Since #808 an UNS folder with no placement in the generation is denied (fail closed), so the matrix's ad hoc "Eq" folder made every UNS case fail with BadUserAccessDenied on the candidate server. The fixture now supplies unsFolderScopes (+ the alarm's tagReferencingEquipment) as a deployed generation does. An unplaced "Unplaced" UNS folder is kept as a negative control: the Shared client leg requires it denied against a #808+ server with the ACL on. No server authorization code changed. Claude-Session: https://claude.ai/code/session_01GT67ACmpMR7b9LGRPLijMi
Actual ScadaBridge consumer compatibility
This isolated process references the real ScadaBridge OpcUaDataConnection and
RealOpcUaClient, with their own dependency graph. It never loads the candidate
SDK into that process. The verified consumer source is
0e89966da670e289bd875166295bb0e85d8cf8b2, pinned to SDK 1.5.378.106.
Build with an explicit clean consumer checkout:
dotnet build scripts/validation/scadabridge-sdk-compatibility/Probe.csproj \
-c Release -p:ScadaBridgeSourceRoot=/absolute/ScadaBridge
First build the separate application hosts with the parent
scripts/e2e/test-opcua-sdk-compatibility.ps1 harness. Then choose a new output
directory and pass its original and candidate ProcessHost.dll paths:
python3 scripts/validation/scadabridge-sdk-compatibility/run.py \
--baseline-host /absolute/matrix/build-baseline/bin/Release/net10.0/ProcessHost.dll \
--candidate-host /absolute/matrix/build-candidate/bin/Release/net10.0/ProcessHost.dll \
--probe scripts/validation/scadabridge-sdk-compatibility/bin/Release/net10.0/Probe.dll \
--results /absolute/fresh-consumer-evidence
The helper runs each application version with None, Sign and SignAndEncrypt,
plus two trust negative controls per secure profile (server does not trust the
client, client does not trust the server) that must fail closed. None and Sign
are enabled only in their own test fixtures (OPCUA_MATRIX_SERVER_SECURITY=none|sign);
the ordinary compatibility host remains strict SignAndEncrypt. Before each secure
leg the probe's prepare step provisions the consumer identity through
ScadaBridge's own certificate code and exports only its public certificate, which
the runner places in the server's trusted store before the server starts.
OPCUA_MATRIX_ACL=off disables the server's node-ACL check. The fixture's Eq equipment folder is placed in the
authority snapshot (unsFolderScopes, as a deployed generation does since lmxopcua#808, fixed in lmxopcua#888), so
the UNS cases pass with the ACL on and off; an unplaced Unplaced UNS folder is kept as a negative control that the
Shared client leg requires to stay denied with the ACL on. The task key is
generated per process pair, issuer/trusted/rejected stores are task-local, and
server public certificates are explicitly copied. Autoaccept remains false.
Never commit an entire output directory: it contains the fixture's private PKI.
The consumed subset covers API-key activation, raw/UNS scalar and Int32[] roundtrips, durable hierarchical browse including the native alarm, data quality and timestamps on raw and UNS subscriptions, alarm filter/ConditionRefresh, disconnect/reconnect, and (ScadaBridge#125) a Server-object alarm subscription on the reconnected session whose ConditionRefresh must replay the active native condition (11 cases per trusted leg). History and Part 9 acknowledgment are not exposed by the inspected consumer interfaces; the parent Shared/CLI matrix covers those application services instead.
ScadaBridge#121 (consumer never configured an application certificate) is
fixed in ScadaBridge ff835447/36c64a6b. Re-run 2026-11-12 with ScadaBridge
424db155: None, Sign and SignAndEncrypt 9/9 against the SDK 1.5.378 baseline
(83ed880e), the SDK 2.0.1 candidate (ebdc5892) and master 182fb353 with
ACL off; all trust negative controls failed closed. The runner retains the
nonzero result and each actual failure; it does not loosen trust or change
expected results to return success. No ScadaBridge production source or user PKI is modified.
Redundancy failover (ScadaBridge#125)
run.py also runs a failover suite (--suites matrix,failover, both by
default; --versions candidate runs one application version only). Each leg
starts two independent servers and runs Probe failover <primary> <backup> <mode> <dir>, which drives ScadaBridge's own DataConnectionActor (the
production primary/backup state machine, the real DataConnectionFactory,
production DataConnectionOptions defaults, FailoverRetryCount = 3). Once the
probe has a steady primary (Good values on a raw and a UNS tag, a write, the
Server-object alarm subscription with its ConditionRefresh) it writes
primary-ready; the runner then loses the primary and writes primary-killed.
The probe must then see Bad quality pushed, "Connected to backup", Good values
whose first value is the backup's own (proving the source), a fresh
ConditionRefresh replaying the native condition, and a write through the backup.
Two loss shapes run per security mode (--failover-modes None,SignAndEncrypt,
--failover-loss kill,freeze):
kill— SIGKILL; the OS closes the primary's sockets, so the client sees the loss at once.freeze— SIGSTOP; the sockets stay open and silent (hung host / dead link), so only the consumer's session keep-alive can detect it.
ScadaBridge does not read ServiceLevel/ServerRedundancy: its failover is
endpoint-level (primary/backup connection details), so two independent fixture
servers exercise exactly what it consumes. rig-failover.sh <Probe.dll> <dir>
runs the same probe against the real local docker-dev pair (central-1 :4840,
central-2 :4841), docker kills central-1 once the primary is steady and
starts it again afterwards. The rig admits anonymous sessions read-only and has
no active native alarm, so that variant checks values and ConditionRefresh
completion only. Local docker-dev only; never point it at a wonder box.
Run 2026-11-12 (ScadaBridge#125) with ScadaBridge 94ae1860 (SDK client
1.5.378.106), ACL off, against the SDK 1.5.378.182 baseline (83ed880e) and
master a28adba2 (SDK 2.0.1): matrix 11/11 in None, Sign and SignAndEncrypt on
both, all 8 trust controls failed closed (0x80130000 / 0x801A0000); failover 8/8
legs (11/11 cases each). Loss-to-backup timings are the same on both versions:
kill about 20 s (three 5 s reconnect attempts, then the backup), freeze about
20 s to detect and 86–130 s to reach the backup, because each reconnect attempt
waits out a connect timeout against the silent primary. rig-failover.sh passed
9/9 against the docker-dev pair (image SDK 2.0.1), central-1 killed, about 20 s
to central-2.