AB Legacy — DH+ via 1756-DHRIO bridging

PR ablegacy-13 / #256. The AB Legacy driver can address a PLC-5 sitting on a DH+ link by routing CIP requests through a 1756-DHRIO module installed in a ControlLogix chassis. This is the canonical way to keep an installed-base PLC-5 fleet alive after the chassis- level migration to ControlLogix; the DHRIO module exposes a DH+ "side" that talks to the legacy PLC-5 / SLC-DH+ peers and a backplane "side" that the ControlLogix CPU + Ethernet bridge can route through.

Wire layout

OtOpcUa server  ──EtherNet/IP──►  1756-EN2T (slot 0)  ──backplane──►  1756-DHRIO (slot N)  ──DH+──►  PLC-5

Two CIP hops:

  1. Backplane — port 1, slot <N> (the slot the DHRIO module lives in).
  2. DH+ — port 2, station <S> (the DH+ node address of the target PLC-5, in octal).

Resulting CIP path: 1,<N>,2,<S>.

The first port 1 is always the backplane; port 2 is the DH+ side of the 1756-DHRIO module. This mirrors the convention Rockwell uses in RSLinx + RSLogix 5.

Octal station number

The DH+ network was specified with octal node addresses. Rockwell tooling displays them in octal too (RSLogix 5 → "DH+ Node Address" field on the controller properties dialog). The driver follows suit — the station segment of the CIP path must be parsed as octal (digits 0..7 only; 8, 9, and multi-byte garbage are rejected).

DH+ addresses run 0..77 octal == 0..63 decimal. Quick reference:

Octal Decimal Octal Decimal Octal Decimal Octal Decimal
00 0 20 16 40 32 60 48
01 1 21 17 41 33 61 49
02 2 22 18 42 34 62 50
03 3 23 19 43 35 63 51
04 4 24 20 44 36 64 52
05 5 25 21 45 37 65 53
06 6 26 22 46 38 66 54
07 7 27 23 47 39 67 55
10 8 30 24 50 40 70 56
11 9 31 25 51 41 71 57
12 10 32 26 52 42 72 58
13 11 33 27 53 43 73 59
14 12 34 28 54 44 74 60
15 13 35 29 55 45 75 61
16 14 36 30 56 46 76 62
17 15 37 31 57 47 77 63

Anything past 77 octal (i.e. decimal > 63) is invalid on a real DH+ network and rejected by the parser.

PLC-5 only

DHRIO bridging is PLC-5-only. The driver enforces this at AbLegacyDriver.InitializeAsync time: a DH+ bridge path combined with PlcFamily=Slc500 / MicroLogix / LogixPccc throws InvalidOperationException("DHRIO bridging is PLC-5-only") immediately rather than letting reads silently fail with BadCommunicationError on the wire.

Background: the 1756-DHRIO module only speaks DH+ to PLC-5 / SLC-DH+ peers, and libplctag's PCCC stack only exposes the PLC-5 side. SLC 5/04 boxes on DH+ can be physically reached through a DHRIO module, but the protocol stack needed to drive them isn't exposed by libplctag — out of scope for this driver.

CLI worked example

PLC-5 at DH+ node 07 (octal == 7 decimal), DHRIO module in slot 3, gateway 192.168.1.10:

otopcua-ablegacy-cli probe `
    -g ab://192.168.1.10/1,3,2,07 `
    -P Plc5 `
    -a N7:0
# Read N7:10 from the PLC-5 across the DHRIO bridge
otopcua-ablegacy-cli read `
    -g ab://192.168.1.10/1,3,2,07 `
    -P Plc5 `
    -a N7:10 `
    -t Int

The driver surfaces the parsed bridge form on the host-address record: BackplaneSlot=3, DhPlusPort=2, DhPlusStation=7 (decimal-translated). Use those values when reading driver-diagnostics output to confirm the bridge was recognised — a non-bridge CIP path leaves all three fields null.

Manual smoke procedure

There is no automated end-to-end coverage for DH+ bridging because the only path to wire-level validation is real hardware (libplctag's ab_server Docker image doesn't simulate the DHRIO + DH+ + PLC-5 stack). The unit-test layer covers parser positive / negative cases.

Hardware smoke checklist:

  1. Confirm the 1756-DHRIO module is present in the target ControlLogix chassis. RSLinx Classic should show DH+, 1 under the chassis tree with the PLC-5 nodes enumerated underneath.

  2. Note the DHRIO module's slot number (the <N> in 1,<N>,2,<S>).

  3. Note the target PLC-5's DH+ node address — read it off the front-panel switch bank, or the controller properties in RSLogix 5. Read it as octal.

  4. From an OtOpcUa box that can reach the EtherNet/IP gateway:

    otopcua-ablegacy-cli probe -g ab://<gateway>/1,<slot>,2,<station-octal> -P Plc5 -a S:0
    

    S:0 (status file word 0) is non-destructive and present on every PLC-5.

  5. If the probe succeeds, exercise an N file read against a known non-zero address. Compare against the value displayed in RSLogix 5 → Online → Data → N7.

If the probe fails with BadCommunicationError:

  • Wrong slot number — re-check via RSLinx.
  • Wrong octal node — convert from RSLogix 5's display value (already octal); a decimal-thinking conversion mistake is the most common smoke failure.
  • DHRIO module's DH+ baud rate doesn't match the PLC-5's switch setting (57.6k / 115.2k / 230.4k) — driver-side problem this can't paper over.
  • A scanner on the DHRIO is in scheduled-mode and starving unscheduled PCCC traffic — bump the DHRIO's unscheduled-message slice in RSLogix 5000.