline builder —
lands in the next PR on this branch.

Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
2026-04-19 07:16:21 -04:00

121 lines
5.3 KiB
C#

using S7NetCpuType = global::S7.Net.CpuType;
namespace ZB.MOM.WW.OtOpcUa.Driver.S7;
/// <summary>
/// Siemens S7 native (S7comm / ISO-on-TCP port 102) driver configuration. Bound from the
/// driver's <c>DriverConfig</c> JSON at <c>DriverHost.RegisterAsync</c>. Unlike the Modbus
/// driver the S7 driver uses the PLC's *native* protocol — port 102 ISO-on-TCP rather
/// than Modbus's 502, and S7-specific area codes (DB, M, I, Q) rather than holding-
/// register / coil tables.
/// </summary>
/// <remarks>
/// <para>
/// The driver requires <b>PUT/GET communication enabled</b> in the TIA Portal
/// hardware config for S7-1200/1500. The factory default disables PUT/GET access,
/// so a driver configured against a freshly-flashed CPU will see a hard error
/// (S7.Net surfaces it as <c>Plc.ReadAsync</c> returning <c>ErrorCode.Accessing</c>).
/// The driver maps that specifically to <c>BadNotSupported</c> and flags it as a
/// configuration alert rather than a transient fault — blind Polly retry is wasted
/// effort when the PLC will keep refusing every request.
/// </para>
/// <para>
/// See <c>docs/v2/driver-specs.md</c> §5 for the full specification.
/// </para>
/// </remarks>
public sealed class S7DriverOptions
{
/// <summary>PLC IP address or hostname.</summary>
public string Host { get; init; } = "127.0.0.1";
/// <summary>TCP port. ISO-on-TCP is 102 on every S7 model; override only for unusual NAT setups.</summary>
public int Port { get; init; } = 102;
/// <summary>
/// CPU family. Determines the ISO-TSAP slot byte that S7.Net uses during connection
/// setup — pick the family that matches the target PLC exactly.
/// </summary>
public S7NetCpuType CpuType { get; init; } = S7NetCpuType.S71500;
/// <summary>
/// Hardware rack number. Almost always 0; relevant only for distributed S7-400 racks
/// with multiple CPUs.
/// </summary>
public short Rack { get; init; } = 0;
/// <summary>
/// CPU slot. Conventions per family: S7-300 = slot 2, S7-400 = slot 2 or 3,
/// S7-1200 / S7-1500 = slot 0 (onboard PN). S7.Net uses this to build the remote
/// TSAP. Wrong slot → connection refused during handshake.
/// </summary>
public short Slot { get; init; } = 0;
/// <summary>Connect + per-operation timeout.</summary>
public TimeSpan Timeout { get; init; } = TimeSpan.FromSeconds(5);
/// <summary>Pre-declared tag map. S7 has a symbol-table protocol but S7.Net does not expose it, so the driver operates off a static tag list configured per-site. Address grammar documented in S7AddressParser (PR 63).</summary>
public IReadOnlyList<S7TagDefinition> Tags { get; init; } = [];
/// <summary>
/// Background connectivity-probe settings. When enabled, the driver runs a tick loop
/// that issues a cheap read against <see cref="S7ProbeOptions.ProbeAddress"/> every
/// <see cref="S7ProbeOptions.Interval"/> and raises <c>OnHostStatusChanged</c> on
/// Running ↔ Stopped transitions.
/// </summary>
public S7ProbeOptions Probe { get; init; } = new();
}
public sealed class S7ProbeOptions
{
public bool Enabled { get; init; } = true;
public TimeSpan Interval { get; init; } = TimeSpan.FromSeconds(5);
public TimeSpan Timeout { get; init; } = TimeSpan.FromSeconds(2);
/// <summary>
/// Address to probe for liveness. DB1.DBW0 is the convention if the PLC project
/// reserves a small fingerprint DB for health checks (per <c>docs/v2/s7.md</c>);
/// if not, pick any valid Merker word like <c>MW0</c>.
/// </summary>
public string ProbeAddress { get; init; } = "MW0";
}
/// <summary>
/// One S7 variable as exposed by the driver. Addresses use S7.Net syntax — see
/// <c>S7AddressParser</c> (PR 63) for the grammar.
/// </summary>
/// <param name="Name">Tag name; OPC UA browse name + driver full reference.</param>
/// <param name="Address">S7 address string, e.g. <c>DB1.DBW0</c>, <c>M0.0</c>, <c>I0.0</c>, <c>QD4</c>. Grammar documented in <c>S7AddressParser</c> (PR 63).</param>
/// <param name="DataType">Logical data type — drives the underlying S7.Net read/write width.</param>
/// <param name="Writable">When true the driver accepts writes for this tag.</param>
/// <param name="StringLength">For <c>DataType = String</c>: S7-string max length. Default 254 (S7 max).</param>
/// <param name="WriteIdempotent">
/// Per <c>docs/v2/plan.md</c> decisions #44, #45, #143 — flag a tag as safe to replay on
/// write timeout / failure. Default <c>false</c>; writes do not auto-retry. Safe candidates
/// on S7: DB word/dword set-points holding analog values, configuration DBs where the same
/// value can be written again without side-effects. Unsafe: M (merker) bits or Q (output)
/// coils that drive edge-triggered routines in the PLC program.
/// </param>
public sealed record S7TagDefinition(
string Name,
string Address,
S7DataType DataType,
bool Writable = true,
int StringLength = 254,
bool WriteIdempotent = false);
public enum S7DataType
{
Bool,
Byte,
Int16,
UInt16,
Int32,
UInt32,
Int64,
UInt64,
Float32,
Float64,
String,
DateTime,
}